QUINT-PS/ 1AC/12DC/20
103383_en_02 PHOENIX CONTACT 4
DC OK active
Output description U
OUT
> 0.9 x U
N
: High signal
Voltage + 5 V DC ... 12 V DC
Current 20 mA (short circuit resistant)
Status display "DC OK" LED green / U
OUT
< 0.9 x U
N
: LED flashing
DC OK floating
Output description Relay contact, U
OUT
> 0.9 x U
N
: Contact closed
Voltage 30 V AC/DC ( 0.5 A / at 60 V AC/DC)
Current 1 A
Status display "DC OK" LED green / U
OUT
< 0.9 x U
N
: LED flashing
POWER BOOST, active
Output description I
OUT
< I
N
: High signal
Voltage + 5 V DC ... 12 V DC
Current 20 mA (short circuit resistant)
Status display LED "BOOST", yellow / I
OUT
> I
N
: LED on
General data
Insulation voltage input/output 4 kV AC (type test)
2 kV AC (routine test)
Insulation voltage input / PE 3.5 kV AC (type test)
2 kV AC (routine test)
Insulation voltage output / PE 500 V DC (routine test)
Degree of protection IP20
Class of protection I, with PE connection
MTBF > 500 000 h in acc. with IEC 61709 (SN 29500)
Housing material Steel sheet, zinc-plated
Dimensions W / H / D (state of delivery) 90 mm / 130 mm / 125 mm
Dimensions W / H / D (90° turned) 122 mm / 130 mm / 93 mm
Weight 1.5 kg
Ambient conditions
Ambient temperature (operation) -25 °C ... 70 °C (> 60°C derating)
Ambient temperature (storage/transport) -40 °C ... 85 °C
Max. permissible relative humidity (operation) 95 % (at 25°C, no condensation)
Vibration (operation) < 15 Hz, amplitude ±2.5 mm in acc. with IEC 60068-2-6
15 Hz ... 150 Hz, 2.3g, 90 min.
Shock 30g in all directions in acc. with IEC 60068-2-27
Pollution degree in acc. with EN 50178 2
Climatic class 3K3 (in acc. with EN 60721)
Standards
Electrical Equipment for Machinery EN 60204
Safety transformers for power supply units IEC 61558-2-17
Electrical safety (of information technology equipment) IEC 60950/VDE 0805 (SELV)
Electronic equipment for use in electrical power installations EN 50178/VDE 0160 (PELV)
SELV IEC 60950 (SELV) and EN 60204 (PELV)
Safe isolation DIN VDE 0100-410
DIN VDE 0106-1010
Protection against electric shock DIN 57100-410
Protection against electric shock, basic requirements for safe isolation in
electrical equipment
DIN VDE 0106-101
QUINT-PS/ 1AC/12DC/20
103383_en_02 PHOENIX CONTACT 5
Limitation of mains harmonic currents EN 61000-3-2
Device safety GS (tested safety)
Network variants (undervoltage) Semi F47-200
Certificate CB Scheme
Approvals
UL approvals UL Listed UL 508
UL/C-UL Recognized UL 60950
Conformance with EMC guideline 2004/108/EC and for low-voltage guideline 2006/95/EC
Noise immunity according to EN 61000-6-2
Electrostatic discharge EN 61000-4-2
Housing Level 4
Contact discharge 8 kV
Discharge in air 15 kV
Comments Criterion B
Electromagnetic HF field EN 61000-4-3
Housing Level 4
Frequency range 80 MHz ... 1000 MHz
Field intensity 20 V/m
Comments Criterion A
Fast transients (burst) EN 61000-4-4
Input 4 kV (level 4 - asymmetrical)
Output 2 kV (level 1 - asymmetrical)
Signal 1 kV (level 1 - asymmetrical)
Comments Criterion B
Surge current loads (surge) EN 61000-4-5
Input 4 kV (inst. class 4 - asymmetrical: conductor to ground)
2 kV (inst. class 4 -symmetrical: conductor to conductor)
Output 2 kV (level 3 - asymmetrical: conductor to ground)
1 kV (level 1 - symmetrical: conductor to conductor)
Signal 1 kV (level 3 - asymmetrical: conductor to ground)
Comments Criterion B
Conducted interference EN 61000-4-6
Input/Output/Signal Level 3 - asymmetrical
Frequency range 0.15 MHz ... 80 MHz
Voltage 10 V
Comments Criterion A
Voltage dips EN 61000-4-11
Input (mains buffering > 20 ms)
Comments Criterion B
Emitted interference in acc. with EN 61000-6-3
Radio interference voltage in acc. with EN 55011 EN 55011 (EN 55022) Class B, area of application: Industry and residential
Emitted radio interference in acc. with EN 55011 EN 55011 (EN 55022) Class B, area of application: Industry and residential
Standards (Continued)
QUINT-PS/ 1AC/12DC/20
103383_en_02 PHOENIX CONTACT 6
5Structure
QUINT POWER
++
---
Output DC 2V 20A1
LNPE
Input AC 100-240 V
13 14
Signal
D
C
O
K
I
<
I
N
DC OK
Boost
518-V
1
2
9
6
7
8
3
4
5
1 AC input
2 DC output
3 POWER BOOST switching output, active
4 DC OK switching output active
5 DC OK output, floating
6 Potentiometer 5 V DC ... 18 V DC
7 "DC OK" LED
8 "BOOST" LED
9 Universal DIN rail adapter UTA 107/30
[mm
2
] AWG [Nm]
solid stranded Torque
Input 0.2 - 6 0.2 - 4 18 - 10 0.5 - 0.6
Output 0.2-6 0.2-4 12-10 0.5-0.6
Signal 0.2-6 0.2-4 18-10 0.5-0.6
Input data
Input nominal voltage range 100 V AC ... 240 V AC
AC input voltage range 85 V AC ... 264 V AC
Short-term input voltage 300 V AC
DC input voltage range 90 V DC ... 350 V DC
AC frequency range 45 Hz ... 65 Hz
DC frequency range 0 Hz
Input fuse, integrated 12 A (slow-blow, internal)
Recommended backup fuse for mains protection 10 A
16 A (characteristic B)
Type of connection Screw connection
Stripping length 7 mm
Output data
Nominal output voltage 12 V DC ±1%
Setting range of the output voltage 5 V DC ... 18 V DC (> 12 V constant capacity)
Output current 20 A (-25°C ... 70°C)
26 A (with POWER BOOST, -25°C ... 40°C permanent)
120 A (with SFB technology, 12 ms)
Type of connection Screw connection
Stripping length 7 mm

2866721

Mfr. #:
Manufacturer:
Phoenix Contact
Description:
DIN Rail Power Supplies QUINT-PS/1AC/12DC/20 12VDC 20A
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union