7210_en_02 PHOENIX CONTACT 14
12 OUT process data output words
Three OUT process data words are available.
Configure the terminal channels via the OUT process data words.
Where:
– Output word OUT1 contains the command
– Output word OUT2 contains the parameters for channel 1
– Output word OUT3 contains the parameters for channel 2
The following configurations are possible:
Configuration errors are indicated in the status word. The configuration settings are stored in a volatile memory.
If you change the configuration, the message "Measured value invalid" appears (diagnostic code 8004
hex
), until new
measured values are available.
12.1 Output word OUT1 (control word)
Bit 15 to bit 8 (command code):
Configuration Short designation Default
Selection of mean value generation (filtering) Filter 16-sample mean value
Characteristic for calculating the gain (see "Startup/measuring jumper
detuning" on page 21)
Characteristic ±2 mV/V
OUT1
Bit 1514131211109876543210
Assignment
Command code 00000000
Bit 15 to bit 8 OUT1 Command function
0 0 0 0 0 0 0 0 0000
hex
Read measured values
0 0 0 1 0 0 0 C 1x00
hex
Read configuration channel-by-channel in IN2
(C = Channel number; 0 = Channel 1, 1 = Channel 2)
0 0 1 1 0 0 0 0 3000
hex
Read min. value; IN2: Min. value channel 1, IN3: Min. value channel 2
0 0 1 1 0 0 0 1 3100
hex
Read max. value; IN2: Max. value channel 1, IN3: Max. value channel 2
0 0 1 1 0 0 1 0 3200
hex
Delete minimum and maximum value of channel 1
0 0 1 1 0 0 1 1 3300
hex
Delete minimum and maximum value of channel 2
0 0 1 1 1 1 0 03C00
hex
Read firmware version and module ID in IN2.
0 1 0 0 0 0 0 0 4000
hex
Configure device;
configuration for channel 1 in OUT2 and for channel 2 in OUT3
During the transient response (e.g., following a configuration command), the fluctuating measured values may
exceed the minimum and maximum values. Therefore, at the start of acquisition delete the minimum and
maximum values using command 3200
hex
and/or 3300
hex
.
One measurement is performed for each bus cycle.