QUINT-PS/ 1AC/12DC/20
103383_en_02 PHOENIX CONTACT 7
6Block diagram
13
I<I
N
DC OK
14
L (+)
N (-)
PE
active
PFC
7Safety notes
DANGER OF EXPLOSION!
Only remove equipment when it is disconnected and not in the potentially explosive area.
DANGER
The device contains dangerous live elements and high levels of stored energy.
Never carry out work when the power is turned on.
WARNING
Before startup please ensure:
The mains connection has been carried out by a competent person and protection against electric shock is
guaranteed!
The device can be disconnected outside the power supply unit in accordance with the regulations as in EN
60950 (e.g. through primary side line protection)!
The ground conductor is connected!
All feed lines are sufficiently protected and dimensioned!
All output lines are dimensioned according to the maximum output current of the device or separately
protected!
Sufficient convection is guaranteed!
CAUTION
The power supply units are built-in devices. The device may only be installed and put into operation by qualified
personnel. The corresponding national regulations must be observed.
QUINT-PS/ 1AC/12DC/20
103383_en_02 PHOENIX CONTACT 8
8 Installation
QUINT POWER
++
-
--
O
utp
ut
D
C
V0A12 2
L
NPE
Inp
ut
AC
10
0-2
40
V
13 14
S
ignal
D
C
O
K
I
<
I
N
D
C
O
K
Boost
5-18 V
ATTENTION
In order to ensure sufficient convection, we
recommend a minimum vertical distance of 5
cm to the other modules.
A lateral distance of 5 mm, and in the case of
active components, that of 15 mm is necessary
for proper functioning of the module.
Depending on the ambient temperature and
the load of the module, the housing can
become very hot!
The power supply unit can be snapped onto all
DIN rails in acc. with EN 60715. They must be
mounted horizontally (connecting terminal
blocks top and bottom).
9 Installation position
QUINT POWER
++
---
Output DC 2 V 20 A1
LNPE
Input AC 100-240 V
13 14
Signal
DC
OK
I
<
I
N
DC OK
Boost
5-18 V
90
55
122
130
50
115
230
Slim-style installation: Installation depth 125 mm (+ DIN rail)
(state at delivery)
Low-profile installation: Installation depth 93 mm (+ DIN rail)
QUINT-PS/ 1AC/12DC/20
103383_en_02 PHOENIX CONTACT 9
10 Mounting on DIN rails
A
B
B
A
Slim-style installation
Assembly:
Position the module with the DIN rail guide on the upper edge
of the DIN rail, and snap it in with a downward motion.
Removing:
Pull the snap lever open with the aid of a screwdriver and slide
the module out at the lower edge of the DIN rail.
Low-profile installation
Low-profile installation can be achieved by mounting the device at right-angles to the DIN rail. Mount the DIN rail adapter
(UTA 107/30) as described in the figure. No additional mounting material is required. Fixing screws: Torx T10 (torque 0.8 Nm
... 0.9 Nm).

2866721

Mfr. #:
Manufacturer:
Phoenix Contact
Description:
DIN Rail Power Supplies QUINT-PS/1AC/12DC/20 12VDC 20A
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union

Products related to this Datasheet