AXL F DO8/2 2A 1H
8238_en_04 14 / 14
PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany
phoenixcontact.com
13 Application objects
In the case of valid parameters, the parameterization is stored in the module permanently.
13.1 Substitute value behavior (FF8D
hex
: PD Output Substitute Configuration)
With this object, you parameterize the behavior of the module so that an application reset can be detected if necessary.
13.2 Message “Actuator supply not present” (FF8F
hex
: DiagOut)
With this object, you parameterize whether the “Actuator supply missing” error is reported to the controller or not.
If you parameterize the module so that the error is not reported to the controller, the corresponding indicator in LEDD
(flashing green/yellow) is suppressed and the LED lights up green.
14 Device descriptions
The device is described in the device description files.
The device descriptions for controllers from Phoenix
Contact are included in PC Worx and the corresponding
service packs.
The device description files for other systems are available
for download at phoenixcontact.net/products in the
download area of the bus coupler used.
Index
(hex)
Object name Object
type
Data type A L Rights Assignment
FF8D PD Output
Substitute
Configuration
Var Unsigned 8 1 1 R/W Substitute value behavior
FF8F DiagOut Var Unsigned 8 1 1 R/W Message “Actuator supply not
present”
FF8D
hex
: PD Output Substitute Configuration (Read, write)
Subindex Data type Length in bytes Contents
0Var100
hex
(Default) "0" output to all output bits
01
hex
Hold last value
FF8F
hex
: DiagOut (Read, write)
Subindex Data type Length in bytes Contents
0Var100
hex
(Default) Do not report error to the controller
01
hex
Report error to the controller