6 Local status and diagnostic indicators
Figure 3 Local status and diagnostic indicators
Designation Color Meaning State Description
LNK 1/2 green Link port 1/2 ON Connection via Ethernet to a module via port 1/2 established
 Flashing PROFINET module identification ("flashing")
 OFF No connection established via port 1/2
FO 1/2 yellow Status of the fiber
optic path:
ON Receiving power under 0 dB; the "Maintenance demanded"
message is triggered.
 Flashing Borderline receiving power; the "Maintenance required" mes-
sage is triggered.
 OFF Receiving power is OK
ACT 1/2 yellow Activity port 1/2 ON Transmission or reception of Ethernet telegrams at port 1/2
 OFF No transmission or reception of Ethernet telegrams at port 1/2
BF red Communication
error (BusFail)
ON No link status available
 Flashing Link status available, no communication connection to the
PROFINET controller
 OFF A PROFINET controller has established an active communi-
cation connection to the PROFINET device.
SF red System failure
(PROFINET)
ON PROFINET diagnostics available
 OFF PROFINET diagnostics not available
UL green U
Logic
ON 24 V bus coupler supply/7.5 V communications power present
 OFF 24 V bus coupler supply/7.5 V communications power not
present
US green U
Segment
ON 24 V segment circuit supply present
 OFF 24 V segment circuit supply not present
UM green U
Main
ON 24V main circuit supply/internal communications power pres-
ent
 OFF 24V main circuit supply/internal communications power pres-
ent
D green Diagnostics ON Data transmission active within the station
 Flashing Data transmission not active within the station
IL PN BK DI8 DO4 2SCRJ-PAC
7649_en_04 PHOENIX CONTACT 11
7 Diagnostic indicators for PROFINET
States during operation
States in the event of an error
EredError ON I/O error, short-circuit/overload of outputs
 OFF No I/O error
1 ... 4 yellow O1 ON/OFF Output is set/not set.
1 ... 8 yellow I1, I2 ON/OFF Input is set/not set.
Designation Color Meaning State Description
LED Meaning
SFOFF/BFOFF PROFINET controller was able to establish communication without errors.
LED Meaning Measure/remedy in the event of an
error
SFOFF/BFflashing The logic communication connection has
been interrupted. The PROFINET control-
ler can no longer be accessed.
Check the connection between the
PROFINET controller and the PROFINET
device. Make sure that the PROFINET de-
vice name of the PROFINET device is
identical with the configuration.
SFOFF/BFflashing The PROFINET device is not assigned a
PROFINET device name.
Assign the PROFINET device name using
the relevant tool.
SFOFF/BFON The physical communication path has
been interrupted. The PROFINET control-
ler can no longer be accessed.
Restore the physical connection between
the PROFINET controller and the
PROFINET device.
SFON/BFOFF Diagnostic data is available. Read the diagnostic message using the
relevant tool.
SFflashing/ BFflashing Hardware watchdog has been triggered.
IL PN BK DI8 DO4 2SCRJ-PAC
7649_en_04 PHOENIX CONTACT 12
8 Connection of PROFINET, power
supply, actuators, and sensors
8.1 Connecting PROFINET
Connect PROFINET to the bus coupler via an SCRJ plug.
Figure 4 Connecting PROFINET via SCRJ plug
Observe bending radii
The housing dimensions specified under "Di-
mensions" refer to the bus coupler with I/O
connectors without Ethernet connection.
When installing the bus coupler in a control
box, observe the bending radii of the cables
and the connectors used.
UL
US
UM
BF
SF
P
WR
DE
O1
LN
K
LNK
FO
FO
A
CT
AC
T
R
eset
1
3
2
4
I1
1
3
2
4
I2
65
8
7

2878379

Mfr. #:
Manufacturer:
Phoenix Contact
Description:
I/O Modules IL PN BK DI8 DO4 2SCRJ-PAC
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union

Products related to this Datasheet