Specifications
RATINGS
Supply voltage 100 to 240 VAC, 50/60 Hz 24 VAC, 50/60 Hz/24 VDC
Operating voltage range 85% to 110% of rated supply voltage
Power consumption 7VA 4VA/2.5W
Sensor input Thermocouple: K, J, T, E, L, U, N, R, S, B
Platinum resistance thermometer: Pt100, JPt100
Non-contact temperature sensor: K10 to 70 C, K60 to 120 C, K115 to 165 C, K160 to 260 C
Voltage input: 0 to 50 mV
Control output
Relay output SPST-NO, 250 VAC, 2 A (resistive load), electrical life: 100,000 operations
Voltage output 12 VDC (PNP), max. load current: 21 mA, with short-circuit protection
Alarm output SPST-NO, 250 VAC, 1 A (resistive load), electrical life: 100,000 operations
Control method PID or ON/OFF control
Setting method Digital setting using front panel keys
Indication method 7-segment digital display and single-lighting indicator
Other functions According to controller model
Ambient temperature
-10 Cto55 C(14 F to 131 F) with no condensation or icing
Ambient humidity 25% to 85% relative humidity
Storage temperature
-25 Cto65 C (-13 F to 149 F) with no condensation or icing
CHARACTERISTICS
Indication accuracy Thermocouple:
( 0.5% of indicated value or 1 C, whichever greater) 1 digit max. (See Note.)
Platinum resistance thermometer:
( 0.5% of indicated value or 1 C, whichever greater) 1 digit max.
Analog input: 0.5% FS 1 digit max.
CT input: 5% FS 1 digit max.
Hysteresis 0.1 to 999.9 EU (in units of 0.1 EU)
Proportional band (P) 0.1 to 999.9 EU (in units of 0.1 EU)
Integral time (I) 0 to 3999 s (in units of 1 s)
Derivative time (D) 0 to 3999 s (in units of 1 s)
Control period 1to99s(inunitsof1s)
Manual reset value 0.0% to 100.0% (in units of 0.1%)
Alarm setting range -1999 to 9999 (decimal point position depends on input type)
Sampling period 500 ms
Insulation resistance 20 M
min. (at 500 VDC)
Dielectric strength 2000 VAC, 50 or 60 Hz for 1 min (between different charging terminals)
Vibration resistance 10 to 55 Hz, 10 m/s
2
for 2 hours each in X, Y and Z directions
Shock resistance 300 m/s
2
, 3 times each in 3 axes, 6 directions (relay: 100 m/s
2
)
Note: The indication of K thermocouples in the -200
°
C to 1300
°
C range, and T and N thermocouples at a temperature of -100
°
C or less,
and U and L thermocouples at any temperature is
±
2
°
C
±
1 digit maximum. The indication of B thermocouples at a temperature of
400
°
C or less is unrestricted.
The indication of R and S thermocouples at a temperature of 200
°
Corlessis
±
3
°
C
±
1 digit maximum.
(This table continues on the next page.)
E5GN
E5GN
Characteristics Table
-- continued from previous page
Weight
Approx. 90 g Mounting bracket: approx. 10g
Protective structure
Front Panel NEMA4 for indoor use (equivalent to IP66)
Rear Case IP20
Terminals IP00
Memory protection EEPROM (non-volatile memory) (number of writes: 100,000)
EMC Emission Enclosure: EN55011 Group 1 class A
Emission AC Mains: EN55011 Group 1 class A
Immunity ESD: EN61000-4-2: 4 kV contact discharge (level 2)
8 kV air discharge (level 3)
Immunity RF-interference: ENV50140: 10 V/m (amplitude modulated,
80MHzto1GHz)(level3)
10 V/m (pulse modulated, 900 MHz)
Immunity Conducted Disturbance: ENV50141: 10 V (0.15 to 80 MHz) (level 3)
Immunity Burst: EN61000-4-4: 2 kV power-line (level 3)
2 kV I/O signal-line (level 4)
Approval standards UL3121-1, CSA22.2 No. 14, E.B.1402C
Conforms to EN50081-2, EN50082-2, EN61010-1 (IEC1010-1)
Conforms to VDE0106/part 100 (Finger Protection), when the terminal cover is mounted.
COMMUNICATIONS SPECIFICATIONS
Transmission path connection Multiple points
Communications method RS-485 (two-wire, half duplex)
Synchronization method Start-stop synchronization
Baud rate 1,200/2,400/4,800/9,600/19,200 bps
Transmission code ASCII
Data bit length 7or8bits
Stop bit length 1or2bits
Error detection Vertical parity (none, even, odd)
Frame check sequence (FCS): with SYSMAC WAY
Block check character (BCC): with CompoWay/F
Flow control Not available
Interface RS-485
Retry function Not available
Communications buffer 40 bytes
Note: The baud rate, data bit length, stop bit length, or vertical parity can be individually set using the communications setting level.
E5GN
E5GN
Nomenclature
E5GN
Temperature Unit
The temperature unit is displayed
when the display unit parameter is
set to a temperature. Indication is
determined by the currently
selected “temperature unit” parameter
set value. When this parameter is set
to “
°
C,” “ is displayed, and when set
to “
°
F, ” is displayed.
Operation Indicators
1. AL (alarm)
Lights when alarm output is
ON.
2. CMW (communications
writing control)
Lights when communica-
tions writing is enabled and
is out when it is disabled.
3. STP (stop)
Lights when control of the
E5GN has been stopped.
During control, this indicator
lights when an event or the
run/stop function has been
stopped, or, this indicator is
out.
4. OUT (control output)
Lights when control output
is ON.
No. 1 Display
Displays the process value or
parameter type.
No. 2 Display
Displays the set point, manipu-
lated variable or set value (setup)
of the parameter.
Up Key
Each press of this key increases
values displayed on the No.2
display. Holding down this key
continuously increases values.
Down Key
Each press of this key decreases
values displayed on the No.2
display. Holding down this key
continuously decreases values.
Mode Key
Press this key to select parameters
within each level.
Level Key
Press this key to select the setup
level. The setup level is selected
in this order: “operation level”
←→
“adjustment level,” “initial setting
level”
←→
“communications
setting level.”
Level + Mode Key
This key combination sets the
E5GN to the “protect level.”

E5GN-QTC AC/DC24