IB IL 24 SEG-ELF ...
5657_en_01 PHOENIX CONTACT 3
Technical Data
General Data
Housing dimensions (width x height x depth) 12.2 mm x 120 mm x 71.5 mm
Weight (without connectors) 44 g, approximately (without connectors)
Weight (with connectors) 59 g, approximately (with connectors)
Operating mode Process data mode with 2 bits
Permissible temperature (operation) -25°C to +55°C
Permissible temperature (storage/transport) -25°C to +85°C
Permissible humidity (operation) 75% on average, 85% occasionally
Permissible humidity (storage/transport) 75% on average, 85% occasionally
Permissible air pressure (operation) 80 kPa to 106 kPa (up to 2000 m above sea level)
Permissible air pressure (storage/transport) 70 kPa to 106 kPa (up to 3000 m above sea level)
Degree of protection IP20 according to IEC 60529
Protection class Class 3 according to VDE 0106, IEC 60536
In the range from -25°Cto+55°C appropriate measures against increased humidity (> 85%) must be taken.
For a short period, slight condensation may appear on the outside of the housing if, for example, the terminal is brought into a closed room
from a vehicle.
Transmission Speed
IB IL 24 SEG-ELF 500 kbaud
IB IL 24 SEG-ELF-PAC 500 kbaud
IB IL 24 SEG-ELF-2MBD 2 Mbaud
IB IL 24 SEG-ELF-2MBD-PAC 2 Mbaud
Interface
Local bus Through data routing
Power Consumption (500 kbaud)
Communications power 7.5 V
Current consumption from the local bus 30 mA, maximum
Power consumption from the local bus 0.23 W, maximum
Main voltage U
M
24 V DC (nominal value)
Nominal current consumption at U
M
2.5 A (nominal value)
Power Consumption (2 Mbaud)
Communications power 7.5 V
Current consumption from the local bus 60 mA, maximum
Power consumption from the local bus 0.45 W, maximum
Main voltage U
M
24 V DC (nominal value)
Nominal current consumption at U
M
2.5 A (nominal value)
Supply of the Module Electronics and the I/O Through the Bus Terminal/Power Terminal (U
L
, U
M
)
Connection method Through potential routing
24 V I/O Supply (U
M
, U
S
)
The main voltage U
M
is supplied by the bus terminal or by a power terminal. The segment voltage U
S
is provided automatically at the IB IL 24 SEG-ELF
terminal and protected by the internal electronic fuse.
Connections for a supply voltage are not provided on the segment terminal. The terminal points are only provided for measurement purposes and for
connecting a button for resetting the blown fuse.