QUINT-PS/ 1AC/12DC/20
103383_en_02 PHOENIX CONTACT 10
11 Connection to various systems
+
LN
−
PE
PE
N
L
+
LN
−
PE
PEN
L
+
LN
−
PE
PEN
L
+
LN
−
PE
L2(N)
L1
+
LN
−
PE
PE
N
L3
L2
L1
+
LN
−
PE
PEN
L3
L2
L1
+
LN
−
PE
N
L3
L2
L1
+
LN
−
PE
L3
L2
L1
TN-S TN-C TT iT
The connection for 100 V AC ... 240 V AC is established using the L, N, and P screw connections.
The device can be connected to 1-phase AC networks or to two of the phase conductors of three-phase systems (TN, TT or
IT systems in accordance with VDE 0100-300/IEC 60364-3) with nominal voltages of 100 V AC ... 240 V AC.
The device also continues to work on short-term input voltages > 300 V AC.
For operation on two of the phase conductors of a three-phase system, an isolating facility for all poles must
be provided.
12 Input
QUINT POWER
++
---
Output DC V20A12
LNPE
Input AC 100-240 V
13 14
Signal
D
C
O
K
I
<
I
N
DC OK
Boost
5-18 V
Protection of the primary side
The device must be installed in acc. with the regulations as in
EN 60950. It must be possible to disconnect the device using
a suitable isolating facility outside the power supply.
The primary side line protection, for example, is suitable. For
device protection, there is an internal fuse. Additional device
protection is not necessary.
Recommended backup fuse for mains protection
Power circuit breaker 10 A or 16 A, characteristic B (or
identical function). In DC applications, a suitable fuse must be
wired in upstream.
CAUTION
If an internal fuse is triggered, there is most
probably a malfunction in the device. In this
case, the device must be inspected in the
factory!