AXL E EIP DI8 DO8 M12 6P
8425_en_03 PHOENIX CONTACT 13
10 Local status and diagnostic indicators
10.1 Indicators for Ethernet ports and power supply
Figure 9 Indicators for Ethernet ports and power supply
Designation Color Meaning State Description
LNK 1/2 Green Link Green
ON
Connection present at port 1/2.
OFF Connection not present at port 1/2.
ACT 1/2 Yellow Activity Yellow
ON
Data transmission present at port 1/2.
OFF Data transmission not present at port 1/2.
RDY Green/
yellow/
red
Ready Green
ON
Device is ready for operation.
Yellow
flashing
Firmware update is being performed.
Flashing
green/
yellow
Over- or undervoltage at U
S
Temperature of the device is in the critical area.
Failure of the actuator supply U
A
Surge voltage/undervoltage of the actuator supply U
A
And red US LED: sensor supply overload
Red ON Rotary encoding switches are set to an invalid/reserved position.
OFF Device is not ready for operation.
NET Green/
red
Network status Green
ON
At least one CIP connection is in place and the exclusive owner con-
nection has no timeout.
Green
flashing
An IP address is configured, no CIP connection is yet in place, and the
exclusive owner connection has no timeout.
Red ON Duplicate IP. ACD has determined an IP address conflict.
Red
flashing
Connection timeout. A timeout of an exclusive owner connection has
occurred.
Flashing
green/
red
Self test
OFF Device is not ready for operation.
AXL E EIP DI8 DO8 M12 6P
8425_en_03 PHOENIX CONTACT 14
10.2 Input and output indicators
Figure 10 Input and output indicators
MOD Green/
red
Module status Green
ON
Normal operation
Green
flashing
The device is not configured.
Red ON A recoverable error has occurred.
Red
flashing
A unrecoverable error has occurred.
Flashing
green/
red
Self test
OFF Device is not ready for operation.
US Green/
red
U
Sensorik
Green
ON
Communications power/sensor voltage present
OFF Communications power/sensor voltage not present or too low.
Red ON Sensor voltage overload
UA Green U
Aktorik
ON Actuator voltage present.
OFF Actuator voltage not present.
Designation Color Meaning State Description
Designation Color Meaning State Description
00 ... 07 Yellow Status of the inputs ON Input is set.
OFF Input is not set.
00 ... 07 Yellow/red Status of the outputs Yellow ON Output is set.
Red ON Output is short circuited or overloaded.
OFF Output is not set.
The numbering of the LEDs is as follows: the first number specifies the byte, the second number specifies the
bit.
AXL E EIP DI8 DO8 M12 6P
8425_en_03 PHOENIX CONTACT 15
11 Monitoring
The connection monitoring is configured through a timeout
multiplier by the EtherNet/IP
TM
scanner.
If a connection timeout occurs, all the outputs are set to a
safe state by the device itself.
The Ethernet communication is monitored as follows:
12 Substitute value behavior
The substitute value can be set through the Assembly in-
stance 102.
Mechanism Monitoring
Connection monitoring for
the scanner
Client application
Ethernet connection

2701492

Mfr. #:
Manufacturer:
Phoenix Contact
Description:
Terminal Block Interface Modules AXL E EIP DI8 DO8 M12 6P
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union