NCP4201
http://onsemi.com
14
From the Current Limit Set−point paragraph we know the
following:
I
ILIMFS
+
1mW I
LOAD
R
LIMIFS
(eq. 7)
I
IMON
+ 10
1mW I
LOAD
R
LIMFS
For a 150 A current limit R
LIMFS
= 7.5 kW. Assuming the
TDC = 135 A then V
MON
should equal 900 mV when
I
LOAD
= 135 A.
When I
LOAD
= 135 A, I
MON
equals:
(eq. 8)
I
IMON
+ 10
1mW 135 A
7.5 kW
+ 180 mA
V
IMON
+ 900 mV + 180 mA R
MON
This gives a value of 5 kW for R
MON
.
If the TDC and OCP limit for the processor have to be
changed the because the I
LIMITFS
resistor sets up both the
current limit and also the current out of the I
MON
pin, as
explained earlier.
The I
MON
pin also includes an active clamp to limit the
I
MON
voltage to 1.15 V MAX while maintaining accuracy
at 900 mV full scale.
Active Impedance Control Mode
For controlling the dynamic output voltage droop as a
function of output current, the CSA gain and load−line
programming can be scaled to be equal to the droop
impedance of the regulator times the output current. This
droop voltage is then used to set the input control voltage to
the system. The droop voltage is subtracted from the DAC
reference input voltage directly to tell the error amplifier
where the output voltage should be. This allows enhanced
feed forward response.
Load−Line Setting
The load−line is programmable over the PMBus on the
NCP4201. It is programmed using the Load−line
Calibration (0xDE) and Load−line Set (0xDF) commands.
The load−line can be adjusted between 0% and 100% of the
external R
CSA
. In this example R
CSA
= 1 mW R
O
needs to
0.8 mW therefore programming the Load−line Calibration +
Load−line Set register to give a combined percentage of
80% will set the R
O
to 0.8 mW
Table 4. Load−line Commands
Code Load−line (as a percentage of R
CSA
)
0 0000 0%
0 0001 3.226%
1 0000 51.6% = default
1 0001 53.3%
1 1110 96.7%
1 1111 100%
Current Control Mode and Thermal Balance
The NCP4201 has individual inputs (SW1 to SW4) for
each phase that are used for monitoring the per phase
current. This information is combined with an internal ramp
to create a current balancing feedback system that has been
optimized for initial current balance accuracy and dynamic
thermal balancing during operation. This current balance
information is independent of the average output current
information used for positioning. The magnitude of the
internal ramp can be set to optimize the transient response
of the system. It also monitors the supply voltage for
feed−forward control for changes in the supply. A resistor
connected from the power input voltage to the RAMPADJ
pin determines the slope of the internal PWM ramp.
The balance between the phases can be programmed using
the PMBus Phase Bal SW(x) commands (0xE3 to 0xE6).
This allows each phase to be adjusted if there is a difference
in temperature due to layout and airflow considerations. The
phase balance can be adjusted from a default gain of 5 (Bits
4:0 = 10000). The minimum gain programmable is 3.75
(Bits 4:0 = 00000) and the max gain is 6.1718 (Bits 4:0 =
11111).
Voltage Control Mode
A high gain, high bandwidth, voltage mode error
amplifier is used for the voltage mode control loop. The
control input voltage to the positive input is set via the VID
logic according to the voltages listed in Table 10. The VID
code is set using the VID Input pins or it can be programmed
over the PMBus using the VOUT_Command. By default,
the NCP4201 outputs a voltage corresponding to the VID
Inputs. To output a voltage following the VOUT_Command
the user first needs to program the required VID Code. Then
the VID_EN Bits need to be enabled. The following is the
sequence:
1. Program the required VID Code to the
VOUT_Command code (0x21).
2. Set the VID_EN bit (Bit 3) in the VR Config 1 A
(0xD2) and on the VR Config 1B (0xD3).
This voltage is also offset by the droop voltage for
active positioning of the output voltage as a
function of current, commonly known as active
voltage positioning. The output of the amplifier is
the COMP pin, which sets the termination voltage
for the internal PWM ramps.
The negative input (FB) is tied to the output sense
location with Resistor R
B
and is used for sensing
and controlling the output voltage at this point. A
current source (equal to IREF) from the FB pin
flowing through R
B
is used for setting the no load
offset voltage from the VID voltage. The no load
voltage is negative with respect to the VID DAC
for Intel CPU’s.