MINI-DC-UPS/12DC/4
104211_en_00 PHOENIX CONTACT 7
5Structure
R1
OFF
Bat.- Charge
Bat.- Mode
1
0
-1
6
V
D
C
tm
in
max
[]
Alarm
ON
Remote
OUTDC12V 4A
IN AC 100- 240 V
L(+) N(-)
Battery
R2
0
,5
1
2
A
la
rm
B
a
t.-M
o
d
e
B
a
t.-C
h
a
rg
e
P
o
w
e
r
in
O
K
O
v
e
rlo
ad
3
5
1
0
1
5
2
0
30
MINI DC-UPS
1
7
12
11
10
9
2
8
4
5
6
3
1 AC input
2 DC output
3 Rechargeable battery connection
4 Active relay output: Alarm
5 Active relay output: Battery Mode
6 Active relay output: Battery Charge
7 Potentiometer 10 V DC ... 16 V DC
8 Remote shutdown (R1, R2)
9 Red control lamp: Alarm
10 Yellow control lamp: Battery Mode/Battery Charge
11 Green control lamp: Power In OK/Overload
12 Buffer time setting 0.5 min ... 30 min and permanently
[mm
2
] AWG [Nm]
solid stranded Torque
Input 0.2 - 2.5 0.2 - 2.5 24 - 12 0.5 - 0.6
Output 0.2 - 2.5 0.2 - 2.5 24 - 12 0.5 - 0.6
Signal 0.2 - 2.5 0.2 - 2.5 24 - 12 0.5 - 0.6
Input data
Input nominal voltage range 100 V AC ... 240 V AC
AC input voltage range 85 V AC ... 264 V AC
DC input voltage range 100 V DC ... 350 V DC (UL508: 100...250 V DC)
Input fuse, integrated 3.15 A (slow-blow, internal)
Recommended backup fuse for mains protection 6 A (characteristic B)
10 A (characteristic B)
16 A (characteristic B)
Type of connection Pluggable COMBICON screw connections,
Stripping length 8 mm
Output data
Nominal output voltage 12 V DC (AC input voltage available: 10 to 16 V DC, AC input voltage not
available: 13.8 to 9.6 V DC)
Setting range of the output voltage 10 V DC ... 16 V DC (AC input voltage available, AC input voltage not
available: Output voltage depending on the battery voltage: 13.8 V DC ... 9.6
V DC)
Output current 4 A
Type of connection Pluggable COMBICON screw connections,
Stripping length 8 mm
MINI-DC-UPS/12DC/4
104211_en_00 PHOENIX CONTACT 8
6Block diagram
L(+)
N(-)
12V4A
Alarm
Remote
On/Off
Bat.-Mode
Battery
Bat.-Charge
t...[min]
PS
R1
R2
Output DC
7Safety and warning notes
DANGER
The device contains dangerous live elements and high levels of stored energy.
Never carry out work when the power is turned on.
Depending on the ambient temperature and the load, the housing can become very hot!
WARNING
Before startup please ensure:
The mains connection has been carried out by a competent person and protection against electric shock is
guaranteed!
The device can be disconnected outside the power supply unit in accordance with the regulations as in EN
60950 (e.g. through primary side line protection)!
All feed lines are sufficiently protected and dimensioned!
All output lines are dimensioned according to the maximum output current of the device or separately
protected!
Sufficient convection is guaranteed!
CAUTION
The power supply units are built-in devices. The device may only be installed and put into operation by qualified
personnel. The corresponding national regulations must be observed.
8 Installation
In order for the device to function in the manner
intended. it is not necessary to observe any
minimum spacing to other devices.
The power supply unit can be snapped onto all
DIN rails in acc. with EN 60715. They must be
mounted horizontally (connecting terminal
blocks top and bottom).
MINI-DC-UPS/12DC/4
104211_en_00 PHOENIX CONTACT 9
9 Installation position
67,5
99
R1
OFF
Bat.- Charge
Bat.- Mode
10-16
VDC
t min
max
[]
Alarm
ON
Remote
OUTDC12V4A
INAC 100- 240V
L(+) N(-)
Battery
R2
0,5
1
2
Alarm
Bat.-Mode
Bat.-Charge
Power in OK
Overload
3
5
10
15
20
30
MINI DC-UPS
115
110
10 Mounting on DIN rails
Assembly
To mount on a DIN rail, snap the device straight onto the DIN
rail.
Removing
To remove from the DIN rail, press the base latch outward
and pull the device off of the DIN rail.

2866598

Mfr. #:
Manufacturer:
Phoenix Contact
Description:
UPS - Uninterruptible Power Supplies MINI-DC-UPS/12DC/4