105731_en_04 PHOENIX CONTACT 13
Open the bus configuration workspace.
In the “Bus Structure” window, select the bus coupler.
In the “Device Details” window, select the “Module Set-
tings” tab.
Read the node ID (decimal) of the bus coupler and en-
ter it in hexadecimal form at the ID input of the function
block.
The read service is sent on a rising edge at the REQ input of
the function block. If the VALID output is TRUE, the re-
sponse to the service is stored in I/O variable RECORD.
The diagnostic status register is located in byte 0 and byte 1.
In the example, the following response is stored in variable
RECORD:
In this example, the diagnostic status register has the value
00E0
hex
(0000 0000 1110 0000
bin
). Bits 5, 6, and 7 are
TRUE. This means that data cycles are being exchanged,
the configuration is active, and the local bus master is ready.
11 Diagnostic alarms
PROFINET enables the PROFINET device to store diagnos-
tic information together with the error location and error type.
In the default upon delivery the alarms are enabled, how-
ever, they can be disabled with parameters on startup.
An incoming alarm informs the PROFINET controller that di-
agnostic information has been stored.
When the diagnostic information has been removed, an out-
going alarm is transmitted to the controller.
If at least one piece of diagnostic information is stored, the
SF LED is on. If no diagnostic information is present, the SF
LED is off.
12 Startup
Default upon delivery/default settings
By default upon delivery, the following functions and fea-
tures are available:
Firmware started
Once you have supplied the bus coupler with power or
pressed the reset button, the firmware is started. After com-
pletion of the firmware boot process the BF LED is either on
or flashing.
Please note:
The node ID is generated automatically by
PCWorx and may therefore vary in different
projects.
Record
[1] 16#00
[2] 16#E0
[3] 16#00
[4] 16#00
[5] 16#00
[6] 16#00
[7] 16#00
[8] 16#00
[9...15] 16#00
PROFINET name: No name assigned
IP parameters: 0.0.0.0
Module designation: AXL F BK PN
Vendor ID: 00B0
hex
Device ID: 1000
hex
AXL F BK PN
105731_en_04 PHOENIX CONTACT 14
Reset button
The reset button is located beneath the top marking label on
the bus coupler.
Figure 7 Reset button
1 Labeling field
2 Reset button
The reset button has two functions:
Restarting the bus coupler
Resetting of the default settings
Holding down the button during the initialization phase re-
stores the default settings.
If you wish to restore the default settings, proceed as fol-
lows:
Disconnect the power to the module.
Press and hold the reset button.
Switch on the power.
The LEDs indicate the initialization phase:
When the RDY LED lights up green, release the button.
The default settings are restored.
Documentation
13 Service interface
The service interface is located beneath the top marking
field on the bus coupler.
Figure 8 Service interface
1 Labeling field
2 Service interface
You can connect the bus coupler to a PC on which the
Startup+ startup/diagnostic tool is running via USB using the
service interface.
Startup+ offers the following functions:
Parameterization of the station I/O modules
–I/O check
–Diagnostics
LED State Meaning
RDY OFF Starting firmware
RDY Yellow ON Initializing firmware
RDY Green Initialization complete
2
1
How to assign the PROFINET names and the
IP address as well as how to startup a device
within a PROFINET system is described in the
following documents:
- "PC WORX" quick start guide
- "Configuring INTERBUS devices in a
PROFINET network using the example of
STEP 7" quick start guide
For the order designations, please refer to the
ordering data.
The documentation can be found on the Inter-
net at phoenixcontact.net/products.
For detailed information on Startup+, please
refer to the UMQSENSTARTUP+ user man-
ual.
2
1
AXL F BK PN
105731_en_04 PHOENIX CONTACT 15
14 Parameterization
PC Worx
Parameterization of the PROFINET device in PCWorx re-
quires at least PCWorx Version 6.30. This is part of the
AUTOMATIONWORX Software Suite 1.80 and 1.81.
An online data sheet of the device with important technical
data and a configuration file are integrated into PCWorx. If
several versions of the configuration file are available, make
sure that you are working with the file version that corre-
sponds to the firmware/hardware version used.
Other tools
The PROFINET device is parameterized using the configu-
ration tool of the PROFINET controller. Please integrate the
corresponding GSDML file of the bus coupler into the rele-
vant software tool (STEP7/HW Config, ...).
15 Device replacement
Devices can be replaced without having to reconfigure them
within the PROFINET network. The station name and ad-
dress are assigned by the control system to the newly added
PROFINET bus coupler using the neighborhood detection
function.
16 Phoenix Redundancy Layer (PRL)
The Phoenix Redundancy Layer (PRL) makes it possible to
design a redundant system with two PROFINET controllers.
One controller is configured as the primary I/O controller and
the other as the backup I/O controller. Depending on which
PROFINET controller provides valid values, the bus coupler
operated at field level adopts these values or uses failsafe
values.
17 Dynamic configuration on the local
bus
You can use the "Dynamic configuration" function with this
bus coupler.
Dynamic configuration is the specification and configuration
of a maximum configuration. Any subgroup of this maximum
configuration can be operated.
18 Substitute value behavior
If Ethernet communication fails or an error occurs in the local
bus, all outputs of the station are set to the substitute values
previously parameterized on the module.
In order to do this, plug and play mode must be deactivated
and the process data watchdog must be activated.
19 Simple Network Management Pro-
tocol - SNMP
The bus coupler supports SNMP v1 and v2c.
Management Information Base - MIB
For the object descriptions, please refer to the ASN1 de-
scriptions for this product.
The password for read access is “public” and cannot be
changed.
By default upon delivery, the password for write/read access
is “private” and can be modified at any time.
Make sure you always use the latest version
of the FDCML/GSDML file and the latest doc-
umentation for the bus coupler. The latest files
and documentation can be found on the Inter-
net at phoenixcontact.net/products.
PRL (or shared device) and MRP can be used
simultaneously if the PROFINET update time
is 8 ms and the PROFINET watchdog time is
> 200 ms.
For the possible substitute values of a mod-
ule, please refer to the relevant module-spe-
cific data sheet.
The corresponding latest MIBs are available
on the Internet at phoenixcontact.net/prod-
ucts.