UZK24.071, UZO24.071
U-Series
BATTERY MODULE 24V, 7AH
9. REPLACING BATTERIES
Disconnect battery fuse before replacing the batteries.
To replace battery, loosen screw with only one turn and slide the mounting bracket sideways. Replace only one battery
at a time.
Always dispose the batteries through a recycling organization. Batteries must be completely discharged before
recycling. Batteries can also be returned to PULS or the battery manufacturer.
Battery replacements can be acquired through PULS. PULS also offers a list with recommended batteries in case
batteries need to be acquired elsewhere.
10. FUNCTIONAL DIAGRAM
Fig. 10-1 Functional diagram battery module with sensor board
Fuse
+-
BAT1
12V
+-
BAT2
12V
(+)
(-)
4/9
Temp.
Sensor
Temp.
RTN
Center
Tap
X1:
Auto
Resettable
Fuse
2m
2m
UZS24.100
Sensor board
11. ENVIRONMENT
Operational temperature
*)
-10°C
**)
to +40°C (14°F to 104°F) for charging
-15°C to +50°C (5°F to 122°F)
for discharging
Storage temperature
-20°C to +50°C (-4°F to 122°F) for storage and transportation
Humidity 5 to 95% r.h. IEC 60068-2-30
Do not energize while condensation is present
Vibration sinusoidal ±4mm at 16.7Hz
fixed frequency for 1hour
Vibration in vertical mounting orientation
according to IEC/EN 61056-1
Shock free fall from 20cm
onto a wooden floor
Shock with bottom down orientation
according to IEC/EN 61056-1
Altitude 0 to 6000m (0 to 20 000ft) without any restrictions
Degree of pollution 2 IEC 62103, EN 50178, not conductive
LABS compatibility The unit does not release any silicone or other LABS-critical substances and is suitable for
use in paint shops.
*) Operational temperature is the same as the ambient temperature and is defined as the air temperature 2cm below the unit.
**) Frequently charging below +5°C (41°F) reduced the lifetime of the battery
Jul. 2014 / Rev. 1.2 DS-UZK24.071-EN
All parameters are specified at, 25°C ambient temperature unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany