AXL F DI16/1 DO16/1 2H
106378_en_00 PHOENIX CONTACT 7
6 Internal circuit diagram
Figure 2 Internal wiring of the terminal points
Key:
C
D
UI
E1
E2
2x
IN 1...16
U
Bus
Local bus
40 41 73
40
73
41
D
UIO
E1
OUT 1...16
U
24V
IO
0100
33
00
33
01
Output
circuit
16x
Input circuit
Local bus AxiolineF local bus
(hereinafter referred to as local bus)
Microcontroller
Transistor
Optocoupler
LED
Power supply unit
Electrically isolated areas
Input circuit Input circuit
Output circuit Output configuration
µCµC
AXL F DI16/1 DO16/1 2H
106378_en_00 PHOENIX CONTACT 8
7 Terminal point assignment
Figure 3 Terminal point assignment
8 Connection example
Figure 4 Typical connection of sensors and actuators
when using external busbars
Ensure that GND of the sensors and actuators and GND for
U
IO
have the same potential.
Terminal
point
Color Assignment
Supply voltage input
a1, a2 Red 24 V DC
(U
IO
)
Supply to digital input
and output modules (in-
ternally jumpered)
b1, b2 Blue GND Reference potential of
the supply voltage (inter-
nally jumpered)
Digital outputs
00 ... 03 Orange OUT1 ...
OUT4
Digital outputs 1 ... 4
10 ... 13 Orange OUT5 ...
OUT8
Digital outputs 5 ... 8
20 ... 23 Orange OUT9 ...
OUT12
Digital outputs 9...12
30 ... 33 Orange OUT13 ...
OUT16
Digital outputs 13 ... 16
Digital inputs
40 ... 43 Orange IN1 ... IN4 Digital inputs 1 ... 4
50 ... 53 Orange IN5 ... IN8 Digital inputs 5 ... 8
60 ... 63 Orange IN9 ...
IN12
Digital inputs 9 ... 12
70 ... 73 Orange IN13 ...
IN16
Digital inputs 13 ... 16
a1
a2
b1
b2
00
10
20
30
03
13
23
33
00 01 02
03
10 11 12
13
20 21 22
23
30 31 32
33
a1
a2
b1
b2
70
60
50
40
73
63
53
43
70 71 72
73
60 61 62
63
50 51 52
53
40 41 42
43
00 01 02 03
10 11 12 13
20 21 22
23
30 31 32
33
70 71 72 73
60 61 62 63
50 51 52 53
40 41 42
43
+24 V
OUT16OUT13
OUT4OUT1
IN13
+24 V
IN1
+24 V
IN4
+24 V
IN16
+24 V
AXL F DI16/1 DO16/1 2H
106378_en_00 PHOENIX CONTACT 9
9 Local status and diagnostic indicators
Figure 5 Local status and diagnostic indicators
D
UIO
E1
00 02
10 1211 13
20 2221 23
30
41 43
51 53
61 63
71 73
40 42
50 52
60 62
70 72
3231 33
01 03
Designation Color Meaning State Description
DRed/
yellow/
green
Diagnostics of local bus communication
Run Green ON The device is ready for operation, communication within the station
is OK.
All data is valid. There are no faults.
Active Green
flashing
The device is ready for operation, communication within the station
is OK.
The data is not valid. Valid data from the controller/higher-level net-
work not available.
There is no fault in the module.
Device ap-
plication not
active
Flashing
green/yel-
low
The device is ready for operation, communication within the station
is OK.
Output data cannot be outputted and/or input data cannot be read.
There is a fault on the periphery side of the module..
Ready Yellow ON The device is ready for operation but did not detect a valid cycle after
power-on.
Connected Yellow
flashing
The device is not (yet) part of the active configuration.
Reset Red ON The device is ready for operation but has lost the connection to the
bus head.
Not con-
nected
Red flash-
ing
The device is ready for operation but there is no connection to the
previously existing device.
Power
down
OFF Device in (power) reset.
UIO Green U
input/output
ON Supply for digital input and output modules is available.
OFF Supply for digital input and output modules is not available.
E1 Red Peripheral
fault
ON Short-circuit/overload of an output
OFF No I/O error.