AXL F DI32/1 1F
8020_en_03 PHOENIX CONTACT 4
Air pressure (operation) 70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport) 70 kPa ... 106 kPa (up to 3000 m above sea level)
Degree of protection IP20
Protection class III, IEC 61140, EN 61140, VDE 0140-1
Mounting position Any (no temperature derating)
General data
Connection data
Designation AxiolineF connector
Connection method Push-in technology
Conductor cross section solid / stranded 0.2 mm² ... 1.5 mm² / 0.2 mm² ... 1.5 mm²
Conductor cross section [AWG] 24 ... 16
Stripping length 8 mm
Interface AxiolineFlocal bus
Connection method Bus base module
Transmission speed 100 MBit/s
Communications power
Communications power U
Bus
5 V DC (via bus base module)
Current consumption from U
Bus
max. 120 mA
Power consumption at U
Bus
max. 600 mW
I/O supply
Supply of digital input modules U
I
24 V DC
Maximum permissible voltage range 19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current consumption from U
I
max. 50 mA
Power consumption at U
I
typ. 960 mW, max. 1.2 W
Surge protection of the supply voltage Electronic (35 V, 0.5 s)
Polarity reversal protection of the supply voltage Parallel diode; with external 5A fuse (for startup only)
Protection max. 8 A (polarity reversal protection up to 5A)
When using for the first time, protect the module with a 5 A fuse. If all the modules are correctly connected in the system, the 5 A fuse can be
replaced by an 8 A fuse. you can now load the module up to 8A.
NOTE: Damage to the electronics
Provide the module with an external fuse to protect it against polarity reversal. The power supply unit must be able to supply four times the
nominal current of the external fuse, to ensure that it trips in the event of an error.
Digital inputs
Number of inputs 32
Connection method Push-in technology
Connection method 1-wire
Description of the input EN 61131-2 types 1 and 3
Nominal input voltage 24 V DC
Nominal input current 2.4 mA
Current flow Linear until nominal current is reached, then constantly approx. 2.4mA
Input voltage range "0" signal -3 V DC ... 5 V DC
Input voltage range "1" signal 11 V DC ... 30 V DC
Input filter time 3000 µs (default), 1000 µs, < 100 µs
Process data update < 100 µs
Polarity reversal protection of the inputs Parallel diode (30V, 5s)
AXL F DI32/1 1F
8020_en_03 PHOENIX CONTACT 5
Configuration and parameter data in a PROFIBUS system
Required parameter data 3 Byte
Need for configuration data 6 Byte
Error messages to the higher level control or computer system
I/O supply failure Yes
Electrical isolation/isolation of the voltage areas
Test section Test voltage
5 V communications power (logic), 24 V supply (I/O) 500 V AC, 50 Hz, 1 min
5 V supply (logic)/functional earth ground 500 V AC, 50 Hz, 1 min
24 V supply (I/O) / functional earth ground 500 V AC, 50 Hz, 1 min
Mechanical tests
Vibration resistance in acc. with EN60068-2-6/IEC60068-2-6 5g
Shock in acc. with EN60068-2-27/IEC60068-2-27 30g
Continuous shock according to EN60068-2-27/IEC60068-2-27 10g
Conformance with EMC Directive 2004/108/EC
Noise immunity test in accordance with EN 61000-6-2
Electrostatic discharge (ESD) EN61000-4-2/IEC61000-4-2 Criterion B; 6 kV contact discharge, 8 kV air discharge
Electromagnetic fields EN61000-4-3/IEC61000-4-3 Criterion A; Field intensity: 10 V/m
Fast transients (burst) EN61000-4-4/IEC61000-4-4 Criterion B, 2kV
Transient surge voltage (surge) EN61000-4-5/IEC61000-4-5 Criterion B; DC supply lines: ±0.5 kV/±0.5 kV (symmetrical/asymmetrical)
Conducted interference EN61000-4-6/IEC61000-4-6 Criterion A; Test voltage 10 V
Noise emission test according to EN 61000-6-3
Radio interference properties EN 55022 Class B
Approvals
For the latest approvals, please visit phoenixcontact.net/products.
AXL F DI32/1 1F
8020_en_03 PHOENIX CONTACT 6
5 Internal circuit diagram
Figure 1 Internal wiring of the terminal points
Key:
6 Terminal point assignment
Figure 2 Terminal point assignment
7 Connection example
Figure 3 Example of a connection of sensors when
using external busbars
Ensure that GND of the sensors and GND for U
I
have the
same potential.
Local bus AxiolineF local bus
(hereinafter referred to as local bus)
Microcontroller
Optocoupler
LED
Power supply unit
Electrically isolated areas
Input circuit Input circuit
μ
C
D
UI
4x
DI 1...32
U
24 V
I
U
Bus
Local bus
Input circuit
013637 00
00
36
0137
00
10
20
30
01
11
21
31
µC
Termi-
nal
point
Color Assignment
Supply voltage input
a1, a2 Red 24 V DC
(U
I
)
Digital input module sup-
ply (internally jumpered)
b1, b2 Blue GND Reference potential of
the supply voltage (inter-
nally jumpered)
Digital inputs
00 ... 07 Orange IN1 ... IN8 Digital inputs 1 ... 8
10 ... 17 Orange IN9 ... IN16 Digital inputs 9 ... 16
20 ... 27 Orange IN17 ...
IN24
Digital inputs 17 ... 24
30 ... 37 Orange IN25 ...
IN32
Digital inputs 25 ... 32
a1
b1
a2
b2
a1
a2
b1
b2
00
10
20
30
01
11
21
31
04
14
24
34
05
15
25
35
06
16
26
36
07
17
27
37
02
12
22
32
03
13
23
33
00
10
20
30
07
17
27
37
+24V
IN25
+24V
IN1
+24V
IN2
+24V
IN26
+24V
00
10
20
30
01
11
21
31

2688035

Mfr. #:
Manufacturer:
Phoenix Contact
Description:
Terminal Block Interface Modules AXL DI 32/1
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union

Products related to this Datasheet