Data Sheet ADF4108
Rev. E | Page 15 of 20
INITIALIZATION LATCH MAP
P2 P1
0 0 8/9
0 1 16/17
1 0 32/33
1 1 64/65
PD2 PD1 MODE
0
X
X
1
X 0
1 0 1
1 1 1
CPI6 CPI5 CPI4
CPI3 CPI2 CPI1
3kΩ 5.1kΩ 11kΩ
0 0 0 1.06 0.625 0.289
0 0 1 2.12 1.25 0.580
0 1 0 3.18 1.875 0.870
0 1 1 4.24 2.5 1.160
1 0 0 5.30 3.125 1.450
1 0 1 6.36 3.75 1.730
1 1 0 7.42 4.375 2.020
1 1 1 8.50 5.0 2.320
TC4 TC3 TC2 TC1
0 0 0 0 3
0 0 0 1 7
0 0 1 0 11
0 0 1 1 15
0 1 0 0 19
0 1 0 1 23
0 1 1 0 27
0 1 1 1 31
1 0 0 0 35
1 0 0 1 39
1 0 1 0 43
1 0 1 1 47
1 1 0 0 51
1 1 0 1 55
1 1 1 0 59
1 1 1 1 63
F4
0
1
1
M3 M2 M1
0 0 0
0 0 1
0 1 0
0 1 1
1 0 0
1 0 1
1 1 0
1 1 1
F3
0
1
F2
0
1
F1
0
1
DB20 DB19 DB18 DB17 DB16 DB15 DB14 DB13 DB12 DB11
DB10 DB9 DB8 DB7 DB6 DB5 DB4 DB3 DB2 DB1 DB0
C2 (1) C1 (1)
F1
PD1
M1
M2M3F3P1P2 CPI1CPI2CPI5
CPI6
TC4PD2 F2
CPI3CPI4
DB21
TC3 TC2 TC1
DB22DB23
F4
F5
THREE-STATE
F5
X
0
1
NEGATIVE
POSITIVE
PRESCALER
VALUE
POWER-
DOWN 2
CURRENT
SETTING
2
CURRENT
SETTING
1
TIMER COUNTER
CONTROL
FASTLOCK
MODE
FASTLOCK
ENABLE
CP THREE-
STATE
MUXOUT
CONTROL
POWER-
DOWN 1
COUNTER
RESET
CONTROL
BITS
PHASE DETECTOR
POLARITY
COUNTER
OPERATION
NORMAL
R, A, B COUNTERS
HELD IN RESET
CHARGE PUMP
OUTPUT
NORMAL
FASTLOCK DISABLED
FASTLOCK MODE 1
FASTLOCK MODE 2
FASTLOCK MODE
THREE-STATE OUTPUT
DIGITAL LOCK DETECT
(ACTIVE HIGH)
N DIVIDER OUTPUT
DV
DD
R DIVIDER OUTPUT
N-CHANNEL OPEN-DRAIN
LOCK DETECT
SERIAL DATA OUTPUT
DGND
OUTPUT
TIMEOUT
(PFD CYCLES)
I
CP
(mA)
ASYNCHRONOUS POWER-DOWN
NORMAL OPERATION
ASYNCHRONOUS POWER-DOWN
SYNCHRONOUS POWER-DOWN
CE PIN
PRESCALER VALUE
PD
POLARITY
06015-025
Figure 19. Initialization Latch Map
ADF4108 Data Sheet
Rev. E | Page 16 of 20
FUNCTION LATCH
The on-chip function latch is programmed with C2 and C1 set
to 1 and 0, respectively. Figure 18 shows the input data format
for programming the function latch.
Counter Reset
DB2 (F1) is the counter reset bit. When this bit is 1, the R counter
and the AB counters are reset. For normal operation, this bit
should be 0. Upon powering up, the F1 bit needs to be disabled
(set to 0). Then, the N counter resumes counting in close alignment
with the R counter. (The maximum error is one prescaler cycle.)
Power-Down
DB3 (PD1) and DB21 (PD2) provide programmable power-down
modes. They are enabled by the CE pin.
When the CE pin is low, the device is immediately disabled
regardless of the states of PD2 and PD1.
In the programmed asynchronous power-down, the device
powers down immediately after latching a 1 into the PD1 bit,
with the condition that PD2 has been loaded with a 0.
In the programmed synchronous power-down, the device
power-down is gated by the charge pump to prevent unwanted
frequency jumps. Once the power-down is enabled by writing a 1
into PD1 (on condition that a 1 has also been loaded to PD2),
the device goes into power-down on the occurrence of the next
charge pump event.
When a power-down is activated (either synchronous or
asynchronous mode, including CE pin activated power-down),
the following events occur:
All active dc current paths are removed.
The R, N, and timeout counters are forced to their load
state conditions.
The charge pump is forced into three-state mode.
The digital lock detect circuitry is reset.
The RFIN input is debiased.
The reference input buffer circuitry is disabled.
The input register remains active and capable of loading
and latching data.
MUXOUT Control
The on-chip multiplexer is controlled by M3, M2, and M1 on
the ADF4108. Figure 18 shows the truth table.
Fastlock Enable Bit
DB9 of the function latch is the fastlock enable bit. Fastlock is
enabled only when this bit is 1.
Fastlock Mode Bit
DB10 of the function latch is the fastlock mode bit. When fastlock
is enabled, this bit determines which fastlock mode is used. If
the fastlock mode bit is 0, then Fastlock Mode 1 is selected; and
if the fastlock mode bit is 1, then Fastlock Mode 2 is selected.
Fastlock Mode 1
The charge pump current is switched to the contents of Current
Setting 2.
The device enters fastlock by having a 1 written to the CP gain
bit in the AB counter latch. The device exits fastlock by having a
0 written to the CP gain bit in the AB counter latch.
Fastlock Mode 2
The charge pump current is switched to the contents of Current
Setting 2.
The device enters fastlock by having a 1 written to the CP gain
bit in the AB counter latch. The device exits fastlock under the
control of the timer counter. After the timeout period determined
by the value in TC4:TC1, the CP gain bit in the AB counter
latch is automatically reset to 0 and the device reverts to normal
mode instead of fastlock. See Figure 18 for the timeout periods.
Timer Counter Control
The user has the option of programming two charge pump
currents. The intent is that Current Setting 1 is used when the
RF output is stable and the system is in a static state. Current
Setting 2 is meant to be used when the system is dynamic and
in a state of change (that is, when a new output frequency is
programmed).
The normal sequence of events is as follows:
The user initially decides what the preferred charge pump currents
are going to be. For example, the choice may be 2.5 mA as
Current Setting 1 and 5 mA as Current Setting 2.
At the same time, it must be decided how long the secondary
current is to stay active before reverting to the primary current.
This is controlled by the timer counter control bits, DB14:DB11
(TC4:TC1) in the function latch. The truth table is given in
Figure 18.
Now, to program a new output frequency, the user simply
programs the AB counter latch with new values for A and B.
At the same time, the CP gain bit can be set to 1, which sets the
charge pump with the value in CPI6:CPI4 for a period of time
determined by TC4:TC1. When this time is up, the charge pump
current reverts to the value set by CPI3:CPI1. At the same time,
the CP gain bit in the AB counter latch is reset to 0 and is now
ready for the next time the user wishes to change the frequency.
Note that there is an enable feature on the timer counter. It is
enabled when Fastlock Mode 2 is chosen by setting the fastlock
mode bit (DB10) in the function latch to 1.
Data Sheet ADF4108
Rev. E | Page 17 of 20
Charge Pump Currents
CPI3, CPI2, and CPI1 program Current Setting 1 for the charge
pump. CPI6, CPI5, and CPI4 program Current Setting 2 for the
charge pump. The truth table is given in Figure 18.
Prescaler Value
P2 and P1 in the function latch set the prescaler values. The
prescaler value should be chosen so that the prescaler output
frequency is always less than or equal to 300 MHz. Thus, with
an RF frequency of 4 GHz, a prescaler value of 16/17 is valid but
a value of 8/9 is not valid.
PD Polarity
This bit sets the phase detector polarity bit. See Figure 18.
CP Three-State
This bit controls the CP output pin. With the bit set high, the
CP output is put into three-state. With the bit set low, the CP
output is enabled.
INITIALIZATION LATCH
The initialization latch is programmed when C2 and C1 are set
to 1 and 1. This is essentially the same as the function latch
(programmed when C2, C1 = 1, 0).
However, when the initialization latch is programmed, an
additional internal reset pulse is applied to the R and AB counters.
This pulse ensures that the AB counter is at load point when the
AB counter data is latched and the device will begin counting in
close phase alignment.
If the latch is programmed for synchronous power-down (CE
pin is high; PD1 bit is high; PD2 bit is low), the internal pulse
also triggers this power-down. The prescaler reference and the
oscillator input buffer are unaffected by the internal reset pulse
and so close phase alignment is maintained when counting
resumes.
When the first AB counter data is latched after initialization, the
internal reset pulse is again activated. However, successive AB
counter loads after this do not trigger the internal reset pulse.
Device Programming After Initial Power-Up
After initially powering up the device, there are three ways to
program the device.
Initialization Latch Method
1. Apply V
DD
.
2. Program the initialization latch (11 in 2 LSBs of input
word). Make sure that the F1 bit is programmed to 0.
3. Next, do a function latch load (10 in 2 LSBs of the control
word), making sure that the F1 bit is programmed to a 0.
4. Then do an R load (00 in 2 LSBs).
5. Then do an AB load (01 in 2 LSBs).
When the initialization latch is loaded, the following occurs:
1. The function latch contents are loaded.
2. An internal pulse resets the R, AB, and timeout counters to
load state conditions and also three-states the charge pump.
Note that the prescaler band gap reference and the oscillator
input buffer are unaffected by the internal reset pulse,
allowing close phase alignment when counting resumes.
3. Latching the first AB counter data after the initialization
word activates the same internal reset pulse. Successive AB
loads do not trigger the internal reset pulse unless there is
another initialization.
CE Pin Method
1. Apply VDD.
2. Bring CE low to put the device into power-down. This is an
asynchronous power-down in that it happens immediately.
3. Program the function latch (10).
4. Program the R counter latch (00).
5. Program the AB counter latch (01).
6. Bring CE high to take the device out of power-down. The R
and AB counters will now resume counting in close
alignment.
Note that after CE goes high, a duration of 1 μs may be required
for the prescaler band gap voltage and oscillator input buffer
bias to reach steady state.
CE can be used to power the device up and down to check for
channel activity. The input register does not need to be repro-
grammed each time the device is disabled and enabled as long
as it has been programmed at least once after V
DD
was initially
applied.
Counter Reset Method
1. Apply V
DD
.
2. Do a function latch load (10 in 2 LSBs). As part of this,
load 1 to the F1 bit. This enables the counter reset.
3. Do an R counter load (00 in 2 LSBs).
4. Do an AB counter load (01 in 2 LSBs).
5. Do a function latch load (10 in 2 LSBs). As part of this,
load 0 to the F1 bit. This disables the counter reset.
This sequence provides the same close alignment as the
initialization method. It offers direct control over the internal
reset. Note that counter reset holds the counters at load point
and three-states the charge pump, but does not trigger
synchronous power-down.
POWER SUPPLY CONSIDERATIONS
The ADF4108 operates over a power supply range of 3.2 V to
3.6 V. T h e ADP3300ART-3.3 is a low dropout linear regulator
from Analog Devices, Inc. It outputs 3.3 V with an accuracy of
1.4% and is recommended for use with the ADF4108.

ADF4108BCPZ

Mfr. #:
Manufacturer:
Analog Devices Inc.
Description:
Phase Locked Loops - PLL Freq Synthesizer
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union

Products related to this Datasheet