AXL F DI32/1 1F
8020_en_03 PHOENIX CONTACT 7
8 Local status and diagnostic indicators
Figure 4 Local status and diagnostic indicators
Designation Color Meaning State Description
DRed/
yellow/
green
Diagnostics of local bus communication
Run Green ON The device is ready for operation, communication within the station
is OK.
All data is valid. There are no faults.
Active Green
flashing
The device is ready for operation, communication within the station
is OK.
The data is not valid. Valid data from the controller/higher-level net-
work not available.
There is no fault in the module.
Device ap-
plication not
active
Flashing
green/yel-
low
The device is ready for operation, communication within the station
is OK.
Output data cannot be outputted and/or input data cannot be read.
There is a fault on the periphery side of the module..
Ready Yellow ON The device is ready for operation but did not detect a valid cycle after
power-on.
Connected Yellow
flashing
The device is not (yet) part of the active configuration.
Reset Red ON The device is ready for operation but has lost the connection to the
bus head.
Not con-
nected
Red flash-
ing
The device is ready for operation but there is no connection to the
previously existing device.
Power
down
OFF Device in (power) reset.
UI Green U
Input
ON Supply of digital input modules present.
OFF Supply of digital input modules not present.
00 ... 32 Yellow Status of
the inputs
ON Input is set.
OFF Input is not set.
AXL F DI32/1 1F
8020_en_03 PHOENIX CONTACT 8
9Process data
The I/O data is displayed in S7-compatible format.
IN process data
10 Parameter, diagnostics and infor-
mation (PDI)
Parameter and diagnostic data as well as other information
is transmitted via the PDI channel of the AxiolineF station.
The standard and application objects stored in the module
are described in the following section.
The following applies to all tables below:
Please refer to the UMENAXLFSYSINST for an explana-
tion of the object codes and data types.
Byte 0
Bit 76543210
Channel87654321
Terminal
point
07 06 05 04 03 02 01 00
Byte 1
Bit 76543210
Channel16151413121110 9
Terminal
point
17 16 15 14 13 12 11 10
Byte 2
Bit 76543210
Channel2423222120191817
Terminal
point
27 26 25 24 23 22 21 20
Byte 3
Bit 76543210
Channel3231302928272625
Terminal
point
37 36 35 34 33 32 31 30
Abbreviation Meaning
A Number of elements
L Length of the elements
RRead
WWrite
Every visible string is terminated with a zero
terminator (00
hex
). The length of a visible
string element is therefore one byte larger
than the amount of user data.
For detailed information on PDI and the ob-
jects, please refer to the
UMENAXLFSYSINST user manual.
AXL F DI32/1 1F
8020_en_03 PHOENIX CONTACT 9
11 Standard objects
11.1 Objects for identification (device rating plate)
Index
(hex)
Object name Object
type
Data type A L Rights Meaning Contents
Manufacturer
0001 VendorName Var Visible String 1 16 R Vendor name Phoenix Contact
0002 VendorID Var Visible String 1 7 R Vendor ID 00A045
0003 VendorText Var Visible String 1 49R Vendor text Components and
systems for indus-
trial automation
0012 VendorURL Var Visible String 1 23 R Vendor URL www.phoenixcon-
tact.com
Module - general
0004 DeviceFamily Var Visible String 1 15 R Device family I/O digital IN
0006 ProductFamily Var Visible String 1 6 R Product family AXL F
000E CommProfile Var Visible String 1 4 R Communication pro-
file
633
000F DeviceProfile Var Visible String 1 5 R Device profile 0010
0011 ProfileVersion Record Visible String 2 11; 20 R Profile version 2011-12-07;
Basic Profile V2.0
003A VersionCount Array Unsigned 16 4 4 * 2 R Version counter e.g., 0007 0001
0000 0000
hex
Module - special
0005 Capabilities Array Visible String 1 8 R Features Nothing
0007 ProductName Var Visible String 1 16 R Product name AXL F DI32/1 1F
0008 SerialNo Var Visible String 1 11 R Serial number xxxxxxxxxx (e.g.,
1234512345)
0009 ProductText Var Visible String 1 37 R Product text 32 digital inputs, ad-
justable filter
000A OrderNumber Var Visible String 1 8 R Order No. 2688035
000B HardwareVersion Record Visible String 2 11; 3 R Hardware version e.g., 2011-02-04; 00
000C FirmwareVersion Record Visible String 2 11; 3 R Firmware version 0000-00-00; --
000D PChVersion Record Visible String 2 11; 6 R Parameter channel
version
2010-01-08; V1.00
0037 DeviceType Var Octet string 1 8 R Module identification 00 80 00 04 00 00 00
D2
hex
Use of the device
0014 Location Var Visible String 1 59 R/W Location Can be filled out by
the user.
0015 EquipmentIdent Var Visible String 1 59 R/W Equipment identifier Can be filled out by
the user.
0016 ApplDeviceAddr Var Unsigned 16 1 2 R/W Application device
address
Can be filled out by
the user.

2688035

Mfr. #:
Manufacturer:
Phoenix Contact
Description:
Terminal Block Interface Modules AXL DI 32/1
Lifecycle: