AXL F BK PN
105731_en_04 PHOENIX CONTACT 7
5 Internal circuit diagram
Figure 1 Internal wiring of the terminal points
Key:
24 V
3.3 V
U
Bus
UL
U
24 V
L
Service
Reset
FE
C
D
E
RDY
BF
SF
U
Bus
Local bus
FE
PROFINET
5V
3.3V
RJ45
RJ45
FE Functional earth ground
Service Service interface
Reset Reset button
Local bus AxiolineF local bus
(hereinafter referred to as local bus)
RJ45 interface
Power supply unit with electrical isolation
Microcontroller
Power supply unit
LED
Electrically isolated area
RJ45
µC
XXX
XXX
AXL F BK PN
105731_en_04 PHOENIX CONTACT 8
6 Connecting PROFINET and supply
6.1 Connecting PROFINET
Connect PROFINET to the bus coupler via an 8-pos. RJ45
connector.
Figure 2 Pin assignment of the Ethernet socket (RJ45)
Only one twisted pair cable with an impedance of 100Ω may
be connected to each Ethernet interface in RJ45 format. The
data transmission speed is 100Mbps. The 100Base-TX port
of the bus coupler is able to detect a pair of incorrectly con-
nected receive cables (RD+/RD-) and to correct them using
the auto polarity correction function.
For the pin assignment, please refer to the following table:
6.2 Connecting the supply voltage - terminal point
assignment
Figure 3 Terminal point assignment
7 Connection example
Figure 4 Connection of the cables
Pin Assignment
1TxD + (transmit data+)
2 TxD - (transmit data-)
3RxD+ (receive data +)
4 Reserved
5 Reserved
6 RxD- (receive data -)
7 Reserved
8 Reserved
Auto crossover
Both Ethernet interfaces are provided with the
auto crossover function.
Shielding
The shielding ground of the connected twist-
ed pair cables is electrically connected with
the socket. When connecting network seg-
ments, avoid ground loops, potential trans-
fers, and voltage equalization currents via the
braided shield.
RJ45
Pin 1
Pin 2
Pin 3
Pin 4
Pin 5
Pin 6
Pin 7
Pin 8
Observe bending radii
The housing dimensions specified under "Di-
mensions" refer to the bus coupler with I/O
connectors without Ethernet connection.
When installing the bus coupler in a control
box, observe the bending radii of the Ethernet
cables and the connectors used (e.g.,
FLCAT5FLEX: 30mm for fixed installation
and FLCAT5HEAVY: 30mm without outer
sheath and 45mm with outer sheath). If re-
quired, use angled RJ45 connectors to main-
tain these bending radii.
Termi-
nal
point
Color Assignment
Supply voltage input
a1, a2 Red 24 V DC
(U
L
)
Supply of the logic voltage
(internally jumpered)
b1, b2 Blue GND Reference potential of the
supply voltage (internally
jumpered)
a1
a2
b1
b2
a1
a2
b1
b2
LNK
X1
UL
24V DC
(U )
L
+
-
BF
SF
RDY
D
E
Ethernet
LNKACT
ACT
X2
AXL F BK PN
105731_en_04 PHOENIX CONTACT 9
8 Local status and diagnostic indicators
Figure 5 Local status and diagnostic indicators
UL
BF
SF
RDY
D
E
Designation Color Meaning State Description
UL Green U
Logic
ON Communications power supply present.
OFF Communications power supply not present.
BF Red Communica-
tion error (Bus-
Fail)
ON No link status available on any port
Flashing SF LED not flashing: Link status available, no communication con-
nection to the PROFINET controller
Flashing SF flashing: Hardware watchdog triggered
OFF A PROFINET controller has established an active communication
connection to the PROFINET device.
SF Red System failure
(PROFINET)
ON PROFINET diagnostics available
OFF PROFINET diagnostics not available
Flashing Flashes only together with the BF LED; watchdog triggered
RDY Green/
yellow/
red
Ready Green
ON
Device is ready for operation.
Flashing
green/
yellow
Communications power undervoltage or surge voltage
Overtemperature
Flashing
green,
LED D
yellow on
Device is in standby mode.
Yellow
ON
Firmware/bus coupler is booting
Yellow
flashing
Firmware update is being performed.
Flashing
yellow/
red
Firmware update has failed.
Flashing
red
Faulty firmware
OFF Device is not ready for operation.