IB ST (ZF) 24 PT 100 4/4
5080C 13
Power Consumption
Communications power 9 V
Current consumption from the local bus 85 mA, typical; 100 mA, maximum
Power consumption from the local bus 800 mW, typical
I/O supply voltage U
S
24 V DC
Current consumption of U
S
65 mA, typical; 85 mA, maximum
Power consumption from power pack and
application side (24 V supply)
1.5 W, typical
2.0 W, maximum
I/O Supply Voltage (U
S
)
Nominal value 24 V DC
Permissible ripple 3.6 V
pp
within the permissible voltage range
Permissible voltage range (including ripple) 18.5 V DC to 30.5 V DC
Current consumption of U
S
65 mA, typical
Electrical isolation With DC/DC converter
Test voltage 500 V AC, 50 Hz, 1 min.
Protection against polarity reversal Via diode connected in series
Surge voltage protection Fuses in the terminal block base
IBS TR5 0,4 AT
Transient protection Yes
Failure detection Yes
Power consumption from power supply unit and
application side (24 V supply)
1.5 W, typical
2.0 W, maximum
IB ST (ZF) 24 PT 100 4/4
14 5080C
Analog Inputs for Temperature Sensors (RTD)
Number 4
Available sensor types Pt 100, Pt 1000
Ni 100, Ni 1000
Standards for characteristic curves DIN IEC 60751 (Pt 100, Pt 1000)
DIN 43760 (Ni 100, Ni 1000)
SAMA RC 21-4-1966 (Pt 100, Ni 100
corresponds to Type I)
Landis & Gyr (Ni 1000)
Temperature measuring unit Celsius or Fahrenheit scale
Temperature measuring range (value range) -273,1°C to 3276.7°C on Celsius scale
-459.6°F to 3276.7°F on Fahrenheit scale
Resolution of the measured values 0.1°C corresponds to 0.1 K on the Celsius scale
0.1°F corresponds to 0.056K on the Fahrenheit
scale
Temperature-proportional, linearized
Resolution of the ADC 16 bits
Measuring principle Sigma-delta method
Representation of output value 16-bit two's complement
Sensor current 0.2 mA
Basic error limit ±0.003% of the value range (±0.1°C)
Temperature drift ±0.009% of the value range (±0.3°C)
Typical duration of a measuring cycle depending
on the number of channels connected with 50 Hz
suppression
1 channel: 258 ms
2 channels: 444 ms
3 channels: 630 ms
4 channels: 816 ms
Typical duration of a measuring cycle depending
on the number of channels connected with
16.67 Hz suppression
1 channel: 618 ms
2 channels: 1164 ms
3 channels: 1710 ms
4 channels: 2256 ms
IB ST (ZF) 24 PT 100 4/4
5080C 15
All percentage data refers to the entire value range of the module ranging from -273.1°C
to +3276.7°C.
Module Error Messages
Failure of the internal I/O supply voltage
(+5 V DC)
Yes
Breakdown of fuse F1 for the I/O supply voltage Yes
Breakdown of the external I/O supply voltage U
S
of 24 V DC
Yes
Analog/digital converter defective Yes
Content of the EEPROM invalid Yes
Configuration invalid Yes
Open circuit detection No (error message in the process data input
word)
Tolerances Influenced by Electromagnetic Fields
Type of electromagnetic interference Deviation of the measured temperature
value
Relative Absolute
Radiated-noise immunity according to
IEC 60801-3: 1984 (field strength 10 V/m)
< ±0.3% < ±10.0°C
Radiated-noise immunity according to
IEC 60801-3: 1984 (field strength 3 V/m)
< ±0.005% < ±0.2°C
Conducted high-frequency interference (0.15 MHz to
80 MHz) according to IEC 60801-6, Class 3
(ENV 50141: 1993)
< ±0.015% < ±0.5°C
Transient interferences (burst) according to
IEC 60801-4 Class 4 up to 1000 V
No deviation No deviation
Transient interferences (burst) according to
IEC 60801-4 Class 4 from 1000 V to 2000 V
< ±0.5% < ±18.0°C

2750138

Mfr. #:
Manufacturer:
Phoenix Contact
Description:
Controllers IB STME 24 PT 100 4/4
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union

Products related to this Datasheet