14 Parameterization
PC Worx
Parameterization of the PROFINET device in PCWorx re-
quires at least PCWorx Version 6.30. This is part of the
AUTOMATIONWORX Software Suite 1.80 and 1.81.
An online data sheet of the device with important technical
data and a configuration file are integrated into PCWorx. If
several versions of the configuration file are available, make
sure that you are working with the file version that corre-
sponds to the firmware/hardware version used.
Other tools
The PROFINET device is parameterized using the configu-
ration tool of the PROFINET controller. Please integrate the
corresponding GSDML file of the bus coupler into the rele-
vant software tool (STEP7/HW Config, ...).
15 Device replacement
Devices can be replaced without having to reconfigure them
within the PROFINET network. The station name and ad-
dress are assigned by the control system to the newly added
PROFINET bus coupler using the neighborhood detection
function.
16 Phoenix Redundancy Layer (PRL)
The Phoenix Redundancy Layer (PRL) makes it possible to
design a redundant system with two PROFINET controllers.
One controller is configured as the primary I/O controller and
the other as the backup I/O controller. Depending on which
PROFINET controller provides valid values, the bus coupler
operated at field level adopts these values or uses failsafe
values.
17 Dynamic configuration on the local
bus
You can use the "Dynamic configuration" function with this
bus coupler.
Dynamic configuration is the specification and configuration
of a maximum configuration. Any subgroup of this maximum
configuration can be operated.
18 Substitute value behavior
If Ethernet communication fails or an error occurs in the local
bus, all outputs of the station are set to the substitute values
previously parameterized on the module.
In order to do this, plug and play mode must be deactivated
and the process data watchdog must be activated.
19 Simple Network Management Pro-
tocol - SNMP
The bus coupler supports SNMP v1 and v2c.
Management Information Base - MIB
For the object descriptions, please refer to the ASN1 de-
scriptions for this product.
The password for read access is “public” and cannot be
changed.
By default upon delivery, the password for write/read access
is “private” and can be modified at any time.
Make sure you always use the latest version
of the FDCML/GSDML file and the latest doc-
umentation for the bus coupler. The latest files
and documentation can be found on the Inter-
net at phoenixcontact.net/products.
PRL (or shared device) and MRP can be used
simultaneously if the PROFINET update time
is 8 ms and the PROFINET watchdog time is
> 200 ms.
For the possible substitute values of a mod-
ule, please refer to the relevant module-spe-
cific data sheet.
The corresponding latest MIBs are available
on the Internet at phoenixcontact.net/prod-
ucts.