1Description
AxiolineF digital input and output module,
16inputs, 24VDC, 16outputs, 24VDC,
500mA, 1-wire connection technology
AXL F DI16/1 DO16/1 2H
© PHOENIX CONTACT
Data sheet
The module is designed for use within an AxiolineF station.
It is used to acquire and output digital signals.
The filter times of the inputs can be set to increase noise im-
munity.
Filter times of 100μs allow the user to implement a counter
function with a maximum input frequency of 5kHz in the ap-
plication.
The outputs are short-circuit and overload-protected .
Input features
16 digital inputs according to EN61131-2 type1 and
type3
–24VDC, 2.4mA
Connection of sensors in 1-wire technology
Filter times can be set in three increments: <100µs,
1000µs or 3000µs
Maximum input frequency: 5kHz
Output features
16 digital outputs
24 V DC, 500 mA
Connection of actuators in 1-wire technology
Features of Axioline F
Minimum update time <100μs
Device type label stored
Diagnostic and status indicators
This data sheet is only valid in association with the UMENAXLFSYSINST user manual.
Make sure you always use the latest documentation.
It can be downloaded from the product at phoenixcontact.net/products.
106378_en_00
2015-02-23
AXL F DI16/1 DO16/1 2H
106378_en_00 PHOENIX CONTACT 2
2Table of contents
1 Description .............................................................................................................................. 1
2 Table of contents ..................................................................................................................... 2
3 Ordering data .......................................................................................................................... 3
4 Technical data ......................................................................................................................... 3
5 Maximum outputs power consumption when inductive loads are switched off ........................ 6
6 Internal circuit diagram ............................................................................................................ 7
7 Terminal point assignment....................................................................................................... 8
8 Connection example................................................................................................................ 8
9 Local status and diagnostic indicators..................................................................................... 9
10 Process data.......................................................................................................................... 10
11 Parameter, diagnostics and information (PDI) ....................................................................... 10
12 Standard objects ................................................................................................................... 11
12.1 Objects for identification (device rating plate)............................................................................ 11
12.2 Object for multilingual capacity.............................................................................................. 12
12.3 Diagnostics objects ............................................................................................................ 12
12.4 Objects for process data management.................................................................................... 13
13 Application objects ................................................................................................................ 14
13.1 Substitute value behavior (FF8Dhex: PD Output Substitute Configuration)....................................... 14
13.2 Filter time (FF8Fhex: Input_Filter) .......................................................................................... 14
14 Device descriptions ............................................................................................................... 14
AXL F DI16/1 DO16/1 2H
106378_en_00 PHOENIX CONTACT 3
Description Type Order No. Pcs. / Pkt.
AxiolineF digital input and output module, 16inputs, 24VDC, 16outputs,
24VDC, 500mA, 1-wire connection technology (including bus base mod-
ule and connectors)
AXL F DI16/1 DO16/1 2H 2702106 1
3Ordering data
Accessories Type Order No. Pcs. / Pkt.
AxiolineF bus base module for housing type H (Replacement item) AXL F BS H 2700992 5
Zack marker strip for AxiolineF (device labeling), in 2 x 20.3 mm pitch, un-
printed, 25-section, for individual labeling with B-STIFT 0.8, X-PEN, or
CMS-P1-PLOTTER (Marking)
ZB 20,3 AXL UNPRINTED 0829579 25
Zack marker strip, flat, in 10 mm pitch, unprinted, 10-section, for individual
labeling with M-PEN 0,8, X-PEN, or CMS-P1-PLOTTER (Marking)
ZBF 10/5,8 AXL UNPRINTED 0829580 50
Documentation Type Order No. Pcs. / Pkt.
User manual, English, AxiolineF: System and installation UM EN AXL F SYS INST - -
User manual, English, Axioline F: Diagnostic registers, and error messages UM EN AXL F SYS DIAG - -
Dimensions (nominal sizes in mm)
Width 35 mm
Height 129.9 mm
Depth 54 mm
Note on dimensions The depth is valid when a TH35-7.5 DIN rail is used (according to EN60715).
4 Technical data
35 54
122,4
129,9
General data
Color traffic grey A RAL 7042
Weight 159 g (with connectors and bus base module)
Ambient temperature (operation) -25 °C ... 60 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Permissible humidity (operation) 5 % ... 95 % (non-condensing)
Permissible humidity (storage/transport) 5 % ... 95 % (non-condensing)
Air pressure (operation) 70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport) 70 kPa ... 106 kPa (up to 3000 m above sea level)

2702106

Mfr. #:
Manufacturer:
Phoenix Contact
Description:
I/O Modules AXL F DI16/1 DO16/1 2H
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union