AXL F DI16/1 DO16/1 2H
106378_en_00 PHOENIX CONTACT 10
10 Process data
The I/O data is displayed in S7-compatible format.
OUT process data
IN process data
11 Parameter, diagnostics and
information (PDI)
Parameter and diagnostic data as well as other information
is transmitted via the PDI channel of the AxiolineF station.
The standard and application objects stored in the module
are described in the following section.
The following applies to all tables below:
Please refer to the UMENAXLFSYSINST for an explana-
tion of the object codes and data types.
00 ... 03, 10 ... 13,
20 ... 23, 30 ... 33
Red/
yellow
Diagnos-
tics / Status
of the out-
puts
Red ON Short-circuit/overload of the output.
Yellow ON Output is set.
OFF No error, output is not set.
40 ... 43, 50 ... 53,
60 ... 63, 70 ...73
Yellow Status of
the inputs
ON Input is set.
OFF Input is not set.
Designation Color Meaning State Description
Byte 0
Bit 76543210
Output87654321
Terminal
point
13 12 11 10 03 02 01 00
Byte 1
Bit 76543210
Output 16 15 14 13 12 11 10 9
Terminal
point
33 32 31 30 23 22 21 20
Byte 0
Bit 76543210
Input 87654321
Terminal
point
53 52 51 50 43 42 41 40
Byte 1
Bit 76543210
Input 16151413121110 9
Terminal
point
73 72 71 70 63 62 61 60
Abbreviation Meaning
A Number of elements
L Length of the elements
RRead
WWrite
Every visible string is terminated with a zero
terminator (00
hex
). The length of a visible
string element is therefore one byte larger
than the amount of user data.
For detailed information on PDI and the ob-
jects, please refer to the
UMENAXLFSYSINST user manual.
AXL F DI16/1 DO16/1 2H
106378_en_00 PHOENIX CONTACT 11
12 Standard objects
12.1 Objects for identification (device rating plate)
Index
(hex)
Object name Object
type
Data type A L Rights Meaning Contents
Manufacturer
0001 VendorName Var Visible String 1 16 R Vendor name Phoenix Contact
0002 VendorID Var Visible String 1 7 R Vendor ID 00A045
0003 VendorText Var Visible String 1 49R Vendor text Components and
systems for indus-
trial automation
0012 VendorURL Var Visible String 1 23 R Vendor URL www.phoenixcon-
tact.com
Module - general
0004 DeviceFamily Var Visible String 1 19 R Device family I/O digital IN-OUT
0006 ProductFamily Var Visible String 1 6 R Product family AXL F
000E CommProfile Var Visible String 1 4 R Communication pro-
file
633
000F DeviceProfile Var Visible String 1 5 R Device profile 0010
0011 ProfileVersion Record Visible String 2 11; 20 R Profile version 2011-12-07;
Basic Profile V2.0
003A VersionCount Array Unsigned 16 4 4 * 2 R Version counter e.g., 0007 0001
0000 0000
hex
Module - special
0005 Capabilities Array Visible String 1 8 R Features Nothing
0007 ProductName Var Visible String 1 23 R Product name AXL F DI16/1 DO16/
1 2H
0008 SerialNo Var Visible String 1 11 R Serial number xxxxxxxxxx (e.g.,
1234512345)
0009 ProductText Var Visible String 1 57 R Product text 16 digital inputs, ad-
justable filter, 16dig-
italoutputs
000A OrderNumber Var Visible String 1 8 R Order No. 2702106
000B HardwareVersion Record Visible String 2 11; 3 R Hardware version e.g., 2011-02-04; 00
000C FirmwareVersion Record Visible String 2 11; 3 R Firmware version 0000-00-00; --
000D PChVersion Record Visible String 2 11; 6 R Parameter channel
version
2010-01-08; V1.00
0037 DeviceType Var Octet string 1 8 R Module identification 00 C0 00 02 00 00
0D 04
hex
Use of the device
0014 Location Var Visible String 1 59 R/W Location Can be filled out by
the user.
0015 EquipmentIdent Var Visible String 1 59 R/W Equipment identifier Can be filled out by
the user.
0016 ApplDeviceAddr Var Unsigned 16 1 2 R/W Application device
address
Can be filled out by
the user.
AXL F DI16/1 DO16/1 2H
106378_en_00 PHOENIX CONTACT 12
12.2 Object for multilingual capacity
12.3 Diagnostics objects
Diagnostics state (0018
hex
: DiagState)
This object is used for a structured message of an error.
Index
(hex)
Object name Object
type
Data type A L Rights Meaning Contents
0017 Language Record Visible String 2 6; 8 R Language en-us; English
Index
(hex)
Object name Object
type
Data type A L Rights Assignment/content
0018 DiagState Record 6 2; 1; 1;
2; 1; 1
R Diagnostic state
0018
hex
: DiagState (Read)
Subindex Data type Length in
bytes
Meaning Contents
0 Record 8 Diagnostic state Complete diagnostics information
1 Unsigned 16 2 Error number 0 ... 65535
dez
2 Unsigned 8 1 Priority 00
hex
No error
01
hex
Error
02
hex
Warning
81
hex
Error removed
82
hex
Warning eliminated
3 Unsigned 8 1 Channel/group/module 00
hex
No error
FF
hex
entire device
4 Unsigned 16 2 Error code See table below
5 Unsigned 8 1 More follows 00
hex
6 Visible String 1 Text 00
hex
The message with the priority 81
hex
or 82
hex
is
a one-time internal message to the bus cou-
pler that is implemented onto the error mech-
anisms of the higher-level system by the bus
coupler.

2702106

Mfr. #:
Manufacturer:
Phoenix Contact
Description:
I/O Modules AXL F DI16/1 DO16/1 2H
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union

Products related to this Datasheet