© PHOENIX CONTACT - 11/2008
7210_en_02
AUTOMATION
IB IL SGI 2/F ...
Data sheet
1 Function description
The terminal is designed for use within an Inline station.
This terminal is a fast two-channel input module used to
connect load cells, force transducers, mass pressure
transducers, and similar devices based on strain gauges.
The strain gauges can be connected using 6 or 4-wire
technology. The strain gauge output signals are measured
in each bus cycle and updated in the process data (bus-
synchronous process data update). The terminal is
designed for control system applications with increased
speed requirements.
There are two options for data exchange:
Via process data (both inputs in one bus cycle)
Via PCP (both inputs in the "Analog Values" PCP
object)
The measuring values are represented by standardized
16-bit values.
Features
Two inputs for the strain gauges
Sensor supply voltage provided by the terminal, no
external power supply required
Connection of strain gauges in 6 and 4-wire technology
Communication via either process data or parameter
channel (PCP)
Channels are configured independently of one another
using the bus system
Bus-synchronous process data update
Diagnostic indicators
Inline terminal with two fast analog input channels
for connecting strain gauges
A short circuit in the strain gauge supply at one of the two channels also prevents measured data acquisition
at the other channel for the duration of the short circuit.
This data sheet only is valid in connection with the IL SYS INST UM E user manual (see "Documentation" on
page 3).
Make sure you always use the latest documentation.
It can be downloaded at www.download.phoenixcontact.com
.
This data sheet is valid for all products listed on the following page.
TR
D
4x
SGI 2/F
C
H
2
C
H
1
IB IL SGI 2/F ...
7210_en_02 PHOENIX CONTACT 2
Table of contents
1 Function description ................................................................................................................... 1
2 Ordering data.............................................................................................................................. 3
3 Technical data ............................................................................................................................ 4
4 Local diagnostic and status indicators and terminal point assignment....................................... 7
4.1 Local diagnostic and status indicators ...........................................................................................................7
4.2 Function identification ....................................................................................................................................7
4.3 Terminal point assignment............................................................................................................................. 7
5 Internal circuit diagram ............................................................................................................... 8
6 Electrical isolation....................................................................................................................... 9
7 Installation instructions ............................................................................................................... 9
8 Connection notes................................................................................................................................................... 9
9 Connection examples................................................................................................................10
9.1 6-wire connection (a strain gauge load cell per channel) ............................................................................10
9.2 6-wire connection (several strain gauge load cells per channel) ................................................................11
9.3 4-wire connection.........................................................................................................................................12
9.4 Permissible characteristics according to the jumper supply......................................................................... 13
10 Programming data/configuration data .......................................................................................13
11 Process data..............................................................................................................................13
12 OUT process data words...........................................................................................................14
12.1 Output word OUT1 (control word)................................................................................................................14
12.2 Output word OUT2 and OUT3 (parameter word).........................................................................................15
12.3 Parameters for configuration........................................................................................................................15
13 IN process data words...............................................................................................................16
13.1 Input word IN1 (status word)........................................................................................................................16
13.2 Input words IN2 and IN3 .............................................................................................................................. 16
14 PCP communication..................................................................................................................18
14.1 Object dictionary ..........................................................................................................................................18
14.2 Object description ........................................................................................................................................19
15 Startup/measuring jumper detuning ..........................................................................................21
16 Configuration and analog values...............................................................................................21
IB IL SGI 2/F ...
7210_en_02 PHOENIX CONTACT 3
2 Ordering data
Products
Accessories
Documentation
Description Type Order No. Pcs./Pkt.
Inline terminal with two analog input channels for connecting strain gauges,
without accessories,
transmission speed of 500 kbps
IB IL SGI 2/F 2878434 1
Inline terminal with two analog input channels for connecting strain gauges;
complete with accessories (connectors and labeling fields),
transmission speed of 500 kbps
IB IL SGI 2/F-PAC 2878638 1
Inline terminal with two analog input channels for connecting strain gauges,
without accessories,
transmission speed of 2 Mbps
IB IL SGI 2/F 2MBD 2878531 1
Inline terminal with two analog input channels for connecting strain gauges;
complete with accessories (connectors and labeling fields),
transmission speed of 2 Mbit/s
IB IL SGI 2/F-2MBD-PAC 2878735 1
You need two connectors with shield connection and two standard connectors for the IB IL SGI 2/F and IB IL SGI 2/F 2MBD terminals.
Description Type Order No. Pcs./Pkt.
Inline shield connector for analog Inline terminals, without color print IB IL SCN-6 SHIELD 2726353 5
Connector for digital single-channel, two-channel or 8-channel Inline terminals IB IL SCN-8 2726337 10
Shield connection clamp for applying the shield on busbars,
8 mm diameter
SK8 3025163 10
Shield connection clamp for applying the shield on busbars,
14 mm diameter
SK14 3025176 10
Shield connection clamp for applying the shield on busbars,
20 mm diameter
SK20 3025189 10
Shield connection clamp for applying the shield on busbars,
35 mm diameter
SK35 3026463 10
Support for assembly on DIN rails
for 10 mm x 3 mm busbars
AB-SK 3025341 10
Support for mounting on the NS 35/7,5 DIN rail,
for 10 mm x 3 mm busbars
AB-SK 65 3026489 10
Support for direct mounting with contact to the mounting surface AB-SK/E 3026476 10
PEN conductor busbar,
3 mm x 10 mm, length: 1000 mm
NLS-CU 3/10 0402174 1
Power terminal, cross section: 0.5 - 4 mm², width: 7 mm
Color: Gray
AK 4 0404017 50
Power terminal, cross section: 0.5 - 4 mm², width: 7 mm,
Color: Green/yellow
AK G GNYE 0421029 50
Power terminal, cross section: 0.5 - 4 mm², width: 7 mm,
Color: Black
AKG 4 BK 0421032 50
Description Type Order No. Pcs./Pkt.
"Automation terminals of the Inline product range" user manual IL SYS INST UM E 2698737 1

2878735

Mfr. #:
Manufacturer:
Phoenix Contact
Description: