2. PID Control Using Auto-tuning
Changing Parameters
indicates that there is a parameter. Keep
on pressing the mode key until the de-
sired parameter is selected.
Changing Set Values
Use the or keys to
change the set value displayed
in the setup menu.
Display
E5CN E5GN
No. 1 display
No. 2 display
No. 1 display
No. 2 display
Input type: 4 T thermocouple -200 to 400°C
Control method: PID control
ST (self-tuning): OFF
Calculate PID constants by AT (auto-tuning).
Alarm type: 2 upper limit
Alarm value 1: 30°C (For setting deviation)
Set point: 150°C
Setup procedure
Power ON
Set input
specifications
Set control
specifications
Self-tuning
Set alarm values
Start operation
Power ON
In PID control
To cancel ST
Check the
control period.
Check alarm
type.
Press key for at least one second.
Press keys
to set set point to
“150 C.”
Execute AT
(auto-tuning).
Press
keys to select
input type.
Press
keys to select
PID control.
Press
keys to set ST
to OFF.
Control period
(heat) (unit:
seconds)
Process value/
set point
Press key for less than one second.
To execute AT
Press key for less than one second.
Make sure that
set point is
“150 C.”
Make sure that
control is running.
Press
keys to set
alarm value to
“30 C.”
Process value/
set point
During run
Alarm
value 1
Start program execution
Check control period
Check alarm type
Set the set point
Set operation status
(upper-limit
alarm)
Typical Example
When set to ON,
self-tuning operates.
Recommended set-
tings: 20 seconds for
the relay output and
2 seconds for the
SSR output.
Set to for execut-
ing AT and to
for stopping AT.
AT execution
Process value/
set point
Input type
Press key for at least three
seconds. Control stops.
Alarm 1 type
After AT execution.
During AT execution.
While AT is being
executed, SP will flash.
PV/SP
After AT execution.
During AT execution.
Operation level
Initial setting level
Operation level
Adjustment level
Operation level
E5GN
E5GN
Specification Setting After Turning ON Power
OUTLINE OF OPERATION PROCEDURES
Key Operation
In the following descriptions, all the parameters are introduced in the display sequence. Some parameters may not be displayed
depending on the protect settings and operation conditions.
Note: 1. Of these levels, the initial setting level,
communications setting level, advanced function
setting level and calibration level can be used only
when control has stopped. Note that control is
stopped when these four levels are selected. When
switched back to the operation level from one of these
levels, control will start.
2. For the calibration mode, refer to the relevant
Operation Manual (H100 or H101).
3. On the E5GN, the Key is the Key.
Power ON
Operation level
Adjustment level
+key
1 second min.
key
1 second min.
key
3 second min.
Less than
1 second
key
Control stops
Protect level
Communications
setting level
Initial setting level
key
1 second min.
Less than
1 second
key
Advanced
function setting level
Calibration level
Password input
set value “1201”
Password input
set value “--169”
Control in progress
Control stopped
Level change
DESCRIPTION OF EACH LEVEL
Operation Level
This level is displayed when you turn the power ON. You can
move to the protect level, initial setting level and adjustment level
from this level.
Normally, select this level during operation. During operation, the
process value, set point and manipulated variable can be
monitored, and the alarm value and upper- and lower-limit alarms
can be monitored and modified.
Adjustment Level
To select this level, press the key once for less than one
second.
This level is for entering set values and offset values for control.
This level contains parameters for setting the set values, AT
(auto-tuning), communications writing enable/disable, hysteresis,
multi-SP, input shift values, heater burnout alarm (HBA) and PID
constants. You can move to the top parameter of the operation
level or initial setting level from here.
Initial Setting Level
To select this level, press the key for at least three seconds in
the operation level. This level is for specifying the input type,
selecting the control method, control period, setting direct/reverse
action and alarm type. You can move to the advanced function
setting level or communications setting level from this initial
setting level. To return to the operation level, press the
key for
at least one second. To move to the communications setting
level, press the
key once for less than one second.
E5GN
E5GN
Protect Level
To select this level, simultaneously press the and keys
for at least one second. This level is to prevent unwanted or
accidental modification of parameters. Protected levels will not be
displayed, and so the parameters in that level cannot be
modified.
Communications Setting Level
To select this level, press the key once for less than one
second in the initial setting level. When the communications
function is used, set the communications conditions in this level.
Communicating with a personal computer (host computer) allows
set points to be read and written, and manipulated variables to be
monitored.
Advanced Function Setting Level
To select this level, you must enter the password (“-169”) in the
initial setting level.
You can move only to the calibration level from this level.
This level is for setting the automatic return of display mode, MV
limiter, event input assignment, standby sequence, alarm
hysteresis, ST (self-tune) and to move to the user calibration
level.
Calibration Level
To select this level, you must enter the password (“1201”) in the
advanced function setting level. This level is for offsetting
deviation in the input circuit.
You cannot move to other levels by operating the keys on the
front panel from the calibration level. To cancel this level, turn the
power OFF then back ON again.