AXL F DO8/2 2A 1H
8238_en_04 PHOENIX CONTACT 13 / 14
Error and status of the local diagnostics and status indicators
The behavior of LEDD during an "Actuator supply not present" error depends on whether you have switched error reporting
via the FF8F
hex
object on or off.
12.4 Objects for process data management
The objects 003B
hex
and 003C
hex
are only applicable to tools.
OUT process data (0026
hex
: PDOUT)
You can read the OUT process data of the module with this object.
The structure corresponds to the representation in the "Process data" section.
Subindex 2 3 4
Error Priority Channel/
group/
module
Error
code
LED
hex hex hex D U
O
E1 xx
No error 00 00 0000 Green ON ON OFF OFF
Short-circuit/overload of an output 02 FF 2344 Green ON ON Red ON Red ON
Actuator supply not present 01 FF 3422 flashing green or
green/yellow
OFF OFF OFF
xx LED Diagnostics of the output
xx 00 ... 03, 20 ... 23
Parameterization in FF8F
hex
D LED
Do not report error to the controller green
Report error to the controller Flashing green/yellow
Index
(hex)
Object name Object
type
Data type A L Rights Assignment
0026 PDOUT Var Octet string 1 2 R Output process data
003B PDIN_Descr Array of
Records
3 8; 2; 2 R Description of the IN process data
003C PDOUT_Descr Array of
Records
3 8; 2; 2 R Description of the output process data
0026
hex
: PDOUT (read)
Subindex Data type Length in bytes Meaning
0 Octet string 2 Output process data
AXL F DO8/2 2A 1H
8238_en_04 14 / 14
PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany
phoenixcontact.com
13 Application objects
In the case of valid parameters, the parameterization is stored in the module permanently.
13.1 Substitute value behavior (FF8D
hex
: PD Output Substitute Configuration)
With this object, you parameterize the behavior of the module so that an application reset can be detected if necessary.
13.2 Message “Actuator supply not present” (FF8F
hex
: DiagOut)
With this object, you parameterize whether the “Actuator supply missing” error is reported to the controller or not.
If you parameterize the module so that the error is not reported to the controller, the corresponding indicator in LEDD
(flashing green/yellow) is suppressed and the LED lights up green.
14 Device descriptions
The device is described in the device description files.
The device descriptions for controllers from Phoenix
Contact are included in PC Worx and the corresponding
service packs.
The device description files for other systems are available
for download at phoenixcontact.net/products in the
download area of the bus coupler used.
Index
(hex)
Object name Object
type
Data type A L Rights Assignment
FF8D PD Output
Substitute
Configuration
Var Unsigned 8 1 1 R/W Substitute value behavior
FF8F DiagOut Var Unsigned 8 1 1 R/W Message “Actuator supply not
present”
FF8D
hex
: PD Output Substitute Configuration (Read, write)
Subindex Data type Length in bytes Contents
0Var100
hex
(Default) "0" output to all output bits
01
hex
Hold last value
FF8F
hex
: DiagOut (Read, write)
Subindex Data type Length in bytes Contents
0Var100
hex
(Default) Do not report error to the controller
01
hex
Report error to the controller

2688381

Mfr. #:
Manufacturer:
Phoenix Contact
Description:
Terminal Block Interface Modules AXL DO 8/2-2A
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union

Products related to this Datasheet