IB ST (ZF) 24 PT 100 4/4
5080C 7
Fahrenheit Scale
Sensor Temperature Process Data Word
Decimal Hexadecimal Binary
+3276.7°F +32767 7FFF
hex
0111 1111 1111 1111
bin
... ... ... ...
Pt 100/Pt 1000
+1562.0°F +15620 3D04
hex
0011 1101 0000 0100
bin
... ... ... ...
+1000.0°F +10000 2710
hex
0010 0111 0001 0000
bin
... ... ... ...
Ni100/Ni 1000 DIN characteristic
+482.0°F +4820 12D4
hex
0001 0010 1101 0100
bin
... ... ... ...
Ni 100/Ni 1000 SAMA characteristic
+392.0°F +3920 0F50
hex
0000 1111 0101 0000
bin
... ... ... ...
+100.0°F +1000 03E8
hex
0000 0011 1110 1000
bin
... ... ... ...
+10.0°F +100 0064
hex
0000 0000 0110 0100
bin
... ... ... ...
+1.0°F 10 000A
hex
0000 0000 0000 1010
bin
... ... ... ...
+0.1°F 1 0001
hex
0000 0000 0000 0001
bin
... ... ... ...
0.0°F 0 0000
hex
0000 0000 0000 0000
bin
... ... ... ...
-0.1°F -1 FFFF
hex
1111 1111 1111 1111
bin
... ... ... ...
-1.0°F -10 FFF6
hex
1111 1111 1111 0110
bin
... ... ... ...
-10.0°F -100 FF9C
hex
1111 1111 1001 1100
bin
... ... ... ...
-76.0°F -760 FD08
hex
1111 1101 0000 1000
bin
-100.0°F -1000 FC18
hex
1111 1100 0001 1000
bin
... ... ... ...
-328.0°F -3280 F330
hex
1111 0011 0011 0000
bin
... ... ... ...
-459.6°F -4596 EE0C
hex
1110 1110 0000 1100
bin
+3276.7°F +32767 7FFF
hex
0111 1111 1111 1111
bin
IB ST (ZF) 24 PT 100 4/4
8 5080C
Error Messages
In normal mode, every process data input word
contains the temperature value of the
corresponding channel. When an error occurs
on a channel or module, a code is written to the
corresponding input word that indicates the error
cause.
If the value E0xxh occurs in the
process data this is not a measured
value but an error message.
Figure 7 Bit assignment of the error code
Checking the Supply Voltage
The I/O supply voltage is permanently
monitored. If the voltage value is outside the
predefined range a module error message is
released. The error code E008
hex
is entered into
the process data input words instead of the
temperature values.
Checking the Data in the Non-Volatile
Memory
The configuration is not stored in the volatile
memory of the EEPROM. If the configuration of
the EEPROM is invalid, a module error message
is released and the error code E002
hex
is written
to all process data input words.
Monitoring Converter Activities
A timeout function checks the analog to digital
converter (ADC). If the ADC fails, a module error
message is released and the error code E010
hex
is entered in all process data input words.
15 14
13
12
11
10
9
87
65
4
3
2
10
Bit
Open circuit
5080C 009
E0
hex
R e a d e rro r in E E P R O M
O ut of m easuring range
Supply voltage U
S
not present
AD C defective
Invalid configuration
Reserved
IB ST (ZF) 24 PT 100 4/4
5080C 9
INTERBUS OUT Process Data Word
HIGH and LOW Byte of the First Process Data Output Word
Figure 8 HIGH and LOW byte of the first process data output word
The module can be configured with the INTERBUS master. For this, only the LOW byte of the first
process data output word is used. The configuration is valid for all four channels. The process data
output words of channels 2, 3, and 4 are not evaluated. During configuration, the measured
temperature values continue to be entered in the process data input words of channels 2, 3, and 4
(for channel 1 see note below). The format changes with every new configuration.
Possible Configurations in the LOW Byte
Figure 9 Possible configurations in the LOW byte
The configuration is stored in the non-volatile memory of the EEPROM and is saved when
the supply voltage is disconnected. After the configuration is read/written, the 0000
hex
value must be written to the first process data output word. This causes the first channel
to be reset to measuring operation. In the first process data input word, the measured temperature
value is transmitted. The default upon module delivery is that all bits of the configuration bytes are
set to zero. This leads to the following configuration:
Process data format: °C, standard of the characteristic curve: DIN IEC 60751, sensor type: Pt 100,
filter frequency: 50 Hz
15 14
13
12
11
10
9
87
65
4
3
2
10
Bit
HIGH byte
LO W byte
5080C 007
7
6
5
4
3
2
1
0
Bit
Sensor type
5080C 008
000 - P t 100
001 - P t 1000
010 - N i 100
011 - N i 1000
100 - N i 1000
(L a n d is & G y r)
Standard
0 - D IN IEC 751 (P t)
DIN 43760 (Ni)
1 - SAM A
00
Unit
0 - C e ls iu s
1 - Fahrenheit
Filter frequency
(suppression)
0 - 50 H z
1 - 16
2
3
Hz

2750138