IB IL SGI 2/P-PAC
7647_en_04 PHOENIX CONTACT 7
5 Additional tables
The typical values contain the typical offset error, gain error
and linearity error in the respective configuration related to the
positive measuring range up to 100% of the nominal charac-
teristic value.
This data is valid for nominal operation (preferred mounting
position, U
S
=24V) with a conversion time of 100ms and a
16-sample average value.
The maximum tolerance values represent the worst case
measurement inaccuracy. Besides the maximum offset error,
the gain error and the linearity error, the maximum tolerance
values also comprise the longtime drift as well as the maxi-
mum tolerances of the test and calibration equipment.
Please also observe the values for temperature drift and the
tolerances under influences of electromagnetic interferences.
The values refer to nominal operation with default settings.
The typical value contain the typical offset value and gain
value in the respective configuration in the temperature range
from -25°C up to +55°C related to the positive measuring
range up to 100% of the nominal characteristic value.
This data is valid for nominal operation (preferred mounting
position, U
S
=24V) with a conversion time of 100ms and a
16-sample average value.
The maximum tolerance values represent the worst case
measurement inaccuracy. Besides maximum offset and gain
drift, they also comprise longtime drift as well as the maximum
tolerances of the test and calibration equipment.
Tolerances at T
A
=25°C
Nominal characteristic
value
Relative deviation in %
related to the measuring
range final value
Typical Maximum
±1mV/V, ±2mV/V, ±3mV/V,
±3.33mV/V, ±4mV/V, ±5mV/V
±0.01% ±0.05%
Additional tolerances influenced by electromagnetic
fields
Type of electromagnetic
interference
Typical deviation in %
related to the measuring
range final value
Electromagnetic fields; field strength
10V/m according to EN61000-4-3/
IEC61000-4-3
< ±0.1%
Conducted interference, Class3
(10V test voltage) according to
EN61000-4-6/IEC61000-4-6
-
Fast transients (burst) up to an inter-
ference voltage of ±2.2 kV in acc.
with EN61000-4-4 /
IEC61000-4-4
-
Temperature and drift response (T
A
= -25°C ... +55°C)
Relative drift in ppm/K
related to the measuring
range final value
Typical Maximum
±1mV/V, ±2mV/V, ±3mV/V,
±3.33mV/V, ±4mV/V, ±5mV/V
5 ppm/K 15 ppm/K
IB IL SGI 2/P-PAC
7647_en_04 PHOENIX CONTACT 8
6 Internal circuit diagram
Figure 1 Internal wiring of the terminal points
Key:
Supervisor
µC
SRE 1SRE 1
OPC
Level Adaptation 3V/5VLevel Adaptation 3V/5V
24 V24 V
+5V +5V
Local bus
+24 V (US)
+24 V (UM)
U
L+
U
ANA
U
L–
GND
UV
GND
UV
GND
TxD
GND
UV
+UV1
+UV2
+U01
+U02
–U01 –U02
+Ud1
Ka1
Tx+
Ka2
Kb1
Tx–
Kb2
+Ud2
–Ud1 –Ud2
Protocol chip
Register expansion
Level adaptation
Hardware monitoring
Microprocessor
Optocoupler with bipolar buffer
Analog/digital converter
OPC
SRE 1
Level Adaptation
3V/5V
Supervisor
µC
Low pass filter
DC/DC converter
DC/DC converter with electrical isolation
RS-485 interface with electrical isolation
Photomos relay
Electrically isolated area
Explanation for other used symbols has been
provided in the IL SYS INST UM E user manu-
al.
XXX
XXX
XXX
XXX
IB IL SGI 2/P-PAC
7647_en_04 PHOENIX CONTACT 9
7 Local diagnostic indicators
Figure 2 Local diagnostic indicators
An open circuit is detected according to the following table:
Note regarding open circuit message
During power up or configuration the system does not detect
whether a sensor is connected or if a cable break has oc-
curred (all cables disconnected) due to the measuring princi-
ple.
In this case, you will not obtain any valid data. As such, take
the time to ensure that the sensor is fully connected.
If an open circuit message is output, first remove the cause
prior to resetting the message.
If you do not remove the cause of the open circuit message
and perform a voltage reset or configure the module, the mod-
ule itself will behave according to the following table.
Function identification
Green
Designa-
tion
Color Meaning
D green Diagnostics (bus and logic voltage)
TR green PCP communication
CH 1 green Diagnostics of channel1
Green ON Channel 1 is OK
green OFF Channel 1 not connected or not
supplied or open circuit
CH 2 green Diagnostics of channel 2
Green ON Channel 2 is OK
green OFF Channel 2 not connected or not
supplied or open circuit
Faulty sensor cable Open-circuit message in
diagnostics
+U
V
No
GND
Uv
Yes
+U
0
Yes
-U
0
Yes
+U
d
Yes
-U
d
Yes
Open circuit message trig-
gered by
Behavior following volt-
age reset or configuration
No sensor connected/cable
break
Malfunction not detected and
not reported
Defective sensor cable (GN-
D
Uv
, +U
0
, -U
0
, +U
d
, -U
d
)
Malfunction is detected and
reported

2884907

Mfr. #:
Manufacturer:
Phoenix Contact
Description:
Controllers IB IL SGI 2/P-PAC
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union

Products related to this Datasheet