AXL E EIP DI8 DO8 M12 6P
8425_en_03 PHOENIX CONTACT 4
Dimensions (nominal sizes in mm)
Width 60 mm
Height 185 mm
Depth 30.5 mm
Note on dimensions The height is 212 mm including fixing clips.
General data
Housing material Pocan
®
Color anthracite
Weight 480 g
Ambient temperature (operation) -25 °C ... 60 °C
CAUTION: Risk of burns
If the device is used at an ambient temperature above50°C, the contact temperature of metal surfaces may exceed70°C.
Ambient temperature (storage/transport) -25 °C ... 85 °C
Permissible humidity (operation) 5 % ... 95 %
Permissible humidity (storage/transport) 5 % ... 95 %
Air pressure (operation) 80 kPa ... 108 kPa (up to 3000 m above sea level)
Air pressure (storage/transport) 70 kPa ... 106 kPa (up to 3000 m above sea level)
Degree of protection IP65/67
Protection class III, IEC 61140, EN 61140, VDE 0140-1
Connection data
Connection method M12 connector
Interface EtherNet/IP™
Number 2
Connection method M12 connectors, D-coded
Designation connection point Copper cable
Number of positions 4
Transmission speed 10/100 MBit/s (with auto negotiation)
Cycle Time min. 1 ms (RPI)
4 Technical data
185
212
30,5
198,5
60
30
AXL E EIP DI8 DO8 M12 6P
8425_en_03 PHOENIX CONTACT 5
EtherNet/IP™
Equipment type EtherNet/IP™ slave
EtherNet/IP™ protocols ACD, DLR, IGMP v2
Additional protocols SNMP v1, HTTP, TFTP, FTP, BootP, DHCP
Specification CIP Edition 3.11
EIP adaptation of CIP 1.12
Supply: Module electronics and sensors (U
S
)
Connection method M12 connector (T-coded)
Number of positions 4
Supply voltage 24 V DC
Nominal supply voltage range 18 V DC ... 31.2 V DC (including all tolerances, including ripple)
Typical current consumption 190 mA ±15 % (at 24 V DC)
Current consumption max. 12 A
Supply: Actuators (U
A
)
Connection method M12 connector (T-coded)
Number of positions 4
Supply voltage 24 V DC
Nominal supply voltage range 18 V DC ... 31.2 V DC (including all tolerances, including ripple)
Typical current consumption 30 mA ±15 % (at 24 V DC)
Current consumption max. 12 A
Digital inputs
Number of inputs 8 (EN 61131-2 types 1 and 3)
Connection method M12 connector, double occupancy
Connection method 2, 3, 4-wire
Nominal input voltage 24 V DC
Nominal input current typ. 3 mA
Sensor current per channel typ. 0.75 mA (from Us)
Total sensor current max. 0.6 A (per device)
Input voltage range "0" signal -30 V DC ... 5 V DC
Input voltage range "1" signal 11 V DC ... 30 V DC
Input filter time < 1000 µs
Permissible conductor length to the sensor 30 m
Overload protection, short-circuit protection of sensor supply Yes
Digital outputs
Number of outputs 8
Connection method M12 connector, double occupancy
Connection method 2, 3-wire
Nominal output voltage 24 V DC (from voltage U
A
)
Maximum output current per channel 500 mA
Nominal load, ohmic 12 W (48 ; with nominal voltage)
Nominal load, inductive 12 VA (1.2 H; 48 ; with nominal voltage)
Signal delay max. 150 µs (when switched on)
Signal delay max. 200 µs (when switched off)
Switching frequency max. 5500 per second (with at least 50mA load current)
Switching frequency max. 1 per second (with inductive load)
AXL E EIP DI8 DO8 M12 6P
8425_en_03 PHOENIX CONTACT 6
Limitation of the voltage induced on circuit interruption -28 V ... -17 V
Output voltage when switched off max. 1 V
Output current when switched off max. 20 µA
Behavior with overload Auto restart
Reverse voltage resistance to short pulses Reverse voltage proof
Overcurrent shut-down min. 0.7 A
Overload protection, short-circuit protection of outputs Electronic
Electrical isolation/isolation of the voltage areas
Test section Te s t vo l t a g e
24 V supply (communications power and sensor supply, digital inputs)/
bus connection (Ethernet1)
500 V AC, 50 Hz, 1 min
24 V supply (communications power and sensor supply, digital inputs)/
bus connection (Ethernet2)
500 V AC, 50 Hz, 1 min
24 V supply (communications power and sensor supply, digital inputs)/FE 500 V AC, 50 Hz, 1 min
Bus connection (Ethernet1)/FE 500 V AC, 50 Hz, 1 min
Bus connection (Ethernet2)/FE 500 V AC, 50 Hz, 1 min
Bus connection (Ethernet1)/bus connection (Ethernet2) 500 V AC, 50 Hz, 1 min
24 V supply (actuator supply, digital outputs)/
24 V supply (communications power and sensor supply, digital inputs)
500 V AC, 50 Hz, 1 min
24 V supply (actuator supply, digital outputs)/bus connection (Ethernet1) 500 V AC, 50 Hz, 1 min
24 V supply (actuator supply, digital outputs)/bus connection (Ethernet2) 500 V AC, 50 Hz, 1 min
24 V supply (actuator supply, digital outputs)/FE 500 V AC, 50 Hz, 1 min
Mechanical tests
Vibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 5 g
Shock in acc. with EN 60068-2-27/IEC 60068-2-27 30 g, 11 ms period, half-sine shock pulse
Continuous shock according to EN60068-2-27/IEC60068-2-27 10 g
Conformance with EMC Directive 2004/108/EC
Noise immunity test in accordance with EN 61000-6-2
Electrostatic discharge (ESD) EN61000-4-2/IEC61000-4-2 Criterion B; 6 kV contact discharge, 8 kV air discharge
Electromagnetic fields EN61000-4-3/IEC61000-4-3 Criterion A; Field intensity: 10 V/m
Fast transients (burst) EN61000-4-4/IEC61000-4-4 Criterion B, 2kV
Transient surge voltage (surge) EN61000-4-5/IEC61000-4-5 Criterion B; DC supply lines: ±0.5 kV/±0.5 kV (symmetrical/asymmetrical)
Conducted interference EN61000-4-6/IEC61000-4-6 Criterion A; Test voltage 10 V
Noise emission test as per EN 61000-6-4
Radio interference properties EN 55022 Class A
Approvals
For the latest approvals, please visit phoenixcontact.net/products.
Digital outputs

2701492

Mfr. #:
Manufacturer:
Phoenix Contact
Description:
Terminal Block Interface Modules AXL E EIP DI8 DO8 M12 6P
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union