E5GN
E5GN
PARAMETERS
Parameters related to setting items for each level are marked in
boxes in the flowcharts and brief descriptions are given as
required. At the end of each setting item, press the mode key to
return to the beginning of each level.
Display
E5CN E5GN
No. 1 display
No. 2 display
No. 1 display
No. 2 display
Password input
set value “1201”
Advanced function
setting level
Calibration level
Password input
set value “-169”
Control stops.
Initial setting level
Less than 1 second
key
Communications
setting level
Power ON
Operation level
1 second min.
+key
Protect level
Control in progress
Control stopped
Adjustment level
1 second
min.
key
1 second
min.
key
3 second min.
key
Level change
Less than 1 second
key
Note: Advanced function levels are for E5CN.
Operation Level
PV
PV/SP
Add in the “additional
PV display” parameter.
Multi-SP
Set point during SP ramp
Heater current value monitor
Run/stop
Alarm value 1
Upper-limit
alarm value 1
Lower-limit
alarm value 1
Set either of
these parameters.
Alarm value 2
Upper-limit
alarm value 2
Lower-limit
alarm value 2
Set either of
these parameters.
MV monitor (heat)
MV monitor (cool)
Current value
monitor of HBA
Select SP.
: RUN
:STOP
Power ON
1
1
1
1
1
1
1
Note: 1. For E5CN only.
E5GN
E5GN
Initial Setting Level
Input type
Scaling upper limit
Decimal point
Temperature unit
Set point upper limit
PID / ON/OFF
Standard/heating and cooling
ST
Control period (heat)
Alarm 1 type
Move to advanced function
setting level
Set the pulse
output cycle.
Direct/reverse operation
Alarm 2 type
Limit the set point.
Select the control system.
Self-tuning
Select the alarm
mode.
Control period (cool)
For analog input
(Input type: 16)
0- to 50-mVsetting
Number of displayed digits
: °C
: °F
: ON/OFF control
: PID control
: Standard
: Heating/cooling
: Enabled
: Disabled
: Reverse
: Direct
Set point lower limit
Scaling lower limit
1
1
1
Note: 1. For E5CN only.
Adjustment Level
Hysteresis (heat)
AT execute/cancel
Communications writing
Heater current
value monitor
HBA
function
Set point 0
Set point 1
Temperature input shift
1-point shift
2-point shift
Proportional band
PID settings
Cooling coefficient
Dead band
Usedinheating and
cooling control
Manual reset value
Auto-tuning
Heater burnout
detection
Set point 2
Set point 3
Lower-limit temperature
input shift value
Upper-limit temperature
input shift value
Derivative time
Integral time
Clear the offset during
stabilization of P or PD
control.
Set hysteresis.
P
I
D
Hysteresis (cool)
: Enabled
: Disabled
2
2
2
2
2
multi-SP functions
are for E5CN only.
Note: 2. For E5CN only.
E5GN
E5GN
Protect Level
Operation/adjustment protection
Restricts display and modification of menus in the
operation and adjustment levels.
Initial setting/communications protection
Restricts display and modification of menus in the initial
setting, operation level and adjustment levels.
Setting change protection
Protects changes to setups by operating the front
panel keys.
Operation/Adjustment Protection
The following table shows the relationship between set values
and the range of protection.
Level
Set value
0 1 2 3
Operation
l
l
PV
level
PV/SP
Other X X
Adjustment level X X X
When this parameter is set to “0,” parameters are not protected.
Default setting: 0
:
Can be displayed and changed
: Can be displayed
: Cannot be displayed and move to other levels not possible
Initial Setting/Communications Protection
This protect level restricts movement to the initial setting level,
communications setting level and advanced function setting level.
Set
value
Initial setting
level
Communications
setting level
Advanced
function
setting level
0
1 X
2 X X X
Default setting: 1
: Move to other levels possible
: Move to other levels not possible
Setting Change Protection
This protect level protects setup from being changed by
operating the keys on the front panel.
Set value
Description
OFF Setup can be changed by key operation.
ON Setup cannot be changed by key operation.
(The protect level, can be changed.)
Default setting: OFF