AXL F DI32/1 1F
8020_en_03 PHOENIX CONTACT 10
11.2 Object for multilingual capacity
11.3 Diagnostics objects
Diagnostics state (0018
hex
: DiagState)
This object is used for a structured message of an error.
Error and status of the local status and diagnostics indicators
Index
(hex)
Object name Object
type
Data type A L Rights Meaning Contents
0017 Language Record Visible String 2 6; 8 R Language en-us; English
Index
(hex)
Object name Object
type
Data type A L Rights Assignment/content
0018 DiagState Record 6 2; 1; 1;
2; 1; 1
R Diagnostic state
0018
hex
: DiagState (Read)
Subindex Data type Length in
bytes
Meaning Contents
0 Record 8 Diagnostic state Complete diagnostics information
1 Unsigned 16 2 Error number 0 ... 65535
dez
2 Unsigned 8 1 Priority 00
hex
No error
01
hex
Error
02
hex
Warning
81
hex
Error removed
82
hex
Warning eliminated
3 Unsigned 8 1 Channel/group/module 00
hex
No error
FF
hex
entire device
4 Unsigned 16 2 Error code See table below
5 Unsigned 8 1 More follows 00
hex
6 Visible String 1 Text 00
hex
The message with the priority 81
hex
or 82
hex
is
a one-time internal message to the bus cou-
pler that is implemented onto the error mech-
anisms of the higher-level system by the bus
coupler.
After all errors have been eliminated, it is au-
tomatically reset.
Subindex 2 3 4
Error Priority Channel/group/
module
Error code LED
hex hex hex dec D UI
No error 00 00 0000 0 Green ON ON
I/O supply failure 01 FF 3412 13330 Flashing
green/yel-
low
OFF
AXL F DI32/1 1F
8020_en_03 11
PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany
phoenixcontact.com
11.4 Objects for process data management
The objects 003B
hex
and 003C
hex
are only applicable to tools.
IN process data (0025
hex
: PDIN)
You can read the IN process data of the module with this object.
The structure corresponds to the representation in the "Process data" section.
12 Application objects
In the case of valid parameters, the parameterization is stored in the module permanently.
Filter time (FF8F
hex
: Input_Filter)
You parameterize the filter time of the module with this object.
13 Device descriptions
The device is described in the device description files.
The device descriptions for controllers from Phoenix Con-
tact are included in PC Worx and the corresponding service
packs.
The device description files for other systems are available
for download at phoenixcontact.net/products in the down-
load area of the bus coupler used.
Index
(hex)
Object name Object
type
Data type A L Rights Assignment
0025 PDIN Var Octet string 1 4 R Input process data
003B PDIN_Descr Array of Re-
cords
3 8; 2; 2 R Description of the IN process data
003C PDOUT_Descr Array of Re-
cords
3 8; 2; 2 R Description of the output process data
0025
hex
: PDIN (Read)
Subindex Data type Length in bytes Meaning
0 Octet string 4 Input process data
Index
(hex)
Object name Object
type
Data type A L Rights Assignment
FF8F Input_Filter Var Unsigned 8 1 1 R/W Filter time
FF8F
hex
: Input_Filter (read, write)
Subindex Data type Length in bytes Contents
0Var100
hex
(Default) 3000µs
01
hex
1000 µs
02
hex
< 100 µs

2688035

Mfr. #:
Manufacturer:
Phoenix Contact
Description:
Terminal Block Interface Modules AXL DI 32/1
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union