MINI-DC-UPS/12DC/4
104211_en_00 PHOENIX CONTACT 4
Power consumption
Maximum power dissipation idling 3.8 W
Power loss nominal load max. 10.5 W
Power dissipation battery operation 2.9 W
Alarm
Output description Relay output
Voltage 12 V
Status display LED red / Malfunction/alarm: LED permanently lit
Battery charge
Output description Relay output
Voltage 12 V
Status display LED yellow, flashing / Battery charge/battery is being charged: LED flashing
Battery mode
Output description Relay output
Voltage 12 V
Status display Yellow LED / Battery mode/buffer mode: LED permanently lit
General data
Insulation voltage input/output 2 kV (routine test)
4 kV (type test)
Degree of protection IP20
Class of protection II (in an enclosed control cabinet)
MTBF > 500 000 h in acc. with IEC 61709 (SN 29500)
Type of housing Polyamide PA, color: green
Dimensions W / H / D (state of delivery) 67.5 mm / 99 mm / 115 mm
Weight 0.45 kg
Ambient conditions
Ambient temperature (operation) -25 °C ... 70 °C (> 60 °C derating)
Ambient temperature (storage/transport) -40 °C ... 80 °C
Max. permissible relative humidity (operation) 95 % (at 25 °C, no condensation)
Vibration (operation) < 15 Hz, amplitude ±2.5 mm in acc. with IEC 60068-2-6
15 Hz ... 150 Hz, 2.3g, 90 min.
Shock 30g in all directions in acc. with IEC 60068-2-27
Pollution degree in acc. with EN 50178 2
Climatic class 3K3 (in acc. with EN 60721)
MINI-DC-UPS/12DC/4
104211_en_00 PHOENIX CONTACT 5
Standards
Electrical Equipment for Machinery EN 60204
Safety transformers for power supply units EN 61558-2-17
Electrical safety (of information technology equipment) EN 60950/VDE 0805 (SELV)
EN 61558-2-17
Electronic equipment for use in electrical power installations EN 50178/VDE 0160 (PELV)
SELV EN 60950 (SELV)
EN 60204 (PELV)
Safe isolation DIN VDE 0100-410
DIN VDE 0106-1010
Protection against electric shock, basic requirements for safe isolation in
electrical equipment
DIN VDE 0106-101
Approvals
UL approvals UL Listed UL 508
UL/C-UL Recognized UL 60950
Conformance with EMC guideline 2004/108/EC and for low-voltage guideline 2006/95/EC
Noise immunity according to EN 61000-6-2
Electrostatic discharge EN 61000-4-2
Housing Level 3
Contact discharge 6 kV
Discharge in air 8 kV
Comments Criterion B
Electromagnetic HF field EN 61000-4-3
Housing Level 3
Frequency range 80 MHz ... 2 GHz
Field intensity 10 V/m
Comments Criterion A
Fast transients (burst) EN 61000-4-4
Input 4 kV (level 4 - asymmetrical: conductor to ground)
Output 2 kV (level 3 - asymmetrical: conductor to ground)
Signal 1 kV (level 2 - asymmetrical: conductor to ground)
Comments Criterion B
Surge current loads (surge) EN 61000-4-5
Input 4 kV (level 4 - asymmetrical: conductor to ground)
2 kV (level 4 - symmetrical: conductor to conductor)
Output 2 kV (Level 3 - asymmetrical)
1 kV (Level 3 - symmetrical)
Signal 2 kV (Level 3 - asymmetrical)
1 kV (Level 3 - symmetrical)
Comments Criterion B
Conducted interference EN 61000-4-6
Input/Output/Signal Level 3
Frequency range 10 kHz ... 80 MHz
Voltage 10 V
Comments Criterion A
MINI-DC-UPS/12DC/4
104211_en_00 PHOENIX CONTACT 6
Voltage dips EN 61000-4-11
Input (mains buffering > 20 ms)
Comments Criterion B
Emitted interference in acc. with EN 61000-6-3
Radio interference voltage in acc. with EN 55011 EN 55011 (EN 55022) Class B, area of application: Industry and residential
Emitted radio interference in acc. with EN 55011 EN 55011 (EN 55022) Class B, area of application: Industry and residential
Conformance with EMC guideline 2004/108/EC and for low-voltage guideline 2006/95/EC (Continued)
Noise immunity according to EN 61000-6-2