ETD-BL-1T-OFF-CC- 10S
103617_en_03 PHOENIX CONTACT 3
General data
Mechanical service life Approx. 2 x 10
7
cycles
Service life, electrical Approx. 2 x 10
5
cycles at ohmic load, 1000 VA
Operating mode 100% operating factor
Degree of protection IP20
Pollution degree 2 (according to EN 50178)
Surge voltage category III, safe isolation (according to EN 50178)
Rated insulation voltage 300 V AC (According to EN 50178)
Impulse withstand voltage 6 kV (According to EN 50178)
Inflammability class according to UL 94 V0
Mounting on standard DIN rail NS 35 in accordance with EN 60715
Mounting position Any
Width 6.2 mm
Height 80 mm
Depth 86 mm
Type of housing Polyamide PA, self-extinguishing
Color green
Connection data Screw connection
Conductor cross section, solid 0.14 mm² ... 2.5 mm²
Conductor cross section, stranded 0.14 mm² ... 2.5 mm²
AWG 30 ... 12
Stripping length 8 mm
Tightening torque 0.6 Nm ... 0.8 Nm / 5 lb in ... 7 lb in
Connection data Spring-cage conn.
Conductor cross section, solid 0.14 mm² ... 2.5 mm²
Conductor cross section, stranded 0.14 mm² ... 2.5 mm²
AWG 26 ... 12
Stripping length 8 mm
Connection data Push-in conn.
Conductor cross section, solid 0.14 mm² ... 2.5 mm²
Conductor cross section, stranded 0.14 mm² ... 2.5 mm²
AWG 26 ... 14
Stripping length 8 mm
Ambient conditions
Ambient temperature (operation) -20 °C ... 65 °C
Ambient temperature (storage/transport) -25 °C ... 80 °C
Permissible humidity (operation) 15 % ... 85 %
Conformance / approvals
Conformance CE-compliant
ATEX X II 3 G Ex nA nC IIC T4 Gc X
UL, USA / Canada UL/C-UL listed UL 508
GL (not for ETD-BL-...-PT) GL EMC 1 C