PSR-MS60
106171_en_02 PHOENIX CONTACT 7
6 Basic circuit diagram
Figure 1 Block diagram
Key:
7Derating
7.1 Vertical or horizontal mounting position
Figure 2 Derating curve - vertical or horizontal mounting
position with connected modules
8Load curve
8.1 Ohmic load
Figure 3 Relay load curve - ohmic load
9 Function/time diagrams
Figure 4 Time diagram
Key:
Designation Explanation
A1 +24V power supply
A2 0V power supply
S12 Input sensor circuit (channel 1)
S22 Input sensor circuit (channel 2)
13/14
Enabling current path (channel 1),
undelayed
23/24
Enabling current path (channel 2),
undelayed
13 23
14 24
A1
A2
S22 S12
PWR
24V DC
IN
PSR-MS60
K1
K2
K1/K2
10 20 30 40 50 60 70
0
T [°C]
A
I[A]
TH
²²
55
8
28
0
10
20
30
40
50
60
70
72
Designation Explanation
A1/A2 Power supply
S12 Input sensor circuit (channel 1)
S22 Input sensor circuit (channel 2)
13/14
Enabling current path (channel 1),
undelayed
23/24
Enabling current path (channel 2),
undelayed
A1/A2
S12
S22
13/14
23/24
PSR-MS60
106171_en_02 PHOENIX CONTACT 8
10 Operating and indication elements
10.1 Connection versions
Figure 5 Connection versions
1 Fixed screw connection
2 Snap-on foot for DIN rail mounting
Figure 6 Year of manufacture of the device
10.2 Connection assignment
2
APPROVALS
HW/FW: 00/--HW/FW: 00/--
Serial No. xxxxxxxxxxSerial No. xxxxxxxxxx
Warning - D
o not sepe
r
ateWarning - Do not seperate
when energized!when energized!
PWR
1
0,5-0,6 Nm
5-7 lb In
12 mm
AWG 26-12
0,2-2,5 mm
2
The year the device was constructed can be
found underneath the CE designation on the
housing.
P
W
R
PHOENIX
CONT
ACT
Gm
bH &
CO
.KG
Flachs
marktstr
asse 8
3282
5 Blom
ber
g,
German
y
14
Figure Designation Explanation

A1 +24V power supply
A2 0V power supply
S22 Input sensor circuit (channel 2)
S12 Input sensor circuit (channel 1)





PWR Power LED (green)
IN Status indicator sensor circuit; LED (green)
K1/K2 Status indicator safety circuit; LED (green)



23/24 Enabling current path (channel 2), undelayed
13/14 Enabling current path (channel 1), undelayed
PSR-MS60
106171_en_02 PHOENIX CONTACT 9
11 Mounting and connection
Mount the module on a 35 mm DIN rail according to
EN60715.
Figure 7 Mounting and removing
Connect the cables to the connection terminal blocks using
a screwdriver.
Figure 8 Connection of the cables
12 Startup
Apply the rated control supply voltage (24VDC) at terminal
blocks A1/A2. The PWR LED lights up.
Close sensor circuit 24V/S12 and 24V/S22. The IN LED
lights up.
The K1/K2 LED lights up.
If the rated control supply voltage drops, the enabling cur-
rent paths of the output circuits (13/14 and 23/24) open and
the contacts enter the safe state.
If a channel to the sensor circuit is opened (24V/S12 or
24V/S22) the corresponding enabling current path opens
(13/14 or 23/24).
For compliance with UL approval, use copper
wire that is approvedupto 60°C/75°C.
A
B
0,5-0,6 Nm
5-7 lb In
12 mm
AWG 26-12
0,2-2,5 mm
2
The sensor circuits are assigned to the en-
abling current paths as follows:
S12 to 13/14 and S22 to 23/24
(see block diagram).
This means:
If only sensor circuit S12 opens, only enabling
current path 13/14 is opened.
If sensor circuit S22 also opens, enabling cur-
rent path 23/24 is also opened.

2904958