ADE7761B
Rev. 0 | Page 18 of 24
Fault with Active Input Greater Than Inactive Input
If V
1A
is the active current input (that is, being used for billing),
and the voltage signal on V
1B
(inactive input) falls below 93.75%
of V
1A
, the fault indicator becomes active. Both analog inputs
are filtered and averaged to prevent false triggering of this logic
output. As a consequence of the filtering, there is a time delay of
approximately 3 sec on the Logic Output FAULT after the fault
event. The FAULT logic output is independent of any activity on
the F1 or F2 outputs.
Figure 28 shows one condition under
which FAULT becomes active. Because V
1A
is the active input
and it is still greater than V
1B
, billing is maintained on V
1A
; that
is, no swap to the V
1B
input occurs. V
1A
remains the active input.
V
1B
V
1N
V
1A
AGND
FILTER
AND
COMPARE
TO
MULTIPLIER
FAULT
A
B
V
1A
V
1B
V
1B
< 93.75% OF V
1A
>0
<0
ACTIVE POINT – INACTIVE INPUT
6.25% OF ACTIVE INPUT
0V
FAULT
V
1A
V
1B
06797-026
Figure 28. Fault Conditions for Active Input Greater Than Inactive Input
Fault with Inactive Input Greater Than Active Input
Figure 29 illustrates another fault condition. If the difference
between V
1B
, the inactive input, and V
1A
, the active input (that
is, being used for billing), becomes greater than 6.25% of V
1B
,
the FAULT indicator becomes active and a swap over to the V
1B
input occurs. The Analog Input V
1B
becomes the active input.
Again, a time constant of about 3 sec is associated with this swap.
V
1A
does not swap back to the active channel until V
1A
is greater
than V
1B
, and the difference between V
1A
and V
1B
, in this order,
becomes greater than 6.25% of V
1A
. However, the FAULT indi-
cator becomes inactive as soon as V
1A
is within 6.25% of V
1B
. This
threshold eliminates potential chatter between V
1A
and V
1B
.
V
1B
V
1N
V
1A
AGND
FILTER
AND
COMPARE
TO
MULTIPLIER
FAULT
A
B
V
1A
V
1B
V
1A
< 93.75% OF V
1B
>0
<0
ACTIVE POINT – INACTIVE INPUT
6.25% OF INACTIVE INPUT
0V
FAULT + SWAP
V
1A
V
1B
06797-027
Figure 29. Fault Conditions for Inactive Input Greater Than Active Input
Calibration Concerns
Typically, when a meter is being calibrated, the voltage and current
circuits are separated, as shown in
Figure 30. This means that
current passes through only the phase or neutral circuit.
Figure 30
shows current being passed through the phase circuit. This is
the preferred option because the ADE7761B starts billing on the
input V
1A
on power-up. The Phase Circuit CT is connected to
V
1A
in Figure 30. Because there is no current in the neutral circuit,
the FAULT indicator comes on under these conditions. However,
this does not affect the accuracy of the calibration and can be
used as a means to test the functionality of the fault detection.
AGND
V
1B
V
1N
V
1A
R
F
R
F
C
F
C
F
CT
CT
RB
RB
0V
V
1A
IB
IB
PHASE
NEUTRAL
1
RB + VR = RF.
VR
1
RB
1
RA
1
V
2P
R
F
V
2N
C
T
C
F
V
TEST
CURRENT
240V rms
06797-028
Figure 30. Conditions for Calibration of Channel B
If the neutral circuit is chosen for the current circuit in the
arrangement shown in
Figure 30, this may have implications for
the calibration accuracy. The ADE7761B powers up with the
V
1A
input active as normal. However, because there is no current
in the phase circuit, the signal on V
1A
is zero. This causes a fault
to be flagged and the active input to be swapped to V
1B
(neutral).
The meter can be calibrated in this mode, but the phase and
neutral CTs may differ slightly. Because under no-fault conditions
all billing is carried out using the phase CT, the meter should be
calibrated using the phase circuit. Of course, both phase and
neutral circuits can be calibrated.
MISSING NEUTRAL MODE
The ADE7761B integrates a novel fault detection scheme that
warns and allows the ADE7761B to continue to bill in case a
meter is connected to only one wire (see
Figure 31). For correct
operation of the ADE7761B in this mode, the V
DD
pin of the
ADE7761B must be maintained within the specified range
(5 V ± 5%). The missing neutral detection algorithm is designed
to work over a line frequency of 45 Hz to 55 Hz.
ADE7761B
Rev. 0 | Page 19 of 24
V
1B
V
1N
V
1A
R
F
R
F
C
F
C
F
CT
CT
RB
RB
0V
V
1A
1
RB + VR = RF.
VR
1
RB
1
RA
1
V
2P
R
F
V
2N
C
F
C
F
LOAD
244V rms
POWER
GENERATOR
IB
06797-029
Figure 31. Missing Neutral System Diagram
The ADE7761B detects a missing neutral condition by continu-
ously monitoring the voltage channel input (V
2P
− V
2N
). The
FAULT pin is held high when a missing neutral condition is
detected. In this mode, the ADE7761B continues to bill the energy
based on the signal level on the current channel (see
Figure 32).
The billing rate or frequency outputs can be adjusted by changing
the dc level on the MISCAL pin.
V
1A
V
1N
V
1B
MISSING NEUTRAL
GAIN ADJUSMTENT
DIGITAL-TO-
FREQUENCY
CONVERTERS
CF
F1 F2
ZERO
CROSSING
DETECTION
A > B
B > A
A B
ADC
ADC
ADC
MISCAL
LPF
HPF
06797-030
Figure 32. Energy Calculation in Missing Neutral Mode
Important Note for Billing of Active Energy
The ADE7761B provides pulse outputs, CF, F1, and F2, that are
intended to be used for the billing of active energy. Pulses are
generated at these outputs in two different situations.
Case 1
When the analog input V
2P
− V
2N
complies with the conditions
described in
Figure 34, the CF, F
1
, and F
2
frequencies are propor-
tional to active power and can be used to bill active energy.
Case 2
When the analog input V
2P
− V
2N
does not comply with the
conditions described in
Figure 34, the ADE7761B does not
measure active energy but a quantity proportional to kAh. This
quantity is used to generate pulses on the same CF, F1, and F2.
This situation is indicated when the FAULT pin is high.
Analog Devices cautions users of the ADE7761B about the
following:
Billing active energy in Case 1 is consistent with the under-
standing of the quantity represented by pulses on the CF, F1,
and F2 outputs (watthour).
Billing active energy while the ADE7761B is in Case 2 must
be decided knowing that the entity measured by the ADE7761B
in this case is ampere-hour and not watthour. Users should
be aware of this limitation and decide if the ADE7761B is
appropriate for their application.
Missing Neutral Detection
The ADE7761B continuously monitors the voltage input and
detects a missing neutral condition when the voltage input peak
value is smaller than 9% of the analog full scale or when no zero
crossings are detected on this input (see
Figure 33).
0V
FSFS
0V
FS
9% OF FS
0V
FILTER AND
THRESHOLD
V2
V
2P
V
2N
AGND
ADC
MISSING
NEUTRAL
|V2|
PEAK
< 9% OF FULL SCALE
V
2P
– V
2N
V
2P
– V
2N
V
2P
– V
2N
NO ZERO CROSSING ON V2OR
06797-031
Figure 33. Missing Neutral Detection
The ADE7761B leaves the missing neutral mode for normal
operation when both conditions are no longer valid; that is,
a voltage peak value of greater than 9% of full scale and zero
crossing on the voltage channel is detected (see
Figure 34).
FILTER AND
THRESHOLD
V2
V
2P
V
2N
A
GND
ADC
MISSING
NEUTRAL
|V2|
PEAK
> 9% OF FULL SCALE
AND
ZERO CROSSING ON V2
FS
+9% OF FS
–9% OF FS
V
2P
– V
2N
06797-032
Figure 34. Return to Normal Mode After Missing Neutral Detection
ADE7761B
Rev. 0 | Page 20 of 24
Missing Neutral Gain Calibration
Example
When the ADE7761B is in missing neutral mode, the energy is
billed based on the active current input signal level. The frequency
outputs in this mode can be calibrated with the MISCAL analog
input pin. In this mode, applying a dc voltage of 330 mV on
MISCAL is equivalent to applying, in normal mode, a pure sine
wave on the voltage input with a peak value of 330 mV. The
MISCAL input can vary from 0 V to 660 mV (see the
Analog
Inputs
section). When set to 0 V, the frequency outputs are
close to zero. When set to 660 mV dc, the frequency outputs are
twice that when MISCAL is at 330 mV dc. In other words,
Equation 7 can be used in missing neutral mode by replacing
V2
rms
by MISCAL
rms
/√2.
In normal mode, ac voltages of ±330 mV peak are applied to
Channel V1 and Channel V2, and then the expected output
frequency on F1 and F2 is calculated as follows:
Gain =1; PGA =0
F
1–4
= 1.7 Hz, SCF = S1 = S0 = 0
V1 = rms of 330 mV peak ac = 0.33/√2 V
V2 = rms of 330 mV peak ac = 0.33/√2 V
V
REF
= 2.5 V (nominal reference value)
Hz0917.0
5.222
Hz7.133.033.013.6
,
2
21
=
××
××
×
=FrequencyFF
2
21
2/113.6
,
REF
41rmsrms
V
fMISCALVGain
FrequencyFF
××××
=
(8)
CF Frequency = F
1
, F
2
Frequency × 64 = 5.87 Hz
In missing neutral mode, the ac voltage of ±330 mV peak is
applied to Channel V1, no signal is connected on Channel V2,
and a 330 mV dc input is applied to MISCAL. With the ADE7761B
in the same configuration as the previous example, the expected
output frequencies on CF, F1, and F2 are
where:
F
1
, F
2
Frequency is the output frequency on F1 and F2 (Hz).
Gain is 1 or 16, depending on the PGA gain selection made
using Logic Input PGA.
V1
rms
is the differential rms voltage signal on Channel V1 (V).
MISCAL
rms
is the differential rms voltage signal on the MISCAL
pin (V).
V
REF
is the reference voltage (2.5 V ± 8%) (V).
f
1-4
is one of four possible frequencies selected by using Logic
Input S0 and Logic Input S1 (see
Table 6).
Hz0917.0
5.22
Hz7.12/33.033.013.6
,
2
=
×
×××
=FrequencyFF
21
CF Frequency = F
1
, F
2
Frequency × 64 = 5.87 Hz

ADE7761BARSZ

Mfr. #:
Manufacturer:
Analog Devices Inc.
Description:
Data Acquisition ADCs/DACs - Specialized Energy Metering IC w/ On-Chip Fault
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union

Products related to this Datasheet