IB IL RS UNI(-2MBD)-PAC
8235_en_01 PHOENIX CONTACT 19
Byte 3 (D/DB: baud rate/data width)
Byte 4 and 5 (1st del, 2nd del: 1st and 2nd delimiters)
The 1st delimiter and 2nd delimiter contain the end characters
for the end-to-end and dual buffer protocols.
When selecting the end-to-end protocol, the two delimiters
can be adjusted.
Default settings:
Byte 6 (ErrP: error pattern)
The error pattern contains the character that is written to the
FIFO if a character was received with errors (e.g., in the event
of a parity error).
The error pattern is used for the following protocols:
Transparent
–End-to-end
XON/XOFF
Baud rate
Code [hex] Wert [baud]
0110
1300
2600
3 1200
4 1800
5 2400
6 4800
7 9600
8 15625
9 19200
A 38400
B 57600
C 115200
D 230400
E 250000
F Direct (Uni1 ... 3)
The specified baud rates of 110baud to
250000baud are adequate for most applica-
tions. However, you can freely choose the
baud rate by direct programming. For this, use
the 0F
hex
baud rate code.
Data width
Code [hex] Meaning
- Data bits Parity Stop bits
07 Even 1
17 Odd 1
28 Even 1
38 Odd 1
48 Without 1
57 Without 1
67 Even 2
77 Odd 2
88 Even 2
98 Odd 2
A8 Without 2
B7 Without 2
C8Constantly at 01
D8Constantly at 11
E6 Without 1
FDirectly
(Uni1)
The specified combinations of data width, pari-
ty and stop bits are adequate for most applica-
tions. However, you can freely choose the
combination by direct programming. For this,
use the 0F
hex
data width code.
Delimiter Default
value
ASCII character
1st del 0D
hex
CR = carriage return
2nd del 0A
hex
LF = line feed
Error pattern
Code [hex] Meaning
24 $
xx Any character
00 If a character is received with an error, no
error pattern is stored.
FF The invalid character is stored instead of
the error pattern.
IB IL RS UNI(-2MBD)-PAC
8235_en_01 PHOENIX CONTACT 20
Byte 7 ... 9 (Uni1 ... Uni3: universal byte 1 ... 3)
These bytes can be used as universal bytes for direct specifi-
cation of the baud rate or the data width.
Direct specification of baud rate
If the provided baud rates do not correspond to the desired
baud rate, the baud rate can be directly specified. For this,
write the desired baud rate on the Uni1 to Uni3 fields in the
form of a numeric value. Transfer is right-aligned. However,
only the 2 lower bits of Uni1 are permitted.
The maximum value is 18bits. The maximum value =
3FFFF
hex
which corresponds to 262143baud.
Direct specification of the data width
If the provided combinations of data width, parity and stop bits
are inadequate, they can be directly specified. Use the Uni1
byte. Bit 1 and bit 0 are reserved.
Example for direct specification of the baud rate:
Baud rate: 100000 baud
100000
dec
= 01 86 A0
hex
Byte 7 Byte 8 Byte 9
765432107 ... 07 ... 0
Data width Baud rate
76 5 4 3 21 0
Parity Enable parity Stop
bits
Data bits res. res.
Parity
Code [bin] Meaning
00 Odd
01 Even
10 Constantly at 1
11 Constantly at 0
Enable parity
Code [bin] Meaning
0Disable
1Enable
Stop bits
Code [bin] Meaning
01 stop bit
12 stop bits
Data bits
Code [bin] Meaning
00 5 bits
01 6 bits
10 7 bits
11 8 bits
Word0123456
Byte112345678910111213
OUT 40
hex
xx
hex
T/P B/DB res. res. ErrP Uni1 Uni2 Uni3 res. res. Tv Tn
OUT 40
hex
xx
hex
xx Fx
hex
00 00 xx 01 86 A0 00 00 xx xx
IB IL RS UNI(-2MBD)-PAC
8235_en_01 PHOENIX CONTACT 21
Byte 12 und 13 (Tv, Tn: lead time, lag time)
These two times are used for the RS-232 protocol
The times are specified with a resolution of 1ms. This allows
for waiting times of 1ms ... 255ms.
When transmitting data via RS-232 the RTS signal is set. If Tv
does not equal 0, transmission only starts after this time has
elapsed. After all the data is sent and Tn does not equal 0, the
RTS signal is only set to LOW after this time has elapsed.
15 PCP communication
15.1 General information
By default upon delivery, the terminal is configured according
to the default settings (under configuration). The terminal can
be configured using process data or PCP to suit your applica-
tion.
In PCP mode, the terminal is configured with the "Config Ta-
ble" object.
Tv Lead time
Tn Lag time
For information on PCP communication,
please refer to the PCP user manuals (see Or-
dering data).
The programs IBS CMD (for standard control-
ler boards) and PC WorX (for Controllers (ILC),
Field Controllers (FC) and Remote Field Con-
trollers (RFC)) are available for the configura-
tion and parameterization of your INTERBUS
system.
For additional information, please refer to the
documentation of the software used.