AXL F BK PN
105731_en_04 PHOENIX CONTACT 5
Interface AxiolineFlocal bus
Connection method Bus base module
Transmission speed 100 MBit/s
Interface Service
Number 1
Connection method Micro USB type B
System limits
Number of supported devices max. 63 (per station)
NOTE: Electronics may be damaged when overloaded
Observe the logic current consumption of each device when configuring an AxiolineF station. It is specified in every module-specific data
sheet. The current consumption can differ depending on the individual module. The permissible number of devices that can be connected
therefore depends on the specific station structure.
PROFINET
Device function PROFINET device
Protocols supported
Protocols supported PROFINET, FTP, TFTP, PTCP, LLDP, SNMP, MRP, DDI, BootP
Supply of the bus coupler
Supply of communications power U
L
24 V DC
Maximum permissible voltage range 19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current supply at U
Bus
2 A
Current consumption from U
L
typ. 105 mA (without I/Os and U
L
= 24 V)
max. 570 mA (with 2A at U
Bus
for the I/Os and U
L
= 24 V)
Power consumption at U
L
typ. 2.5 W (without I/Os)
max. 13.7 W (with 2A load at U
Bus
for the I/Os)
NOTE: Electronics may be damaged when overloaded
Provide external fuses for the 24 V U
L
area. The power supply unit must be able to supply four times the nominal current of the external fuse
to ensure that it blows in the event of an error.
Digital inputs
Connection method Push-in connection
Input voltage range "0" signal
Input voltage range "1" signal
Error messages to the higher level control or computer system
None
Mechanical tests
Vibration resistance in acc. with EN60068-2-6/IEC60068-2-6 5g
Shock in acc. with EN60068-2-27/IEC60068-2-27 30g
Continuous shock according to EN60068-2-27/IEC60068-2-27 10g
Conformance with EMC Directive 2004/108/EC
Noise immunity test in accordance with EN 61000-6-2
Electrostatic discharge (ESD) EN61000-4-2/IEC61000-4-2 Criterion B, 6 kV contact discharge, 8 kV air discharge
Electromagnetic fields EN61000-4-3/IEC61000-4-3 Criterion A; Field intensity: 10 V/m
Fast transients (burst) EN61000-4-4/IEC61000-4-4 Criterion B, 2kV
Transient overvoltage (surge) EN61000-4-5/IEC61000-4-5 Criterion B, DC supply lines: ±0.5 kV/±0.5 kV (symmetrical/asymmetrical), field-
bus cable shield: ±1 kV