IL PN BK DI8 DO4 2SCRJ-PAC
7649_en_04 PHOENIX CONTACT 5
Interface PROFINET
Number 2
Connection method SCRJ socket
Transmission speed 100 MBit/s (acc. to PROFINET standard)
Wavelength 660 nm
Laser protection Class 1 according to DINEN60825-1
Transmission length incl. 3 dB system reserve min. 50 m (Polymer fiber with F-K 980/1000 230 dB/km at 100 Mbps)
Interface Inline local bus
Connection method Inline data jumper
Transmission speed 500 kBit/s / 2 MBit/s (Automatic detection, no combined system)
System limits
Amount of process data max. 488 Byte (Max. 244 bytes IN - max. 244 bytes OUT)
IN process data for I/O modules that can be aligned 244 Byte
OUT process data for I/O modules that can be aligned 244 Byte
Number of supported devices max. 63 (per station)
Number of local bus devices that can be connected max. 61 (On board I/Os are two devices)
Number of devices with parameter channel max. 16
Observe the logic current consumption of each device when configuring an Inline station! It is specified in every terminal-specific data sheet.
The current consumption can differ depending on the individual terminal. The permissible number of devices that can be connected therefore
depends on the specific station structure.
PROFINET
Device function PROFINET device
Conformance class B
Update rate min. 1 ms (depending on the size of the bus system)
Power supply for module electronics
Connection method Spring-cage connection
Name Bus coupler supply U
BC
; Communications power U
L
(7.5V) and the analog sup-
ply U
ANA
(24 V) are generated from the bus coupler supply.
Supply voltage 24 V DC (via Inline plug)
Supply voltage range 19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current consumption typ. 250 mA (from U
BK
)
max. 0.83 A DC (from U
BK
)
Power loss typ. 3 W (Entire device)
Power consumption
NOTE: Electronics may be damaged when overloaded
Provide external fuses for the 24V areas U
BK
, U
M
, and U
S
. The power supply unit must be able to supply four times the nominal current of the
external fuse, to ensure that it trips in the event of an error.
Main circuit supply U
M
24 V DC
Supply voltage range U
M
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Power supply at U
M
max. 8 A DC (Sum of U
M
+ U
S
; 4A, maximum, when used in potentially explosive
areas.)
Current consumption from U
M
max. 8 A DC
Segment supply voltage U
S
24 V DC
Supply voltage range U
S
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Power supply at U
S
max. 8 A DC (Sum of U
M
+ U
S
; 4A, maximum, when used in potentially explosive
areas.)
Current consumption from U