PCA9542A All information provided in this document is subject to legal disclaimers. © NXP Semiconductors N.V. 2015. All rights reserved.
Product data sheet Rev. 5.1 — 15 July 2015 7 of 27
NXP Semiconductors
PCA9542A
2-channel I
2
C-bus multiplexer and interrupt logic
6.5 Voltage translation
The pass gate transistors of the PCA9542A are constructed such that the V
DD
voltage can
be used to limit the maximum voltage that will be passed from one I
2
C-bus to another.
Figure 6 shows the voltage characteristics of the pass gate transistors (note that the graph
was generated using the data specified in Section 12 “
Dynamic characteristics of this
data sheet). In order for the PCA9542A to act as a voltage translator, the V
o(sw)
voltage
should be equal to, or lower than the lowest bus voltage. For example, if the main bus was
running at 5 V, and the downstream buses were 3.3 V and 2.7 V, then V
o(sw)
should be
equal to or below 2.7 V to effectively clamp the downstream bus voltages. Looking at
Figure 6
, we see that V
o(sw)(max)
will be at 2.7 V when the PCA9542A supply voltage is
3.5 V or lower so the PCA9542A supply voltage could be set to 3.3 V. Pull-up resistors
can then be used to bring the bus voltages to their appropriate levels (see Figure 13
).
More Information can be found in Application Note AN262, PCA954X family of I
2
C/SMBus
multiplexers and switches.
(1) maximum
(2) typical
(3) minimum
Fig 6. Pass gate voltage versus supply voltage
V
DD
(V)
2.0 5.54.53.0 4.0
002aaa964
3.0
2.0
4.0
5.0
V
o(sw)
(V)
1.0
3.5 5.02.5
(1)
(2)
(3)
PCA9542A All information provided in this document is subject to legal disclaimers. © NXP Semiconductors N.V. 2015. All rights reserved.
Product data sheet Rev. 5.1 — 15 July 2015 8 of 27
NXP Semiconductors
PCA9542A
2-channel I
2
C-bus multiplexer and interrupt logic
7. Characteristics of the I
2
C-bus
The I
2
C-bus is for 2-way, 2-line communication between different ICs or modules. The two
lines are a serial data line (SDA) and a serial clock line (SCL). Both lines must be
connected to a positive supply via a pull-up resistor when connected to the output stages
of a device. Data transfer may be initiated only when the bus is not busy.
7.1 Bit transfer
One data bit is transferred during each clock pulse. The data on the SDA line must remain
stable during the HIGH period of the clock pulse as changes in the data line at this time
will be interpreted as control signals (see Figure 7
).
7.2 START and STOP conditions
Both data and clock lines remain HIGH when the bus is not busy. A HIGH-to-LOW
transition of the data line while the clock is HIGH is defined as the START condition (S). A
LOW-to-HIGH transition of the data line while the clock is HIGH is defined as the STOP
condition (P) (see Figure 8
).
7.3 System configuration
A device generating a message is a ‘transmitter’, a device receiving is the ‘receiver’. The
device that controls the message is the ‘master’ and the devices which are controlled by
the master are the ‘slaves’ (see Figure 9
).
Fig 7. Bit transfer
mba607
data line
stable;
data valid
change
of data
allowed
SDA
SCL
Fig 8. Definition of START and STOP conditions
mba608
SDA
SCL
P
STOP condition
S
START condition
PCA9542A All information provided in this document is subject to legal disclaimers. © NXP Semiconductors N.V. 2015. All rights reserved.
Product data sheet Rev. 5.1 — 15 July 2015 9 of 27
NXP Semiconductors
PCA9542A
2-channel I
2
C-bus multiplexer and interrupt logic
7.4 Acknowledge
The number of data bytes transferred between the START and the STOP conditions from
transmitter to receiver is not limited. Each byte of eight bits is followed by one
acknowledge bit. The acknowledge bit is a HIGH level put on the bus by the transmitter,
whereas the master generates an extra acknowledge related clock pulse.
A slave receiver which is addressed must generate an acknowledge after the reception of
each byte. Also, a master must generate an acknowledge after the reception of each byte
that has been clocked out of the slave transmitter. The device that acknowledges has to
pull down the SDA line during the acknowledge clock pulse so that the SDA line is stable
LOW during the HIGH period of the acknowledge related clock pulse; set-up and hold
times must be taken into account.
A master receiver must signal an end of data to the transmitter by not generating an
acknowledge on the last byte that has been clocked out of the slave. In this event, the
transmitter must leave the data line HIGH to enable the master to generate a STOP
condition.
Fig 9. System configuration
Fig 10. Acknowledgement on the I
2
C-bus
002aaa987
S
START
condition
9821
clock pulse for
acknowledgement
not acknowledge
acknowledge
data output
by transmitter
data output
by receiver
SCL from master

PCA9542APW,112

Mfr. #:
Manufacturer:
NXP Semiconductors
Description:
Encoders, Decoders, Multiplexers & Demultiplexers 2-CH I2C MUX W/INTERRUPT
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union