UZK24.071

UZK24.071, UZO24.071
U-Series
BATTERY MODULE 24V, 7AH
P
ASSIVE BATTERY MODULE
24V, 7Ah Battery Capacity
(2x 12V Batteries in Series)
IP00 Open Type Protection Level
Small Mounting Footprint
ATO Fuse for Power Wires Included
2m Power Leads Included
PT1000 Sensor for Battery Module Temperature
Included
Center-tap Terminal with Auto-resettable Fuse
Included to Support the PULS 1-Battery-Concept
1. GENERAL DESCRIPTION
1/9
The UZK24.071 passive battery module utilizes two non-
spillable maintenance-free lead-acid batteries
(connected in series), that are assembled in one package
with all the required wiring included.
The battery module includes the monitoring and
protection board UZS24.100. This board contains a
temperature sensor and a center-tap connection with
an auto-resettable fuse to protect the center-tap wire
between the battery module and the DC-UPS control
unit. Connecting the center-tap wire to the DC-UPS
control unit enables all the benefits of the PULS 1-
Battery-Concept. This makes the use of matched
replacement batteries unnecessary and allows a precise
battery charging and testing which results in the
longest possible battery life.
The UZK24 battery module is available in two different
options. It can be ordered with assembled batteries or
as a battery bracket without batteries, allowing for
different battery options. The mounting bracket option
also allows the batteries to be assembled just in time,
avoiding outdated batteries due to limited shelf life.
2. DATA
Battery type VRLA Lead-acid
Battery design life 3 to 5 years acc. EUROBAT
Battery voltage DC 24V
Battery capacity 7Ah
Battery current max. 35A for discharging
max. 1.8A for charging
Battery fuse 35A ATO fuse
Temperature sensor PT1000
Charging voltage 27.8V
27.5V
27.15V
26.8V
at 10°C
at 20°C
at 30°C
at 40°C
Self-discharge rate 3%/month at 20°C
Temperature range -10°C to +40°C for charging
-15°C to +50°C for discharging
-20°C to +50°C for storage
Dimensions 137x186x143mm WxHxD
Weight 6000g / 13.3lb
800g / 1.8lb
UZK24.071
UZO24.071
3. ORDER NUMBERS
Battery Module UZK24.071 Battery module with
assembled batteries
UZO24.071 Battery module without
assembled batteries
Replacement UZB12.071 Battery replacement
12V, 7Ah 2pcs needed
for one battery module
4. MARKINGS
IND. CONT. E
Q.
UL 508, pending
UL 60950-1,
pending
LVD
Jul. 2014 / Rev. 1.2 DS-UZK24.071-EN
All parameters are specified at, 25°C ambient temperature unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
UZK24.071, UZO24.071
U-Series
BATTERY MODULE 24V, 7AH
INDEX
Page Page
1.
General Description ............................................1
2. Data .....................................................................1
3. Order Numbers....................................................1
4. Markings..............................................................1
5. Intended Use .......................................................2
6. Instructions for Disposal of the Battery .............2
7. Warranty..............................................................2
8. Installation Instructions ......................................3
9. Replacing Batteries .............................................4
10. Functional Diagram............................................ 4
11. Environment ....................................................... 4
12. UZS24.100 Sensor Board..................................... 5
13. Protection Features ............................................ 6
14. Approvals............................................................ 6
15. Physical Dimensions and Weight ....................... 7
16. Recommendations for a Long Battery Life ....... 8
17. Mounting Orientations ...................................... 9
The information presented in this document is believed to be accurate and reliable and may change without notice.
No part of this document may be reproduced or utilized in any form without permission in writing from the publisher.
5. INTENDED USE
This module is designed for installation in an enclosure and is intended for the general professional use such as in
industrial control, office, communication, and instrumentation equipment.
Do not use this module in equipment, where malfunction may cause severe personal injury or threaten human life.
6. INSTRUCTIONS FOR DISPOSAL OF THE BATTERY
Always dispose the batteries through a recycling organization.
Batteries must be completely discharged before recycling.
7. WARRANTY
3 Year limited warranty except batteries which are considered a service part.
Jul. 2014 / Rev. 1.2 DS-UZK24.071-EN
All parameters are specified at, 25°C ambient temperature unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
2/9
UZK24.071, UZO24.071
U-Series
BATTERY MODULE 24V, 7AH
8. INSTALLATION INSTRUCTIONS
This device may only be installed and put into operation by qualified personnel.
Check the last charging date of the batteries (marked on the battery). If it is older than 9 month replace the batteries.
PULS charges every battery before shipment.
For storage, installation and operation, the requirements of the EN 50272-2 as well as other national regulations must
be observed.
Place the battery module in a cool area inside a cabinet and ensure sufficient ventilation for the battery. The battery
module should be securely mounted on a flat surface.
If damage or malfunction should occur during installation or operation, immediately turn power off and send unit to
the factory for inspection.
Shorten the (+) and (-) wires as needed for the DC-UPS between the battery module and the DC-UPS. If seperate wires
are used, do not use wires smaller than 4mm
2
(12 AWG).
When required, install the UZS24.100 sensor board. The sensor board can be snapped on the metal mounting bar as
shown in chapter 12. Connect the blue center-tap wire to the battery.
Connect the sensor board to the DC-UPS by using control wires with a minimum wire size of 0.5mm
2
/ 20AWG.
The last step is to insert the battery fuse and to store the spare fuse in the designated holes of the plastic cover.
Do not store batteries or the battery module longer than 9 month without supplementary charge or performance
might change.
WARNING
Risk of electrical shock, fire, personal injury or death.
- Do not short-circuit the battery poles or power wires
- Observe correct battery polarity
- Disconnect battery fuse before working on the battery or on the DC-UPS. Protect against inadvertent re-powering.
- Make sure that the wiring is correct by following all local and national codes.
- Do not modify or repair the unit.
- Do not use in wet locations or in areas where moisture or condensation can be expected.
Fig. 8-1 Wiring scheme Fig. 8-2 Bracket hole pattern
3/9
Battery
DC-UPS
Data/
Temp.
(11)
RTN
(12)
Center
Tap
(13)
X1
(+)
X2
(-)
Load
(+)
(-)
UZK24.071
Battery Module
Battery
wires
(+)
(
-
)
X1
Temp.
(11)
RTN
(12)
Center
Tap
(13)
optional
OutputInput
Jul. 2014 / Rev. 1.2 DS-UZK24.071-EN
All parameters are specified at, 25°C ambient temperature unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany

UZK24.071

Mfr. #:
Manufacturer:
Description:
BATTERY DIN RAIL MOUNTABLE 24V
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union

Products related to this Datasheet