IB ST (ZF) 24 PT 100 4/4
10 5080C
Assignment of the HIGH and LOW Byte in the First Process Data Output Word
The control system transmits a request to the module to read or write the configuration
through a corresponding process data output word.
The module confirms this process through a corresponding process data input word.
Read configuration
Write configuration
Adresses for Error Messages and Configuration
Programming Data
HIGH Byte LOW Byte
Output word 80
hex
00
hex
Input word
Result OK 80
hex
Previous configuration
Result error 88
hex
Previous configuration
HIGH Byte LOW Byte
Output word 81
hex
New configuration
Input word
Result OK 81
hex
New configuration
Result error 89
hex
Previous configuration
Status Process Data Word
Decimal Hexadecimal Binary
Error messages -7937 E0FF
1110 0000 1111 1111
... ... ...
-8192 E000
1110 0000 0000 0000
Reserved ... ... ...
Configuration -32257 81FF
1000 0001 1111 1111
... ... ...
-32768 8000
1000 0000 0000 0000
ID code 7B
hex
(123
dec
) Output address area 8 bytes
Length code 4
hex
Parameter channel
(PCP)
0 bytes
Input address area 8 bytes Register length 8 bytes
IB ST (ZF) 24 PT 100 4/4
5080C 11
Assignment of the Module Terminals to the INTERBUS Reference
INTERBUS
reference
Word
Word x
Bit 1514131211109876543210
Byte
Byte 0 Byte 1
Bit 7654321076543210
Module
terminals
channel 1
Sensor current
(+)
Sign bit
Terminal 1
Sensor power (+) Terminal 2
Sensor power (-) Terminal 3
Sensor current (-) Terminal 4
Shield Terminal 20
Module
terminals
channel 2
Sensor current
(+)
Sign bit
Terminal 5
Sensor power (+) Terminal 6
Sensor power (-) Terminal 7
Sensor current (-) Terminal 8
Shield Terminal 24
Module
terminals
channel 3
Sensor current
(+)
Sign bit
Terminal 9
Sensor power (+) Terminal 10
Sensor power (-) Terminal 11
Sensor current (-) Terminal 12
Shield Terminal 28
Module
terminals
channel 4
Sensor current
(+)
Sign bit
Terminal 13
Sensor power (+) Terminal 14
Sensor power (-) Terminal 15
Sensor current (-) Terminal 16
Shield Terminal 32
IB ST (ZF) 24 PT 100 4/4
12 5080C
Technical Data
General
Housing dimensions (width x height x depth) 118 mm x 116 mm x 117 mm
(4.646 in. x 4.567 in. x 4.606 in.)
Operating mode Process data operation with 4 words
Connection type of the sensors 2-, 3-, or/and 4-wire technology
Total power consumption 2.4 W, typical
Permissible operating temperature -25°C to 55°C (-13°F to +131°F)
Permissible storage temperature -25°C to +75°C (-13°F to +167°F)
Degree of protection IP 20, DIN 40050, IEC 60529
Class of protection Class 3 VDE 0106, IEC 60536
Humidity 75% on average, 85% occasionally,
no condensation
Air pressure (operation) 80 kPa to 106 kPa, 2000 m (6562 ft.) above sea
level
Electrical isolation Test voltage
Bus/inputs 500 V AC, 1 min., 50 Hz
Supply voltage/inputs 500 V AC, 1 min., 50 Hz
Supply voltage/protective conductor 500 V AC, 1 min., 50 Hz
I/O voltage/protective conductor 500 V AC, 1 min., 50 Hz
Emitted interference EN 50081-2, Class A
Processor monitoring Watchdog circuit
Preferred installation position Panel mounting
Protective ground Via DIN rail
Weight 540 g, typical
Interface
INTERBUS ST interface ST cable (supplied with the module)

2750138

Mfr. #:
Manufacturer:
Phoenix Contact
Description:
Controllers IB STME 24 PT 100 4/4
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union