8 Time setting
6
A1+
A2-
B1
12
14
11
+
OFF-CC
0,1-10s
R
x10%
1
The time can be adjusted variably using a screwdriver (blade
width 2.5 mm). The value set on the knurled wheel multiplied
by 10 gives the percentage set value of the time end value.
Example:
Time end range of the time relay = 10s
1 Setting on the knurled wheel = 6 6 x 10% = 60%
Time end range of the time relay = 10s 60 % of10 s = 6s
According to the setting of the knurled wheel (1...10), you can
also read the time directly from the "Time setting for different
time setting ranges" table.
Time settings for various time setting ranges:
Position
Knurled wheel
0.1 - 10 s
time [seconds]
3 - 300 s
time [seconds]
0.3 - 30 min
time [minutes]
3 - 300 min
time [minutes]
00,130,33
1130330
2260660
3390990
4 4 120 12 120
5 5 150 15 150
6 6 180 18 180
7 7 210 21 210
8 8 240 24 240
9 9 270 27 270
10 10 300 30 300
The following table shows some examples: All intermediate values (e.g. 1.5) can be adjusted.
The smallest adjustable time is reached at position "0". No time can be set between "10" and "0". This area is
identified with a quickly flashing geed LED.
ETD-BL-1T-OFF-CC- 10S
103617_en_03 8
PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany
phoenixcontact.com
9Diagnostics
The LEDs indicate the following error states:
LED U/t (green, backlighting of the knurled wheel)
Flashes: Voltage is present, the set time is elapsing
Flashing quickly: Undefined time range between "10" and "0" adjusted
On: Voltage is present, the set time has elapsed
LED R (yellow)
On: The output relay has picked up
Off: The output relay is dropped
10 Connection example
24 VDC
+
A1+
A2–
B1
11
12 14
12
14
11
11 Function
U
LED U/t
A1-B1
LED R
t<t
OFF-CC: With off delay with control contact
Supply voltage U must be applied permanently to the device
(green LED U/t lights up). When control contact A1-B1
closes, the output relay picks up (yellow LED R lights up). If
control contact A1-B1 opens, the set time t starts running
(green LED U/t flashes). After time t has elapsed (green LED
U/t lights up) the output relays drop out (yellow LED R is not
lit). If the control contact is closed again before time t elapses,
the elapsed time is deleted and restarted with the next cycle.