IB IL RS UNI(-2MBD)-PAC
8235_en_01 22
PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany
www.phoenixcontact.com
15.2 Object dictionary for PCP communication
15.3 "Config Table" object
Configure the terminal using this object.
Access this object via subindex 0, i.e., read or write the entire
project.
The first twelve bytes correspond to byte 2 through byte 13 of
the "Write configuration" command. The other four bytes are
reserved.
If an invalid configuration is specified, a negative confirmation
is generated with error message 08
hex
, 00
hex
or xx30
hex
. The
low byte of the Additional_Error_Code is 30
hex
(value is out of
range), the high byte contains the number of the affected
byte.
Index Data type A L Meaning Object name Rights
0080
hex
Record 1 16 Terminal configuration Config Table rd/wr
A Number of elements rd Read access permitted
L Length of an element in bytes wr Write access permitted
Byte Meaning Default value
0 Type, protocol 00
hex
1 Baud rate, data width 72
hex
2 1st delimiter 0D
hex
3 2nd delimiter 0A
hex
4 Error pattern 24
hex
5 ... 7 Uni1 ... Uni3 00 00 00
hex
8, 9 Reserved 00 00
hex
10 Tv 00
hex
11 Tn 00
hex
12 ... 15 Reserved 00 00 00 00
hex

2700893

Mfr. #:
Manufacturer:
Phoenix Contact
Description:
Controllers IB IL RS UNI-PAC
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union

Products related to this Datasheet