PSR-MS60
106171_en_02 PHOENIX CONTACT 10
13 Calculating the power dissipation
Input power dissipation
P
Input
=U
B
²
/(U
S
/I
S
)
Contact power dissipation
With the same load currents:
P
Contact
=nI
L
²
25m
With different load currents:
P
Contact
=(I
L1
²
+I
L2
²
+...+I
Ln
²
)25m
Total power dissipation
P
Total
=P
Input
+P
Contact
therefore
P
Total
=U
B
²
/(U
S
/I
S
)+nI
L
²
25m
or
P
Total
=U
B
²
/(U
S
/I
S
)+(I
L1
²
+I
L2
²
+...+I
Ln
²
)25m
Key:
The total power dissipation of the safety relay
is based on the input power dissipation and
the contact power dissipation for the same
and for different load currents.
Designation Explanation
P Power dissipation in mW
U
B
Applied operating voltage
U
S
Rated control supply voltage
I
S
Rated control supply current
n Number of enabling current paths used
I
L
Contact load current
PSR-MS60
106171_en_02 PHOENIX CONTACT 11
14 Diagnostics
The following section describes the LED indicators for gen-
eral states and error messages as well as possible causes
and remedies.
Function test/proof test
14.1 General states
14.2 Error Messages
Use the function test to check the safety func-
tion. To do this, request the safety function
once by pressing the emergency stop button,
for example. Check whether the safety func-
tion is running correctly by switching the de-
vice on again via the sensor circuits.
PWR
LED
IN
LED
K1/K2
LED
State Notes
ON OFF OFF All relays are not activated. The sensor circuit
is off.
Possible error see error messages
ON ON ON The sensor circuit is active. All relays are
picked up.
-
PWR
LED
IN
LED
K1/K2
LED
State Possible cause Remedy
ON OFF OFF The sensor circuit is actively
controlled, but no input LEDs
are lit up.
Interrupt in the sensor circuit
or faulty signal generator.
Check the sensor circuit/signal
generator. Then perform a
function test.
ON ON OFF The sensor circuit is active.
The safety circuit (K1 and K2)
is not picking up.
Internal error:
1. The diagnostic contact is
not working correctly.
2. An N/O contact is welded.
Internal error: perform a power
down reset with subsequent
function test. If the error oc-
curs again after the function
test, replace the device.
ON ON OFF The sensor circuit is active.
The safety circuit (K1 and K2)
is not picking up.
Error in the sensor circuit. Check the sensor circuit. Then
perform a function test. If the
error occurs again after the
function test, replace the
device.
OFF OFF OFF The sensor circuit is active. 1. No supply voltage at A1/A
2. Over- or undervoltage at
A1
Check the supply voltage.
PSR-MS60
106171_en_02 PHOENIX CONTACT 12
15 Application examples
Key:
Applications with the PSR-MS60
15.1 Light grid monitoring/automatic start
Two-channel light grid monitoring
Automatic start
Monitoring of external contactors
Suitable up to category4, PLe (ENISO13849-1),
SIL3 (EN62061)
Figure 9 Light grid monitoring/automatic start
15.2 Two-channel control via LPSDO module
Two-channel control
Cross-circuit detection by means of LPSDO module
Automatic start
Monitoring of external contactors
Suitable up to category4, PLe (ENISO13849-1),
SIL3 (EN62061)
Figure 10 Two-channel control via LPSDO module
K1/K2 = Contactors
WARNING: Loss of functional safety!
Make sure that the signal generator (e.g., PLC
output card or light grid) and the safety relay
have the same ground potential.
Transmitter
L4ight grid type
K1
K2
M
24V DC
K1
K2
N
L
0V
A1
A2
1323
14 24
PSR-MS60
S22
( )
S12
( )
K1
K2
OSSD1 OSSD2
EDM
Receiver
0V 24V
WARNING: Loss of functional safety!
Make sure that the signal generator (e.g., PLC
output card or light grid) and the safety relay
have the same ground potential.
The bright pulses (test pulses generated by
switching on briefly) sent by the controller can
lead to the brief, unwanted activation of the
safety relay. You should therefore deactivate
the bright pulses of the failsafe controller.
K1
K2
M
24 V DC
K1
K2
N
L
A1
A2
1323
14 24
PSR-MS60
S22
( )
S12
( )
LPSDO 8
DO
V2/V3
DO
DI
PSDI 8
V2/V3
K1
K2
0V

2904958

Mfr. #:
Manufacturer:
Phoenix Contact
Description:
Safety Relays PSR-MS60-2NO- 24DC-SC
Lifecycle: