6.6 Assembly
Figure 3 Mounting and removing
Mount the module on a 35 mm DIN rail according to EN
60715.
When using the DIN rail connector, first place it into the
DIN rail (see A – C). It is used to bridge the power supply.
It is also absolutely vital that you snap the module and the
DIN rail connector into position in the correct direction:
the snap-on foot should be at the bottom and the connec-
tor on the left.
6.7 Connecting the wires
The module is available in two connection versions:
Screw terminal blocks (for MINI MCR-SL-PTB-FM)
Spring-cage terminal blocks (for MINI MCR-SL-PTB-FM-
SP)
Screw connection:
Figure 4 Screw connection
Insert the wire into the corresponding connection terminal
block.
Use a screwdriver to tighten the screw in the opening
above the connection terminal block.
Spring-cage connection:
Figure 5 Spring-cage connection
Insert a screwdriver into the opening above the connec-
tion terminal block.
Insert the wire into the corresponding connection terminal
block.
For additional mechanical redundancy, two
power terminals and two fault monitoring mod-
ules can be used. Only one supply may be con-
nected to each power terminal. In the second
fault monitoring module, fault monitoring of ex-
ternal measuring transducers must be deacti-
vated because evaluation can only take place
via a module in a group.
D
E
C
B
A
www.interface.phoenixcontact.com
Serial No. XXXXXXXX
A
B
www.interface.phoenixcontact.com
Serial No. XXXXXXXX
A
B
MINI MCR-SL-PTB-FM
105449_en_00 8
PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany
www.phoenixcontact.com
7Fault monitoring FM
Fault monitoring simplifies error evaluation in multi-channel
isolation amplifier applications using a group error message.
7.1 Fault monitoring for group error detection
Use MINIAnalog signal conditioners that support fault
monitoring.
Connect these signal conditioners to the MINIMCR-SL-
FM-RC(-SP)-NC fault monitoring module via the DIN rail
connector .
Detected errors on the signal input of a MINIAnalog isolation
amplifier or in the isolation amplifier are reported to the fault
monitoring module via the DIN rail connector. The module re-
ports the error centrally via an N/C contact.
7.2 Fault monitoring for redundancy monitoring
With "supply via power terminal", the fault monitoring module
can be used to monitor the supply voltage in the group. Fail-
ure of the supply voltage generates a central message via an
N/C contact.
Install a power terminal and a fault monitoring module of
the same shape side-by-side without spacing.
Bridge terminals 1 to 4 of the power terminal with termi-
nals 1 to 4 of the fault monitoring module. Use the provid-
ed plug-in bridges FBS2-6 (Order No. 3030336) or
normal cables.
8Diagnostic indicator
The green LEDs on the front indicate that the relevant
supply voltages are present on the DIN rail connector.
Red LEDs light up when supply voltages are connected
to the wrong poles. In the case of a correctly connected
supply voltage, the red LED goes out.