IL PN BK DI8 DO4 2SCRJ-PAC
7649_en_04 PHOENIX CONTACT 4
Documentation Type Order No. Pcs. / Pkt.
User manual, English, Automation terminals of the Inline product range IL SYS INST UM E - -
Quick Start Guide, English, for PC Worx UM QS EN PC WORX - -
Quick Start Guide, English, for planning INTERBUS devices in a
PROFINET network
UM QS EN PROFINET PROXY IB - -
User manual, English, for the Modular Managed Switch System FL SWITCH MM HS UM E - -
Application note, English, Inline terminals for use in zone2 potentially ex-
plosive areas
AH EN IL EX ZONE 2 - -
Application note, German/English, I/O modules at bus couplers AH IL BK IO LIST - -
Application note, English, Firmware update for devices supporting a TFTP
firmware update
AH EN TFTP FIRMWARE UPDATE - -
User manual, English, PROFINET basics UM EN PROFINET SYS - -
Dimensions (nominal sizes in mm)
Width 80 mm
Height 119.8 mm
Depth 71.5 mm
Note on dimensions Specfications with male connectors
4 Technical data
119,8
71,5
General data
Color green
Weight 280 g (with male connectors)
Ambient temperature (operation) -25 °C ... 55 °C (observe derating)
Ambient temperature (storage/transport) -40 °C ... 85 °C
Permissible humidity (operation) 10 % ... 95 % (according to DIN EN 61131-2)
Permissible humidity (storage/transport) 10 % ... 95 % (according to DIN EN 61131-2)
Air pressure (operation) 80 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport) 70 kPa ... 106 kPa (up to 3000 m above sea level)
Degree of protection IP20
Protection class III, IEC 61140, EN 61140, VDE 0140-1
Connection data
Name Inline connectors
Connection method Spring-cage connection
Conductor cross section solid / stranded 0.08 mm² ... 1.5 mm² / 0.08 mm² ... 1.5 mm²
Conductor cross section [AWG] 28 ... 16
IL PN BK DI8 DO4 2SCRJ-PAC
7649_en_04 PHOENIX CONTACT 5
Interface PROFINET
Number 2
Connection method SCRJ socket
Transmission speed 100 MBit/s (acc. to PROFINET standard)
Wavelength 660 nm
Laser protection Class 1 according to DINEN60825-1
Transmission length incl. 3 dB system reserve min. 50 m (Polymer fiber with F-K 980/1000 230 dB/km at 100 Mbps)
Interface Inline local bus
Connection method Inline data jumper
Transmission speed 500 kBit/s / 2 MBit/s (Automatic detection, no combined system)
System limits
Amount of process data max. 488 Byte (Max. 244 bytes IN - max. 244 bytes OUT)
IN process data for I/O modules that can be aligned 244 Byte
OUT process data for I/O modules that can be aligned 244 Byte
Number of supported devices max. 63 (per station)
Number of local bus devices that can be connected max. 61 (On board I/Os are two devices)
Number of devices with parameter channel max. 16
Observe the logic current consumption of each device when configuring an Inline station! It is specified in every terminal-specific data sheet.
The current consumption can differ depending on the individual terminal. The permissible number of devices that can be connected therefore
depends on the specific station structure.
PROFINET
Device function PROFINET device
Conformance class B
Update rate min. 1 ms (depending on the size of the bus system)
Power supply for module electronics
Connection method Spring-cage connection
Name Bus coupler supply U
BC
; Communications power U
L
(7.5V) and the analog sup-
ply U
ANA
(24 V) are generated from the bus coupler supply.
Supply voltage 24 V DC (via Inline plug)
Supply voltage range 19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current consumption typ. 250 mA (from U
BK
)
max. 0.83 A DC (from U
BK
)
Power loss typ. 3 W (Entire device)
Power consumption
NOTE: Electronics may be damaged when overloaded
Provide external fuses for the 24V areas U
BK
, U
M
, and U
S
. The power supply unit must be able to supply four times the nominal current of the
external fuse, to ensure that it trips in the event of an error.
Main circuit supply U
M
24 V DC
Supply voltage range U
M
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Power supply at U
M
max. 8 A DC (Sum of U
M
+ U
S
; 4A, maximum, when used in potentially explosive
areas.)
Current consumption from U
M
max. 8 A DC
Segment supply voltage U
S
24 V DC
Supply voltage range U
S
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Power supply at U
S
max. 8 A DC (Sum of U
M
+ U
S
; 4A, maximum, when used in potentially explosive
areas.)
Current consumption from U
S
max. 8 A DC
IL PN BK DI8 DO4 2SCRJ-PAC
7649_en_04 PHOENIX CONTACT 6
Communications power U
L
7.5 V DC ±5 %
Power supply at U
L
max. 0.8 A DC
I/O supply voltage U
ANA
24 V DC
Supply voltage range U
ANA
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Power supply at U
ANA
max. 0.5 A DC
Power consumption
Digital inputs
Number of inputs 8 (EN 61131-2 type 1)
Connection method Inline plugs
Connection method 2, 3-wire
Input characteristic curve IEC 61131-2 type 1
Nominal input voltage 24 V DC
Nominal input current typ. 3 mA
Current flow Limited to 3mA, maximum
Input voltage range "0" signal -30 V DC ... 5 V DC
Input voltage range "1" signal 15 V DC ... 30 V DC
Delay at signal change from 0 to 1 typ. 5 ms
Delay at signal change from 1 to 0 typ. 5 ms
Permissible conductor length to the sensor 100 m
Protection against polarity reversal Suppressor diode
Digital outputs
Number of outputs 4
Connection method Inline plugs
Connection method 2, 3-wire
Nominal output voltage 24 V DC
Maximum output current per channel 500 mA
Nominal load, ohmic 12 W
Nominal load, inductive 12 VA (1.2 H; 48 )
Nominal load, lamp 12 W
Signal delay typ. 1.2 ms
Signal delay when switching on an ohmic nominal load max. 50 µs (In the case of 0.5 A load)
Signal delay when switching off an ohmic nominal load max. 250 µs (In the case of 0.5 A load)
Maximum operating frequency with inductive nominal load 0.5 Hz (1.2 H; 48 )
Reaction time with short-circuit 1,2 ms
Behavior at voltage switch-off The output follows the power supply without delay
Limitation of the voltage induced on circuit interruption approx. -30 V
Output current when switched off max. 10 µA (When not loaded, a voltage can be measured even at an output that
is not set.)
Behavior with overload Auto restart
Behavior with inductive overload Output can be destroyed
Reverse voltage resistance to short pulses Reverse voltage proof
Resistance to permanent reverse voltage max. 2 A
Overcurrent shut-down min. 0.7 A
Short-circuit and overload protection Free running circuit In output driver
Fieldbus data telegram
IN process data for I/O modules that can be aligned 244 Byte
OUT process data for I/O modules that can be aligned 244 Byte

2878379

Mfr. #:
Manufacturer:
Phoenix Contact
Description:
I/O Modules IL PN BK DI8 DO4 2SCRJ-PAC
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union

Products related to this Datasheet