AXL F AI2 AO2 1H
106048_en_02 PHOENIX CONTACT 4
Permissible humidity (operation) 5 % ... 95 % (non-condensing)
Permissible humidity (storage/transport) 5 % ... 95 % (non-condensing)
Air pressure (operation) 70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport) 70 kPa ... 106 kPa (up to 3000 m above sea level)
Degree of protection IP20
Protection class III, IEC 61140, EN 61140, VDE 0140-1
Mounting position Any (no temperature derating)
General data
Connection data
Designation AxiolineF connector
Connection method Push-in connection
Conductor cross section solid / stranded 0.2 mm² ... 1.5 mm² / 0.2 mm² ... 1.5 mm²
Conductor cross section [AWG] 24 ... 16
Stripping length 8 mm
Please observe the information provided on conductor cross sections in the “AxiolineF: system and installation” user manual.
Interface AxiolineFlocal bus
Connection method Bus base module
Transmission speed 100 MBit/s
Communications power
Communications power U
Bus
5 V DC (via bus base module)
Current consumption from U
Bus
typ. 120 mA, max. 150 mA
Power consumption at U
Bus
typ. 0.6 W, max. 0.75 W
I/O supply
Supply for analog modules U
A
24 V DC
Maximum permissible voltage range 19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current consumption from U
A
typ. 40 mA
max. 80 mA
Power consumption at U
A
typ. 0.96 W, max. 1.92 W
Surge protection Electronic (35 V, 0.5 s)
Protection against polarity reversal Polarity protection diode
Transient protection Suppressor diode
Total power consumption of the module
Power consumption typ. 1.56 W (at U
Bus
and U
A
), max. 2.67 W (at U
Bus
and U
A
)
Analog inputs
Number of inputs max. 2 (Differential inputs, voltage or current can be chosen separately)
Connection method Push-in connection
Connection method 2-wire (shielded)
Resolution A/D 16 bit
A/D conversion time 2 µs
Limit frequency (3 dB) 30 Hz, 12 kHz
Measured value representation 16 bits (15 bits + sign bit)
Data formats IB IL, S7-compatible, standardized representation
Process data update 150 µs
AXL F AI2 AO2 1H
106048_en_02 PHOENIX CONTACT 5
Input filter 30 Hz, 12 kHz and mean-value generation (can be parameterized)
Precision 0.1 % (of measuring range final value for active mean-value generation and 30 Hz
filter)
Transient protection of inputs Suppressor diode
Analog inputs
Differential inputs, voltage
Number of inputs 2
Voltage input signal 0 V ... 5 V, -5 V ... 5 V, 0 V ... 10 V, -10 V ... 10 V
Input resistance of voltage input 268 k (typical)
Open circuit response Goes to 0V
Common mode voltage range signal - ground -50 V DC ... 50 V DC
Overload protection ±30 V DC, maximum
Differential inputs, current
Number of inputs 2
Current input signal 0 mA ... 20 mA, 4 mA ... 20 mA, -20 mA ... 20 mA
Input resistance current input 104 (typical)
Open circuit response Going to 0mA; open-circuit detection from 4 mA ... 20 mA
Overload protection No; ±5.2VDC, maximum, I
max
= 50mA
Analog outputs
Number of outputs 2
Connection method Push-in connection
Connection method 2-wire (shielded, twisted pair)
D/A resolution 16 bit
Representation of output values 16 bits (15 bits + sign)
Data formats IB IL, S7-compatible, standardized representation
Process data update 150 µs
Short-circuit and overload protection Electronic
Transient protection Suppressor diode
Analog outputs, Current
Current output signal 0 mA ... 20 mA, 4 mA ... 20 mA, -20 mA ... 20 mA
Load/output load current output 500
Precision typ. 0.1 % (of output range final value)
Analog outputs, Voltage
Voltage output signal 0 V ... 5 V, -5 V ... 5 V, 0 V ... 10 V, -10 V ... 10 V
Load/output load voltage output > 2 k
Precision typ. 0.1 % (of output range final value)
Configuration and parameter data in a PROFIBUS system
Required parameter data 11 Byte
Need for configuration data 7 Byte
Electrical isolation/isolation of the voltage areas
Test section Test voltage
5 V communications power (logic), 24 V supply (I/O) 500 V AC, 50 Hz, 1 min
5 V supply (logic)/analog inputs and outputs 500 V AC, 50 Hz, 1 min
5 V supply (logic)/functional earth ground 500 V AC, 50 Hz, 1 min
AXL F AI2 AO2 1H
106048_en_02 PHOENIX CONTACT 6
24 V supply (I/O)/analog inputs and outputs 500 V AC, 50 Hz, 1 min
24 V supply (I/O) / functional earth ground 500 V AC, 50 Hz, 1 min
Analog inputs and outputs/functional earth ground 500 V AC, 50 Hz, 1 min
Electrical isolation/isolation of the voltage areas
Test section Test voltage
Mechanical tests
Vibration resistance in acc. with EN60068-2-6/IEC60068-2-6 5g
Shock in acc. with EN60068-2-27/IEC60068-2-27 30g
Continuous shock according to EN60068-2-27/IEC60068-2-27 10g
Conformance with EMC Directive 2004/108/EC
Noise immunity test in accordance with EN 61000-6-2
Electrostatic discharge (ESD) EN61000-4-2/IEC61000-4-2 Criterion B; 6 kV contact discharge, 8 kV air discharge
Electromagnetic fields EN61000-4-3/IEC61000-4-3 Criterion A; Field intensity: 10 V/m
Fast transients (burst) EN61000-4-4/IEC61000-4-4 Criterion B, 2kV
Transient surge voltage (surge) EN61000-4-5/IEC61000-4-5 Criterion B; supply lines DC: ±0.5 kV/±0.5 kV (symmetrical/asymmetrical); ±1 kV
to shielded I/O cables
Conducted interference EN61000-4-6/IEC61000-4-6 Criterion A; Test voltage 10 V
Noise emission test according to EN 61000-6-3
Radio interference properties EN 55022 Class B
Approvals
For the latest approvals, please visit phoenixcontact.net/products.