1Description
Uninterruptible power supply with integrated power
supply unit
MINI-DC-UPS/12DC/4
© PHOENIX CONTACT - 01/2010
Data sheet
INTERFACE
The MINI-DC-UPS provide an uninterruptible DC voltage
both in case of AC power supply network and in the event of
mains interferences. The wide-range input allows input
voltages from 85 V AC to 264 V AC; 4 A is provided at the
output with a regulated and adjustable output voltage from 10
V DC to 16 V DC. The rechargeable battery module supplies
an output voltage from 13.8 V DC to 9.6 V DC in buffer mode.
A 1.6 Ah or a 2.6 Ah rechargeable battery module is optionally
used depending on the required buffer time. The buffer time
varies depending on the load current.
DANGER OF EXPLOSION!
Only remove equipment when it is disconnected and not in the potentially explosive area.
The device contains dangerous live elements and high levels of stored energy.
Never carry out work when the power is turned on.
Make sure you always use the latest documentation.
It can be downloaded from the product at www.phoenixcontact.net/catalog.
Easy assembly on the DIN rail or panel
Quick startup with LED function monitoring
Buffer time of 0.5 to 30 minutes or permanently settable
Can be used worldwide in all industrial sectors due to a
wide-range input and an international approval package
Battery management for optimized, temperature-
compensated charging with simultaneous increase of
battery life
High operating safety due to long mains buffering under
full load and high MTBF (> 500,000 h)
104211_en_00
Features
MINI-DC-UPS/12DC/4
104211_en_00 PHOENIX CONTACT 2
2Table of contents
1 Description ..................................................................................................................................1
Features.....................................................................................................................................................................1
2 Table of contents.........................................................................................................................2
3 Ordering data ..............................................................................................................................3
4 Technical data.............................................................................................................................3
5 Structure......................................................................................................................................7
6 Block diagram .............................................................................................................................8
7 Safety and warning notes ............................................................................................................8
8 Installation ...................................................................................................................................8
9 Installation position......................................................................................................................9
10 Mounting on DIN rails ..................................................................................................................9
Assembly ...................................................................................................................................................................9
Removing...................................................................................................................................................................9
11 Connection, network forms 100...240 V AC networks ...............................................................10
12 Input ..........................................................................................................................................10
13 Output .......................................................................................................................................11
Signaling outputs .....................................................................................................................................................11
14 Signaling ................................................................................................................................... 11
15 Rechargeable battery module ................................................................................................... 12
16 Remote shutdown ("Remote")...................................................................................................12
Remote shutdown inactive.......................................................................................................................................12
Remote shutdown active..........................................................................................................................................12
17 Function .................................................................................................................................... 13
Setting the output voltage ........................................................................................................................................13
Buffer time setting ....................................................................................................................................................13
MINI-DC-UPS/12DC/4
104211_en_00 PHOENIX CONTACT 3
Description Type Order No. Pcs. / Pkt.
Uninterruptible power supply with integrated power supply unit, 4 A, in
combination with MINI-BAT/12/DC 1.6 Ah or 2.6 Ah
MINI-DC-UPS/12DC/4 2866598 1
Accessories Type Order No. Pcs. / Pkt.
Rechargeable battery module, 12 V DC, 1.6 Ah, for use with DC-UPS/4A MINI-BAT/12DC/1.6AH 2866572 1
Rechargeable battery module, 12 V DC, 2,6 Ah, for use with DC-UPS/4A MINI-BAT/12DC/2.6AH 2866569 1
Input data
Input nominal voltage range 100 V AC ... 240 V AC
AC input voltage range 85 V AC ... 264 V AC
DC input voltage range 100 V DC ... 350 V DC (UL508: 100...250 V DC)
Buffer period (Depending on the storage medium, e.g. 20 min / 4A)
Current consumption Approx. 0.5 A / 0.65 A (for 230 V AC)
Approx. 1.15 A / 1.35 A (for 120 V AC)
Inrush current limitation < 34 A
I
2
t < 1.1 A
2
s
Power failure bypass (refer to the diagram)
Typical response time 100 ms
Power factor (cos phi) Approx. 0.5
Protective circuitry Varistor
Input fuse, integrated 3.15 A (slow-blow, internal)
Recommended backup fuse for mains protection 6 A (characteristic B)
10 A (characteristic B)
16 A (characteristic B)
Output data
Nominal output voltage 12 V DC (AC input voltage available: 10 to 16 V DC, AC input voltage not
available: 13.8 to 9.6 V DC)
Setting range of the output voltage 10 V DC ... 16 V DC (AC input voltage available, AC input voltage not available:
Output voltage depending on the battery voltage: 13.8 V DC ... 9.6 V DC)
Output current 4 A
Derating From +60°C to 70°C: 2.5% per Kelvin
Output current limit max. 7 A
Charge current max. 1 A
Max. capacitive load Unlimited
Control deviation < 1 % (change in load, static 10% ... 90%)
Efficiency > 82 %
Ascent time < 100 ms
Residual ripple < 50 mV
PP
Peak switching voltages < 100 mV
PP
Connection in parallel No
Surge protection against internal surge voltages Yes, < 35 V DC
Resistance to reverse feed 35 V DC
3Ordering data
The MINI-DC-UPS/12DC/4 is supplied without battery module. Please order a battery module separately (see accessories).
4 Technical data

2866598

Mfr. #:
Manufacturer:
Phoenix Contact
Description:
UPS - Uninterruptible Power Supplies MINI-DC-UPS/12DC/4
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union

Products related to this Datasheet