LT3905
10
3905fa
For more information www.linear.com/LT3905
Table 1. Inrush Peak Current
V
IN
(V) L (μH) C (μF) I
p
(A)
3.3 10 1 0.47
3.3 22 1 0.37
5 10 1 0.81
5 22 1 0.63
Voltage Feedback
The LT3905 error amplifier is equipped with both a fixed
internal reference of 1.248V and an adjustable external
reference input (CTRL). This feature allows users to select
between using the built-in reference and an external refer
-
ence voltage
when programming the output voltage. It is
possible
to adjust the voltage at the CTRL pin while the
device is operating, in order to alter the output voltage of
LT3905 and therefore the bias voltage of the APD.
To choose the fixed internal reference, tie the CTRL pin
to a voltage higher than 1.5V, such as the input voltage.
The FB pin is regulated to 1.248V. When the CTRL pin is
below 1.248V, the FB pin is regulated to the voltage at
the CTRL pin.
To set the output voltage, tie FB to a resistor divider between
MONIN and GND. The R2 value can be selected to provide
a minimum load to the device, to maintain a constant
switching frequency when the APD current is very low.
Preventing entry into pulse-skipping mode is an important
consideration for
post-filtering the regulator output.
The
value of R1 is determined using the desired output
voltage and the reference voltage, V
REF
. Where V
REF
is
either the internal or external reference voltage as defined
by the state of the CTRL pin, and R2 is the resistor value
previously selected for minimum load.
R1= R2
V
MONIN
V
REF
1
applicaTions inForMaTion
Converter Standby
It is also possible to put the switching converter in standby
mode by driving FB to a voltage higher than 1.8V. In this
mode, only the internal reference and the LOS_MON cir
-
cuitry remain active,
and quiescent current drops to 250μA.
Inductor Selection
The inductor used with LT3905 should have a saturation
rating of 400mA or greater. If the device is used in an
application where the input supply is hot-plugged, the
saturation current should exceed the peak inrush current.
For best loop stability, the inductance value selected should
provide a ripple current of 20% of current limit, or 80mA.
For a given V
IN
and V
OUT
, the inductor value to use in
continuous conduction mode is calculated by:
L =D
V
IN
f 80mA
where:
D=
V
OUT
+1– V
IN
V
OUT
+1
and f is the switching frequency in Hz.
To force the LT3905 to operate in discontinuous conduc-
tion mode
(
DCM), select a smaller value inductor. The
following inequality is true when the LT3905 is operating
in discontinuous conduction mode.
L <
D V
IN
f 400mA
Operating in DCM reduces the maximum output current
and the conversion efficiency.
Capacitor Selection
Use low ESR capacitors at the output to minimize output
voltage ripple. Use only X5R and X7R types, which retain
their capacitance over wider voltage and temperature
ranges than other types. High output voltages typically
require less capacitance for loop stability. Typically use a
1µF capacitor for output voltage less than 25V and 0.22µF
Figure 2. Output Voltage Feedback
LT3905
FB
MONIN
3905 F02
CTRL
R1
R2
LT3905
11
3905fa
For more information www.linear.com/LT3905
capacitor for output voltage beyond 25V. Place the output
capacitor as close as possible to the V
OUT
lead and to the
GND of the IC.
Either ceramic or solid tantalum capacitors may be used
for the input decoupling capacitor, which should be placed
as close as possible to the LT3905. AF capacitor is
sufficient for most applications.
Phase Lead Capacitor
A small value capacitor (i.e., 10pF to 22pF) can be added
in parallel with the R1 resistor between the output and
the FB pin to reduce output perturbation due to a load
step and to improve transient response. This phase lead
capacitor introduces a pole-zero pair to the feedback that
boosts phase margin near the crossover frequency. The
APD is very sensitive to a noisy bias supply. To lowpass
filter noise from the internal reference and error ampli
-
fier, a 0.1µF phase lead capacitor can be used. The corner
frequency of the noise filter is R1 • CPL.
Loss of Signal Monitor
The second largest output current is the LOS_MON
output, at 10% of the APD current. This is typically used
for detecting a loss of signal condition by sensing a
drop in the APD current. The
LOS_MON pin is an input
to the comparator that drives the open-drain LOS pin.
This comparator uses either a fixed internal threshold of
1.248V, activated by pulling the LOS_ADJ pin to V
IN
, or
an adjustable external threshold, activated by driving the
LOS_ADJ pin with a voltage lower than 1.248V. In either
case, the open-drain LOS pin goes high when the voltage
on LOS_MON falls below the threshold.
To program the loss of signal monitor, set a resistor
from LOS_MON to ground such that the LOS_MON volt
-
age reaches the loss of signal threshold at the point the
APD
current has dropped to the desired loss of signal
threshold, IAPD
LOS
.
For the case of internal threshold:
R
LOS _MON
=
10 1.248V
IAPD
LOS
For the case of external threshold, simply replace 1.248V
in the above equation with the external threshold applied
to the LOS_ADJ pin:
R
LOS _MON
=
10 V
LOS _ ADJ
IAPD
LOS
Loss of Signal Hysteresis
The LOS_MON comparator contains internal hysteresis
of typically 20mV on the rising edge of the LOS_MON
voltage. When using an external threshold, additional
external hysteresis can be generated with the addition of
the resistors R7 and R8 shown in Figure 4, where R10 is
the standard pull-up resistor for the LOS signal.
Figure 3. Phase Lead Capacitor
Figure 4. Additional LOS Hysteresis
LT3905
FB
MONIN
3905 F03
CTRL
R1 C
PL
R2
APD Current Monitor
The APD current Monitor is supplied from the MONIN
pin. It provides a current-limited power supply for the
avalanche photodiode on the APD pin, and outputs three
monitor currents proportional to the APD current on the
MON, LOS_MON, and ILIM_MON pins. Each of the moni
-
tor outputs is diode-clamped to a 2.25V internal voltage.
The largest output current is the MON output, at 20% of
the APD current. This output is typically used for precise
system monitoring of the APD bias point, and is tied either
to a resistor to GND or to the input of a transimpedance
amplifier. In either case, it is important to keep the MON
voltage lower than 2.1V, as forward-biasing the internal
diode will clamp the MON voltage and compromise
accuracy.
V
IN
3905 F04
R10
LOS
LOS_ADJ
LOS ADJUST
LOS
R8
R7
LT3905
applicaTions inForMaTion
LT3905
12
3905fa
For more information www.linear.com/LT3905
For this strategy, the ILIM_MON resistor is selected so
the ILIM_MON pin reaches 1.248V at the desired APD
regulation current, IAPD
REG
.
R
ILIM _ MON
=
20 1.248V
IAPD
REG
Although this loop will effectively limit the output voltage to
that which is needed to regulate the APD current, the fast
overload case must be considered as well. The regulation
of the boost converter output is comparatively slow
with respect to an APD overload condition. Additionally,
substantial energy is stored in the charged output capacitor
that should be prevented from flowing into the APD during
a condition of optical flooding. To protect against this type
of overload, the ILIM_MON pin has a fast current regula
-
tor which limits the output current of the APD pin itself.
This current limiting loop has a threshold 100mV above
the 1.248V boost regulation threshold, and two actions
are taken if this threshold is reached.
First, the output current of the APD pin is limited to the
value corresponding to 1.348V on ILIM_MON. For a
shorted or optically flooded APD, the voltage at the APD
pin will drop to any level necessary to limit the current
to the programmed value. Even for the case of the APD
pin shorted to GND, the current will remain limited to the
programmed value and ILIM_MON will continue to indicate
an accurate measurement of APD current.
The second action that is taken in response to an overload
condition is assertion of the open-drain ILIM flag to indicate
the overload condition to the user. It is asserted once
the ILIM_MON voltage exceeds 1.348V and enters active
limiting, and will remain asserted until the ILIM_MON
voltage has dropped by 50mV, indicating that the device
is no longer in active limiting.
The response of the APD current limiter is shown in
Figure5. When the overload is applied, the APD voltage
drops abruptly while the output voltage decays slowly
due to the regulated current load. As the output voltage
reaches the new operating point, the ILIM indicator is
released and the boost converter begins regulating to
1.248V on ILIM_MON.
To compute the values of R7 and R8, start by setting R8
at least 10 times the value of the pull-up resistor R10.
This will prevent undue loading of the LOS signal itself.
Next, compute the total hysteresis using the voltage divider
generated by R7/R8:
V
H
= V
IN
R7
R7+R8
+ 20mV
This hysteresis is composed of two parts, the hysteresis
when LOS_MON is rising (leaving loss of signal) and that
when LOS_MON is falling (entering loss of signal).
Use the formulas below with the value of external threshold
applied to LOS ADJUST to calculate the new rising and
falling thresholds of LOS_MON when using external
hysteresis. Adjust the LOS_MON resistor if necessary to
achieve a desired threshold with respect to APD current.
V
LOS _MON(FALL)
= V
LOS _ ADJUST
R8
R7+R8
V
LOS _MON(RISE)
= V
LOS _ ADJUST
+ 20mV +
R7
V
IN
V
LOS _ ADJUST
R7+R8
Current Limit Monitor
The smallest output current is the ILIM_MON output, at
5% of the APD current. This output is used for regulating
the boost converter to provide a fixed APD current, as well
as detecting and limiting of overload conditions.
When the voltage at ILIM_MON reaches the first threshold
of 1.248V, an auxiliary error amplifier limits the boost
converter output voltage. In this manner, the LT3905 can
regulate a fixed APD current with a single resistor at the
ILIM_MON pin. In this mode, use the FB function to set
a maximum output voltage limit. The FB resistor divider
should be set for an output voltage higher than the expected
output voltage required for the APD and monitor drop. The
ILIM_MON error amplifier is the dominant regulation path,
and the FB error amplifier will only take over to limit the
output voltage in the case of a disconnected APD.
applicaTions inForMaTion

LT3905EUD#TRPBF

Mfr. #:
Manufacturer:
Analog Devices / Linear Technology
Description:
Switching Voltage Regulators 60V Boost DC-DC Converter with APD Current Monitor
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union