H7BR
H7BR
16
Output Input mode
mode Up Down Up/Down A.B.C
K
Preset 2
Preset 1
Output 1
Output 2
0
999,999
Reset
Present value runs continuously. Output 1 is self-holding, and goes off after expiration of the 1-shot period for Output 2.
One-shot time periods for Output 1 and 2 are independent.
P
Preset 2
Preset 1
Output 1
Output 2
0
999,999
Reset
Present value display does not change during 1-shot time period, but reset start status is returned to as soon as count is
reached. Outputs are 1-shot and operate repeatedly. Output 1 is self-holding, and goes off after expiration of the 1-shot
period for Output 2. One-shot time periods for Output 1 and 2 are independent.
Q
Preset 2
Preset 1
Output 1
Output 2
0
999,999
Reset
Present value runs continuously through 1-shot time period and returns to reset start status immediately afterward. Outputs
are 1-shot and operate repeatedly. Output 1 is self-holding, and goes off after expiration of the 1-shot period for Output 2.
One-shot time periods for Output 1 and 2 are independent.
A
Preset 2
Preset 1
Output 1
Output 2
0
999,999
Reset
Present value and output 1 maintain status until reset. Output 1 and 2 operate independently.
H7BR
H7BR
17
One-shot output from Output 1
Self-holding output Self-holding output
One-shot output from Output 2
One-shot outputs can be set to between 10 and 1,000 ms.
Batch Counter Operation
The batch counter counts the number of times set value is reached for 1-stage models, and the number of times set 2 is reached for 2-stage
models.
Batch count reset
Batch output
Batch count set
value
Batch count present
value 0
The batch count output holds until
reset by the batch count reset.
The present value of the batch count
advances continuously.
1. The batch count present value remains at 0 while the batch
count reset is ON.
2. When the batch count set value is 0, the batch count will
proceed, but there will be no output.
3. When the batch count present value exceeds 9999, it returns
to 0.
4. The batch count present value and output do not affect the
RESET Key or reset input.
5. When power is interrupted and the batch count output is ON,
the output will be ON when power returns.
6. When a batch count set value which is greater than the
present value is changed to a set value which is less than the
present value, the output will go ON.
7. If, after the output has gone ON, the set value is changed to a
set value which is greater than the present value, the output
will remain ON.
H7BR-C
Output 2 operation applies for 1-stage models only.
Output
Input mode
mode Up/Down A.B.C
K
Reset
999,999
Set 2
Set 1
0
Output 1
Output 2
Comp.
-999,999
Comp.
Present value increments and decrements within displayable range. Outputs go ON for one-shot.
D
Reset
999,999
Set 2
Set 1
0
Output 1
Output 2
Comp.
-999,999
Comp.
Present value increments and decrements within displayable range. Outputs are ON during the count is equal.
H7BR
H7BR
18
Output Input mode
mode Up/Down A.B.C
L
Reset
999,999
Set 2
Set 1
0
Output 1
Output 2
Comp.
-999,999
Comp.
Present value increments and decrements within displayable range. Output 1 is ON whenever present value is less than or
equal to Set 1; Output 2 is ON whenever present value is greater than or equal to Set 2.
H
Reset
999,999
Set 2
Set 1
0
Output 1
Output 2
Comp.
-999,999
Comp.
Present value increments and decrements within displayable range. Output 1 is ON whenever present value is greater than
or equal to Set 1; Output 2 is ON whenever present value is greater than or equal to Set 2.
Self-holding output/level input
One-shot output
One-shot outputs can be set to be-
tween 10 and 1,000 ms.
Instantaneous (equals) output
Level input
Edge input
Note: 1. Counting inputs are not applied while the reset input is
ON.
2. One-shot outputs, when ON, are turned OFF when the
reset input goes ON.
3. One-shot outputs, when ON, are left ON for the one-shot
time period when the compensation input goes ON
4. One-shot outputs, when ON, are reset and the one-shot
output is restarted if a preset designating the output is
reached.
5. The compensation input is valid only when the present
value is being incremented.
The compensation input is also valid only for the
H7BR-Cj.

H7BR-BV-AC24/DC12-24

Mfr. #:
Manufacturer:
Omron Automation and Safety
Description:
Counters & Tachometers Use H7BX Series
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union