AXL F AI2 AO2 1H
106048_en_02 PHOENIX CONTACT 26
15.6 Objects for device management
15.6.1 Password (001D
hex
: Password)
This object can be used to enable protected module functions, e.g., for the GetExRight object.
15.6.2 Parameter record write control (0029
hex
: ParamSetWriteControl)
This object is used to control block parameterization.
Block parameterization serves to enable the joint transfer of
interdependent parameters.
If you attempt to parameterize dependent parameters indi-
vidually, this may result in the error message “Dependency
of other parameter not taken into consideration”. Block pa-
rameterization should be used in this case.
The plausibility check for the parameterization data is dis-
abled during block parameterization, the data is only stored
temporarily. However, the data length and subindex are
checked.
The plausibility check is only performed when block param-
eterization is terminated with data item 00
hex
.
If the check was completed with no errors, the temporarily
stored parameterization data is applied and stored in the
Flash memory.
If errors were detected in the temporarily stored parameter-
ization data, the service is acknowledged negatively with 08,
00, 0040
hex
.
The exact cause of the error can be read in object 002A
hex
.
The error codes are indicated by object 0080
hex
.
Not all startup objects have to be written.
To use block parameterization without tools, proceed in the
following sequence:
• Initiate block parameterization by writing the value 01
hex
to object 0029
hex
.
• Write the parameter table (ParaTable) to object
0080
hex
.
• Schreiben Sie das Ersatzwertverhalten beim Ausble-
iben von Prozessdaten (ResetCode) auf Objekt
0024
hex
.
• Write the substitute value for the OUT process data in
the event of an error (PDOUT_Subst) to object 002F
hex
.
• Terminate block parameterization by writing the value
00
hex
to object 0029
hex
.
Index
(hex)
Object name Object
type
Data type A L Rights Meaning
001D Password Simple vari-
able
Octet string 1 9 W Password
0029 ParamSetWrite-
Control
Byte Unsigned 8 1 1 R/W Parameter set write control
002A ConflictDictionary Record N 12 R Conflict dictionary
002D ResetParam Simple vari-
able
Unsigned 8 1 1 R/W Reset parameterization
002E CheckSum Simple vari-
able
Unsigned 32 1 4 R Checksum
001D
hex
: password (Write)
Subindex Data type Length in
bytes
Meaning
0 Simple variable 9 Password
0029
hex
: ParameterSetWriteControl (read/write)
Subindex Data type Length in
bytes
Meaning
0 Unsigned 8 1 Parameter record write control
00
hex
Termination of block parameterization
01
hex
Initiation of block parameterization