IB IL 24 SEG-ELF ...
5657_en_01 PHOENIX CONTACT 6
Derating on 30 V I/O Supply (U
M
/U
S
)
Maximum permissible load current in the segment circuit:
I
Lmax
= 2.5 A at -25°C ≤ T
A
≤ +50°C
I
Lmax
= 2.0 A at +50°C < T
A
≤ +55°C
Safety Equipment
Overload/short circuit in the segment circuit Yes (see page 4)
Surge voltage Protective elements in the power terminal or the bus terminal
Polarity reversal Protective elements in the power terminal or the bus terminal
Electrical Isolation/Isolation of the Voltage Areas
Common Potentials
The 24 V main voltage, 24 V segment voltage, and GND have the same potential. FE is a separate potential area.
Separate Potentials in the System Consisting of Bus Terminal/Power Terminal and I/O Terminal
- Test Distance - Test Voltage
5 V supply incoming remote bus/7.5 V supply (bus logic) 500 V AC, 50 Hz, 1 min.
5 V supply outgoing remote bus/7.5 V supply (bus logic) 500 V AC, 50 Hz, 1 min.
7.5 V supply (bus logic)/24 V supply (I/O) 500 V AC, 50 Hz, 1 min.
24 V supply (I/O)/functional earth ground 500 V AC, 50 Hz, 1 min.
To provide electrical isolation between the logic level and the I/O area, it is necessary to supply these areas via the bus terminal or via the
bus terminal and a power terminal from separate power supply units. Interconnection of the power supply units in the 24 V area is not
permitted. (See also user manual.)
Error Messages to the Higher-Level Control or Computer System
Short circuit/overload in the segment circuit Yes
Falling below or exceeding the operating voltage No
Approvals
CE Yes
UL/CUL Yes
If a short circuit occurs in the segment circuit, an error message is generated. LEDs D and E on the terminal also flash to indicate the fault
(see "Local Diagnostic Indicators" on page 7).