LT8697
13
8697fb
For more information www.linear.com/LT8697
APPLICATIONS INFORMATION
Cable Drop Compensation
The LT8697 includes the necessary circuitry to implement
cable drop compensation. Cable drop compensation allows
the regulator to maintain 5V regulation on the USB V
LOAD
despite high cable resistance. The LT8697 increases its
local output voltage V
OUT
above 5V as the load increases
to keep V
LOAD
regulated to 5V. This compensation does
not require running an additional pair of Kelvin sense
wires from the regulator to the load, but does require the
system designer to know the cable resistance R
CABLE
as
the LT8697 does not sense this value.
Program the cable drop compensation using the follow
-
ing ratio:
R
CBL
= 20.55
R
SENSE
R
CDC
R
CABLE
where R
CDC
is a resistor tied between the regulator output
and the USB5V pin, R
CBL
is a resistor tied between the
RCBL pin and GND, R
SENSE
is the sense resistor tied be-
tween the ISP and ISN pins in series between the regulator
output
and the load, and R
CABLE
is the cable resistance.
R
SENSE
is typically chosen based on the desired current
limit and is typically 20mΩ for 2.1A systems and 50
for 0.9A. See the Setting the Current Limit section for
more information.
The current flowing into the USB5V pin through R
CDC
is
identical to the current flowing out of the R
CBL
resistor.
While the ratio of these two resistors should be chosen per
the equation above, choose the absolute values of these
resistors to keep this current between 30µA and 200µA at
full load current. This restriction results in R
CBL
and R
CDC
values between 5k and 33k. If I
USB5V
is too low, capacitive
loading on the USB5V and RCBL pins will degrade the load
step transient performance of the regulator. If I
USB5V
is
too high, the RCBL pin will go into current limit and the
cable drop compensation
feature will not work.
Capacitance across
the remote load to ground downstream
of R
SENSE
forms a zero in the LT8697’s feedback loop
due to cable drop compensation. C
CDC
reduces the cable
drop compensation gain at high frequency. The 1nF C
CDC
capacitor tied across the 10k R
CDC
is required for stability
of the LT8697’s output. If R
CDC
is changed, C
CDC
should
also be changed to maintain roughly the same 10µs RC
time constant. If the capacitance across the remote load
is large compared to the LT8697 output capacitor tied to
the SYS pin, a longer R
CDC
C
CDC
time constant may be
necessary for stability depending on the amount of cable
drop compensation used. Output stability should always
be verified in the end application circuit.
The LT8697 limits the maximum voltage of V
OUT
by
limiting the voltage on the SYS pin V
SYS
to 5.8V. If the
cable drop compensation is programmed to compensate
for more than 0.8V of cable drop at the maximum I
LOAD
,
this V
SYS
maximum will prevent V
OUT
from rising higher
and the voltage at the point of load will drop below 5V.
The following equation shows how to
derive the LT8697
output voltage V
OUT
:
V
OUT
= 5V+
20.55 I
LOAD
R
SENSE
R
CDC
R
CBL
As stated earlier, the LT8697’s cable drop compensation
feature does not allow V
OUT
to exceed the SYS regula-
tion point of 5.8V. If additional impedance is placed in
between
the SYS pin and the OUT node such as R
SENSE
or a USB Switch, the voltage drop through these imped-
ances at
the maximum I
LOAD
must also be factored in to
this maximum allowable V
OUT
value. Refer to Figure 1
for load lines of V
OUT
and V
LOAD
to see how cable drop
compensation works.
Figure 1. Cable Drop Compensation Load Line
LOAD CURRENT (A)
0
4.8
VOLTAGE (V)
5.2
5.6
5.0
5.4
6.0
5.8
1 2
8697 F01
30.5 1.5 2.5
V
LOAD
V
OUT
R
CABLE
= 0.3Ω
R
SENSE
= 20mΩ
R
CDC
= 10kΩ
R
CBL
= 13.7kΩ
LT8697
14
8697fb
For more information www.linear.com/LT8697
APPLICATIONS INFORMATION
Cable Drop Compensation Over a Wide Temperature
Range
Cable drop compensation with zero temperature variation
may be used in many applications. However, matching
the cable drop compensation temperature variation to the
cable resistance temperature variation may result in bet
-
ter overall output voltage accuracy over a wide operating
temperature range. For example, in an application with
0.26Ω of wire resistance and a maximum output current
of 2.1A, cable drop compensation adds 0.55V at 25°C to
the output at max load for a fully compensated wire re
-
sistance. If
the wire in this example is copper, the copper
resistance
temperature coefficient of about 4000ppm/°C
results in an output voltage error of –130mV at 85°C and
55mV at 0°C. Figure 2a shows this behavior.
See Table 1 for a list of copper wire resistances vs gauge.
Table 1. Copper Wire Resistance vs Wire Gauge
AWG RESISTANCE OF Cu WIRE AT 20°C (mΩ/m)
15 10.4
16 13.2
17 16.6
18 21.0
19 26.4
20 33.3
21 42.0
22 53.0
23 66.8
24 84.2
25 106
26 134
27 169
28 213
29 268
30 339
31 427
32 538
33 679
34 856
35 1080
36 1360
37 1720
38 2160
39 2730
40 3440
Cable drop compensation can be made to vary positively
versus temperature with the addition of a negative tem-
perature coefficient
(
NTC) resistor as a part of the RCBL
resistance. This circuit idea assumes the NTC resistor is
at the same temperature as the cable. Figure 2b shows
an example resistor network for R
CBL
that matches cop-
per resistance
variation over a wide –40°C to 125°C
temperature range. Figure 2c shows the resultant cable
drop compensation output at several temperatures using
RCBL with negative temperature variation.
Figure 2b. R
CBL
Resistor Network for Matching
Copper Wire Temperature Coefficient
Figure 2a. Cable Drop Compensation Through 4m of AWG 20
Twisted-Pair Cable (260mΩ) without Temperature Compensation
TEMPERATURE (°C)
–20
4.8
VOLTAGE (V)
5.0
5.2
5.4
5.6
5.8
V
LOAD
V
OUT
0
20 40 60
8697 F02a
80 100
I
LOAD
= 2.1A
CABLE = 4 METERS AWG20
TWISTED-PAIR COPPER
10k
1%
RCBL
8697 F02b
10k
1%
MURATA
NCP21XV103J03RA
10k THERMISTOR
LT8697
15
8697fb
For more information www.linear.com/LT8697
APPLICATIONS INFORMATION
Table 2. Copper Wire Inductors for Use as Sense Resistors
VENDOR PART NUMBER DC RESISTANCE (mΩ)
Coilcraft NA5931-AL 15.7 ±5%
Coilcraft NA5932-AL 21.8 ±5%
Coilcraft NA5933-AL 32.4 ±5%
Coilcraft NA5934-AL 34.3 ±5%
Coilcraft NA5935-AL 44.1 ±5%
Coilcraft NA5936-AL 47.2 ±5%
Effect of Cable Inductance on Load Step Transient
Response
The inductance of long cabling limits the peak-to-peak
transient performance of a 2-wire sense regulator to fast
load steps. Since a 2-wire sense regulator like the LT8697
detects the output voltage at its local output and not at
the point of load, the load step response degradation due
to cable inductance is present even with cable resistance
compensation. The local regulator output capacitor and
the input capacitor of the remote load form a LC tank
circuit through the inductive cabling between them. Fast
load steps through long cabling show a large peak-to-peak
transient response and ringing at the resonant frequency of
the circuit. This ringing is a property of the LC tank circuit
and does not indicate regulator instability.
The NTC resistor does not give a perfectly linear transfer
function versus temperature. Here, for typical component
values, the worse case error is <10% of the cable compen
-
sation output,
or <1% of the total output voltage accuracy.
Better output voltage accuracy versus
temperature can be
achieved if R
CBL
resistor values are optimized for a nar-
rower temperature
range. Contact LTC for help designing
an R
CBL
resistor network.
Choosing an R
SENSE
resistor with a temperature coefficient
that matches the cable resistance temperature coefficient
can reduce this output voltage error overtemperature if the
sense resistor is at roughly the same ambient temperature
as R
SENSE
. Small value copper wire inductors can be used
in this way if the inductor resistance is well specified.
Figure 2d shows the resultant cable drop compensation
output at several temperatures using a copper R
SENSE
.
Use of an R
SENSE
that varies over temperature will make
the LT8697 output current limit vary over temperature. To
achieve the rated output current over the full operating tem
-
perature range, a higher room temperature output current
limit may be necessary. Table 2 shows the manufacturer
specified DCR of several copper wire inductors that may
be used for R
SENSE
.
Figure 2c. Cable Drop Compensation Through 4m of AWG 20
Twisted-Pair Cable (260mΩ) with Temperature Compensation
Using NTC R
CBL
Figure 2d. Cable Drop Compensation Through 4m of AWG 20
Twisted-Pair Cable (260mΩ) with Temperature Compensation
Using Copper R
SENSE
TEMPERATURE (°C)
–20
4.8
VOLTAGE (V)
5.0
5.2
5.4
5.6
5.8
0
20 40
V
LOAD
V
OUT
60
8697 F02c
80 100
I
LOAD
= 2.1A
CABLE = 4 METERS AWG20
TWISTED-PAIR COPPER
TEMPERATURE (°C)
–20
4.8
VOLTAGE (V)
5.0
5.2
5.4
5.6
5.8
0
20 40
V
LOAD
V
OUT
60
8697 F02d
80 100
I
LOAD
= 2.1A
CABLE = 4 METERS AWG20
TWISTED-PAIR COPPER

LT8697HUDD#PBF

Mfr. #:
Manufacturer:
Analog Devices / Linear Technology
Description:
Switching Voltage Regulators USB 5V 2.5A Output, 42V Inpuut Synchronous Step-Down Regulator with Cable Drop Compensation
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union