AXL F AI2 AO2 1H
106048_en_02 PHOENIX CONTACT 10
8 Terminal point assignment
Figure 2 Terminal point assignment
9 Connection examples
Figure 3 Connection for measuring voltage and current
as well as voltage and current output
9.1 Analog inputs
Figure 4 Connection for voltage and current measure-
ment
Figure 5 Connection of potentiometric position sensors
The values of potentiometric position sensors can be ac-
quired with voltage measurement. Supply the potentiometer
via an external power supply unit (U
ext
= 10V).
Figure 6 Connection of positiometers for detecting the
position (OUT1 channel is used for supplying
the positiometer)
Terminal
point
Color Assignment
Supply voltage input
a1, a2 Red 24 V DC
(U
A
)
Supply for analog modules
(bridged internally)
b1, b2 Blue GND Reference potential of the
supply voltage (internally
jumpered)
Analog inputs
00, 01 Orange U1+,
U2+
Positive voltage connec-
tion for channel 1 and 2
10, 11 Orange U1-, U2- Negative voltage connec-
tion for channel 1 and 2
20, 21 Orange I1+, I2+ Positive current connec-
tion for channel 1 and 2
30, 31 Orange I1-, I2- Negative current connec-
tion for channel 1 and 2
Analog outputs
02, 03 Orange U1, U2 Voltage connection for
channel 1 and 2
12, 13 Orange I1, I2 Current connection for
channel 1 and 2
22, 23 Orange GND Reference potential for all
AO channels
32, 33 Orange GND
0300
1310
2320
3330
a1
a2
b1
b2
00
10
20
30
01
11
21
31
02
12
22
32
03
13
23
33
a1
a2
b1
b2
U1+
I1+
U1
I1
U2+
I2+
U2
I2
+
U
ext
AXL F AI2 AO2 1H
106048_en_02 PHOENIX CONTACT 11
Figure 7 Passive pressure sensor at a differential cur-
rent input
Figure 8 Differential voltage input with active 3-wire
transmitter
9.2 Analog outputs
Figure 9 Connection for voltage and current output
10 Connection notes
Connect the cable shield to functional earth immediately
after the cables enter the control cabinet.
If there is no closed control cabinet, connect the shield to a
shield bus.
Use the AXLSHIELDSET Axioline shield connection set for
an optimized connection directly in front of the module.
U1+
I1+
U1
I1
U2+
I2+
U2
I2
P
I
+24 V
GND
U1+
I1+
U1
I1
U2+
I2+
U2
I2
P
U
+24 V
GND
NOTE: Damage to the electronics/mea-
suring errors
Always connect the analog actuators using
shielded twisted-pair cables.
Unshielded cables may lead to values outside
the specified tolerance limits in environments
subject to heavy noise.
For further information on shielding, please
refer to the UMENAXLSYSINST user man-
ual.
AXL F AI2 AO2 1H
106048_en_02 PHOENIX CONTACT 12
11 Local status and diagnostic indicators
Figure 10 Local status and diagnostic indicators
Channel errors are errors that can be associ-
ated with a channel.
Periphery errors are errors that affect the en-
tire module.
Designa-
tion
Color Meaning State Description
D Red/yel-
low/green
Diagnostics of local bus communication
Run Green ON The device is ready for operation, communication within the station
is OK.
All data is valid. There are no faults.
Active Green
flashing
The device is ready for operation, communication within the station
is OK.
The data is not valid. Valid data from the controller/higher-level net-
work not available.
There is no fault in the module.
Device applica-
tion not active
Flashing
green/yel-
low
The device is ready for operation, communication within the station
is OK.
Output data cannot be outputted and/or input data cannot be
read.
There is a fault on the periphery side of the module..
Ready Yellow ON The device is ready for operation but did not detect a valid cycle
after power-on.
Connected Yellow
flashing
The device is not (yet) part of the active configuration.
Reset Red ON The device is ready for operation but has lost the connection to the
bus head.
Not connected Red flash-
ing
The device is ready for operation but there is no connection to the
previously existing device.
Power down OFF Device in (power) reset.
UA Green U
Analog
ON Supply for analog modules U
A
present.
OFF Supply for analog modules U
A
not present.
E1 Red Supply voltage
error
ON Supply for analog modules U
A
is faulty.
OFF Supply for analog modules U
A
is OK.
E2 Red Error ON I/O or channel error has occurred.
OFF No error

2702072